The HRDM Series combines an electromechanical relay output with microcontroller timing circuitry. It offers 12
to 230 V operation in five ranges and factory fixed, external, or onboard adjustable time delays with a repeat
accuracy of +/-0.5%. The output contact rating allows for direct operation of heavy loads such as compressors,
pumps, blower motors, heaters, etc. This series is ideal for OEM applications where cost is a factor.
Operation
Upon application of input voltage, the time delay
begins. The output is de-energized before and during
the time delay . At the end of the time delay, the output
relay energizes and remains energized until input
voltage is removed.
Reset: Removing input voltage resets the time delay
and output.
See accessory pages for
specifications.
HRDMGen 10.03.05
30 A SPDT N.O. Output
Contact
12 ... 230 V Operation in
5 Ranges
Encapsulated Circuitry
Delays from 100 ms ...100 m
in 5 Ranges
+/-0.5% Repeat Accuracy
Fixed, External, or Onboard
Adjustment
Approvals:
Delay On Make (Operate)
HRDM Power -Time
Time Delay Relay
Connection
Example P/N:
Function
B
Mounting bracket
P/N: P1023-6
Female quick
connect P/Ns:
P1015-64
(AWG 14/16)
P1015-13
(AWG 10/12)
Quick connect to
screw adaptor
P/N: P1015-18
External adjust
potentiometer
P/Ns:
P1004-95 (fig A)
P1004-95-X (fig B)
Versa-knob
P/N: P0700-7
DIN rail adaptor
P/N: P1023-20
A
DIN rail P/Ns:
017322005 (Steel)
V = Voltage L = Load R = Reset
TD = Time Delay
Delay On Make
NO
NC
C
NOTE: A knob, or terminals 4 & 5 are only included
on adjustable units. RT is used when external
adjustment is ordered. Relay contacts are not
isolated. Dashed lines are internal connections.
HRDM X X X X
1 - 12 V DC 1 -–A - +/-1% 0 - 0.1 ... 10 s
2 - 24 V AC 2 -Blank - +/-5% 1 - 1 ... 100 s
3 - 24 V DC 2 - 10 ... 1000 s
4 - 120 V AC 3 -3 - 0.1 ... 10 m
6 - 230 V AC 4 - 1 ... 100 m
Series Input Adjustment Time Tolerance Time Delay *
Fixed
Onboard
Knob
External
Adjust
* If Fixed Delay is selected, insert
delay [0.1 … 1000] followed by
(S) sec. or [0.1 ... 100] (M) min.
HRDM421 Fixed – HRDM41A0.5S
= Undefined time
C103PM (Al)
Ordering T able
NO = Normally Open L = Load
C = Common, Transfer Contact
Technical Data
Delay On Make (Operate)
HRDM Power-Time
Time Delay Relay
Low Voltage Products & Systems 5.9
Mechanical View
HRDMGen 10.03.05
Inches (Millimeters)
External Resistance vs Time Delay
Onboard Adjust Detail Replaces
Terminals if Ordered
Time Delay
Input
Output
Protection
Mechanical
Environmental
Type Microcontroller circuitry
Range 100 ms ... 100 m in 5 adjustable ranges or fixed
Repeat Accuracy +/-0.5% or 20 ms, whichever is greater
Tolerance (Factory Calibration) +/-1%, +/-5%
Reset Time 150 ms
Time Delay vs. Temperature & Voltage +/-2%
Voltage 12 or 24 V DC; 24, 120, or 230 V AC
Tolerance 12 V DC & 24 V DC -15% ... +20%
24 ... 230 V AC -20% ... +10%
Line Frequency 50 ... 60 Hz
Power Consumption AC 4 VA; DC 2 W
Type Electromechanical relay
Form SPDT, non-isolated
Ratings: SPDT-N.O. SPDT-N.C.
General Purpose 125/240 V AC 30 A 15 A
Resistive 125/240 V AC 30 A 15 A
28 V DC 20 A 10 A
Motor Load 125 V AC 1 hp* 1/4 hp**
240 V AC 2 hp** 1 hp**
Life Mechanical -- 1 x 106; Electrical -- 1 x 105, *3 x 104, **6,000
Surge IEEE C62.41-1991 Level A
Circuitry Encapsulated
Dielectric Breakdown 2000 V RMS terminals to mounting surface
Insulation Resistance 100 M
Polarity DC units are reverse polarity protected
Mounting Surface mount with one #10 (M5 x 0.8) screw
Package 3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1mm)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Operating / Storage Temperature -40°C ... +60°C / -40°C ... +85°C
Humidity 95% relative, non-condensing