9926 Series Branch Rated Circuit Breakers–AC Version
Circuit Breakers
Hydraulic Magnetic Type
Single pole and double pole versions
120/240 VAC, 50/60 Hz
Up to 25A
Just 13 mm wide
Mounts on 35mm DIN-rail
UL 489 listed, CSA C22.2 No. 5-02, CE
VDE
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
105
125
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve KM
Ambient Temperature 30°C
Trip Curves—Hydraulic Magnetic Type
Typical time/current characteristics at 30ºC
9926 Series–AC version Trip Curve
Ordering Data Type: Single Pole Type: Double Pole
Current Ratings Part No. Current Ratings Part No.
(amps) TS 35 Description (amps) TS 35 Description
0.5 9926251000 QL-1-13-DM-KM-0.5 0.5 9926252000 QL-2-13-DM-KM-0.5
19926251001 QL-1-13-DM-KM-01 1 9926252001 QL-2-13-DM-KM-01
29926251002 QL-1-13-DM-KM-02 2 9926252002 QL-2-13-DM-KM-02
39926251003 QL-1-13-DM-KM-03 3 9926252003 QL-2-13-DM-KM-03
49926251004 QL-1-13-DM-KM-04 4 9926252004 QL-2-13-DM-KM-04
59926251005 QL-1-13-DM-KM-05 5 9926252005 QL-2-13-DM-KM-05
69926251006 QL-1-13-DM-KM-06 6 9926252006 QL-2-13-DM-KM-06
79926251007 QL-1-13-DM-KM-07 7 9926252007 QL-2-13-DM-KM-07
89926251008 QL-1-13-DM-KM-08 8 9926252008 QL-2-13-DM-KM-08
10 9926251010 QL-1-13-DM-KM-10 10 9926252010 QL-2-13-DM-KM-10
13 9926251013 QL-1-13-DM-KM-13 13 9926252013 QL-2-13-DM-KM-13
15 9926251015 QL-1-13-DM-KM-15 15 9926252015 QL-2-13-DM-KM-15
16 9926251016 QL-1-13-DM-KM-16 16 9926252016 QL-2-13-DM-KM-16
20 9926251020 QL-1-13-DM-KM-20 20 9926252020 QL-2-13-DM-KM-20
25 9926251025 QL-1-13-DM-KM-25 25 9926252025 QL-2-13-DM-KM-25
9926 Series
Single Pole
9926 Series
Double Pole
Sample trip characteristics - KM
125% 150% 200% 400% 600% 800% 1000%
minimum 15 8 4 0.7 0.09 0.007 0.005
(sec)
maximum 300 90 28 4 1.5 0.6 0.4
(sec)
Although the 9926 series uses a magnetic only trip mechanism, CSA
testing indicates a trip characteristic similar to thermal magnetic trip
mechanisms. No de-rating is required at elevated temperatures.
Technical Data
Voltage 120/240 VAC, 50/60Hz
Current
minimum 0.5A
maximum 25A
Interrupting capacity 10,000A
Dielectric strength 1500V, 50/60Hz
Insulation resistance 100MM
Operating life 10000 mechanical operations
Operating temperature -40…+65°C
Wire size*
0.5-15A: 14AWG min., 10AWG max.
20-25A: 10AWG min.
Torque 20 in.-lb
Approval
UL 489 listed, CSA C22.2 No. 5-02, CE, VDE
Accessories Part No.
Bus-bar (1 pole, insulated, 1 m) 67101904
Bus-bar (2 pole, insulated, 1 m) 67101972
Bus-bar end cap, 1 pole 67101973
Bus-bar end cap, 2 pole 67101974
Power lug, straight 67101960
Power lug, 90° 67101961
Lock-out handle 67101913
*Wire sizes: gauges specified are the minimum allowable as per CSA
and UL standards.
The 9926 circuit breakers do not have provisions for marking tags.
A possible solution is to cut the adhesive SchS2 tag rail to length
(approximately 20 mm on a single pole unit so the current rating
remains visible or approximately 30 mm on a two pole unit).
The SchS2 accepts DEK, WS and ESG 8/17 marking tags.
The part number for adhesive SchS2 is 1720600000.
19
(0.75)
74
(2.91)
66
(2.6)
17.9
(0.7)
71.4
(2.81)
28.5
(1.12)
5
(0.2)
32
(1.26)
45
(1.77)
64.8
(2.55)
57
(2.24)
13
(0.51)
92.8
(3.65)
26
(1.02)
13
(0.51)
9926 Series AC Version - dimensions in mm (in.)
Additional trip curves and amp ratings are available
upon request.
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
105
130
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve 1
Ambient Temperature 30°C
9926 Series–AC version Trip Curve
Trip Curve 1 applies to the following part numbers where
"XX" is the current rating:
Single Pole— 99262512XX Double Pole— 99262522XX
4
9926 Series Branch Rated Circuit Breakers–AC Version with Contacts
Type: Double Pole Trip
Current
Ratings
(amps) Part No. Description
19926272001 QL-T-2-13-DM-KM-1
29926272002 QL-T-2-13-DM-KM-2
59926272005 QL-T-2-13-DM-KM-5
10 9926272010 QL-T-2-13-DM-KM-10
15 9926272015 QL-T-2-13-DM-KM-15
20 9926272020 QL-T-2-13-DM-KM-20
25 9926272025 QL-T-2-13-DM-KM-25
Type: Double Pole Combo
Current
Ratings
(amps) Part No. Description
19926282001 QL-AT-2-13-DM-KM-1
29926282002 QL-AT-2-13-DM-KM-2
59926282005 QL-AT-2-13-DM-KM-5
10 9926282010 QL-AT-2-13-DM-KM-10
15 9926282015 QL-AT-2-13-DM-KM-15
20 9926282020 QL-AT-2-13-DM-KM-20
25 9926282025 QL-AT-2-13-DM-KM-25
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
105
125
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve KM
Ambient Temperature 30°C
9926 Series–AC version Trip Curve
Circuit Breakers with
Auxiliary switch, Trip alarm,
Combination of both
AC voltages (120/240V)
Single and double pole versions
UL 489 and CSA listed
Factory fitted auxiliary or trip alarm
Compact 6.5mm width
Attached to right hand side of
circuit breaker
*Wire sizes: gauges specified are the minimum
allowable as per CSA and UL standards.
The 9926 circuit breakers do not have provisions for
marking tags. A possible solution is to cut the adhesive
SchS2 tag rail to length (approximately 20 mm on a
single pole unit so the current rating remains visible or
approximately 30 mm on a two pole unit). The SchS2
accepts DEK, WS and ESG 8/17 marking tags. The
part number for adhesive SchS2 is 1720600000.
Technical Data
Voltage 120/240 VAC, 50/60Hz
Current
minimum 0.5A
maximum 25A
Interrupting capacity 10,000A
Dielectric strength 1500V, 50/60Hz
Insulation resistance 100MM
Operating life 10000
mechanical operations
Operating temperature -40…+65°C
Wire size*
0.5-15A: 14AWG min., 10AWG max.
20-25A: 10AWG min.
Torque 20 in.-lb
Approval
UL 489 listed, CSA C22.2 No. 5-02, CE, VDE
9926 Series
Double Pole Trip
(Alarm Contact)
9926 Series
Double Pole Combination
(Auxiliary & Alarm Contact)
Trip Curves—Hydraulic
Magnetic Type Typical
time/current characteristics
at 30ºC
Additional trip curves and
amp ratings are available
upon request.
Type: Double Pole Aux
Current
Ratings
(amps) Part No. Description
19926262001 QL-A-2-13-DM-KM-1
29926262002 QL-A-2-13-DM-KM-2
59926262005 QL-A-2-13-DM-KM-5
10 9926262010 QL-A-2-13-DM-KM-10
15 9926262015 QL-A-2-13-DM-KM-15
20 9926262020 QL-A-2-13-DM-KM-20
25 9926262025 QL-A-2-13-DM-KM-25
9926 Series
Double Pole
w/ Auxiliary Contact
Type: Single Pole Aux
Current
Ratings
(amps) Part No. Description
19926261001 QL-A-1-13-DM-KM-1
29926261002 QL-A-1-13-DM-KM-2
59926261005 QL-A-1-13-DM-KM-5
10 9926261010 QL-A-1-13-DM-KM-10
15 9926261015 QL-A-1-13-DM-KM-15
20 9926261020 QL-A-1-13-DM-KM-20
25 9926261025 QL-A-1-13-DM-KM-25
9926 Series
Single Pole
w/ Auxiliary Contact
Type: Single Pole Trip
Current
Ratings
(amps) Part No. Description
19926271001 QL-T-1-13-DM-KM-1
29926271002 QL-T-1-13-DM-KM-2
59926271005 QL-T-1-13-DM-KM-5
10 9926271010 QL-T-1-13-DM-KM-10
15 9926271015 QL-T-1-13-DM-KM-15
20 9926271020 QL-T-1-13-DM-KM-20
25 9926271025 QL-T-1-13-DM-KM-25
9926 Series
Single Pole Trip
(Alarm Contact)
Type: Single Pole Combo
Current
Ratings
(amps) Part No. Description
19926281001 QL-AT-1-13-DM-KM-1
29926281002 QL-AT-1-13-DM-KM-2
59926281005 QL-AT-1-13-DM-KM-5
10 9926281010 QL-AT-1-13-DM-KM-10
15 9926281015 QL-AT-1-13-DM-KM-15
20 9926281020 QL-AT-1-13-DM-KM-20
25 9926281025 QL-AT-1-13-DM-KM-25
9926 Series
Single Pole Combination
(Auxiliary & Alarm Contact)
Dual Mount Dimensions in mm (in.)
57.0
(2.24)
26.2
(1.03)
31.3
(1.23)
21.1
(0.83)
21.3
(0.84) 32.9
(1.3)
10.7
(0.42)
(N/O)16
(N/C)18
(C)15
11(C)
12(N/C)
14(N/O)
TRIP ALARM Q. CONNECTORS
2
(0.08)
0.5
(0.02)
5.5
(0.22)
AUX SWITCH Q. CONNECTORS
2.8
(0.11)
0.5
(0.02)
7
(0.28)
Accessories
Type Part No.
Bus-bar (1 pole, insulated 1m) 67101904
Bus bar end cap, 1 pole 67101973
Power lug, straight 67101960
Power lug, 90° 67101961
Lock-out handle 67101913
5
9926 Series Branch Rated Circuit Breakers–DC Version
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
130
105
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve U2 DC
(4% Ripple Factor)
Ambient Temperature 30°C
9926 Series–DC version Trip Curve
Circuit Breakers
Hydraulic Magnetic Type
Single pole versions only
U2 trip curve for general purpose
applications
80 and 125 VDC
Up to 60A
Just 13 mm wide
Mounts on 35mm DIN-rail
UL 489A listed
VDE
9926 Series
Single Pole
(80 VDC)
Ordering Data Type: Single Pole (80 VDC)
Current
Ratings
(amps) Part No. Description
0.5 9926251900 QY-1-13-DM-U2-0.5
19926251901 QY-1-13-DM-U2-01
29926251902 QY-1-13-DM-U2-02
39926251903 QY-1-13-DM-U2-03
49926251904 QY-1-13-DM-U2-04
59926251905 QY-1-13-DM-U2-05
10 9926251910 QY-1-13-DM-U2-10
15 9926251915 QY-1-13-DM-U2-15
20 9926251920 QY-1-13-DM-U2-20
25 9926251925 QY-1-13-DM-U2-25
30 9926251930 QY-1-13-DM-U2-30
35 9926251935 QY-1-13-DM-U2-35
40 9926251940 QY-1-13-DM-U2-40
45 9926251945 QY-1-13-DM-U2-45
50 9926251950 QY-1-13-DM-U2-50
60 9926251960 QY-1-13-DM-U2-60
Technical Data
Voltage 80,125 VDC
Current
minimum 0.5 A
maximum 60 A
Interrupting capacity 10,000 A
Dielectric strength 1500 V, 50/60 Hz
Insulation resistance 100 MM
Operating life 10000
mechanical operations
Operating temperature -40…+65°C
Wire size*
1-15A: 14 AWG min.,
10 AWG max.
20-25A: 10 AWG min.
Torque 20 in.-lb
Approval
UL 489A Listed, CE, VDE
*Wire sizes: gauges specified are the minimum allow-
able as per CSA and UL standards.
The 9926 circuit breakers do not have provisions for
marking tags. A possible solution is to cut the adhesive
SchS2 tag rail to length (approximately 20 mm on a
single pole unit so the current rating remains visible or
approximately 30 mm on a two pole unit). The SchS2
accepts DEK, WS and ESG 8/17 marking tags. The
part number for adhesive SchS2 is 1720600000.
19
(0.75)
74
(2.91)
66
(2.6)
17.9
(0.7)
71.4
(2.81)
28.5
(1.12)
5
(0.2)
32
(1.26)
45
(1.77)
64.8
(2.55)
57
(2.24)
13
(0.51)
92.8
(3.65)
9926 Series
Single Pole
(125 VDC)
Type: Single Pole (125 VDC)
Current
Ratings
(amps) Part No. Description
19926251801 QY-1-13-DM-U2-01-B1
29926251802 QY-1-13-DM-U2-02-B1
39926251803 QY-1-13-DM-U2-03-B1
49926251804 QY-1-13-DM-U2-04-B1
59926251805 QY-1-13-DM-U2-05-B1
10 9926251810 QY-1-13-DM-U2-10-B1
15 9926251815 QY-1-13-DM-U2-15-B1
20 9926251820 QY-1-13-DM-U2-20-B1
25 9926251825 QY-1-13-DM-U2-25-B1
30 9926251830 QY-1-13-DM-U2-30-B1
35 9926251835 QY-1-13-DM-U2-35-B1
40 9926251840 QY-1-13-DM-U2-40-B1
45 9926251845 QY-1-13-DM-U2-45-B1
50 9926251850 QY-1-13-DM-U2-50-B1
60 9926251860 QY-1-13-DM-U2-60-B1
Dimensions in mm (in.)
Trip Curves—Hydraulic
Magnetic Type Typical
time/current characteristics
at 30ºC
Additional trip curves and amp ratings
are available upon request.
Type: Single Pole Type: Double Pole Type: Triple Pole
Current Current Current
Ratings Rating Rating
(amps) Part No. Description (amps) Part No. Description (amps) Part No. Description
19926251501 QZ-1-13-D-2-01 1 9926252501 QZ-2-13-D-2-01 10 9926253510 QZ-3-13-D-2-10
29926251502 QZ-1-13-D-2-02 2 9926252502 QZ-2-13-D-2-02 15 9926253515 QZ-3-13-D-2-15
39926251503 QZ-1-13-D-2-03 4 9926252504 QZ-2-13-D-2-04 20 9926253520 QZ-3-13-D-2-20
49926251504 QZ-1-13-D-2-04 5 9926252505 QZ-2-13-D-2-05 25 9926253525 QZ-3-13-D-2-25
59926251505 QZ-1-13-D-2-05 6 9926252506 QZ-2-13-D-2-06 30 9926253530 QZ-3-13-D-2-30
69926251506 QZ-1-13-D-2-06 10 9926252510 QZ-2-13-D-2-10 40 9926253540 QZ-3-13-D-2-40
89926251508 QZ-1-13-D-2-08 15 9926252515 QZ-2-13-D-2-15 50 9926253550 QZ-3-13-D-2-50
10 9926251510 QZ-1-13-D-2-10 20 9926252520 QZ-2-13-D-2-20 60 9926253560 QZ-3-13-D-2-60
15 9926251515 QZ-1-13-D-2-15 25 9926252525 QZ-2-13-D-2-25
20 9926251520 QZ-1-13-D-2-20 30 9926252530 QZ-2-13-D-2-30
25 9926251525 QZ-1-13-D-2-25 35 9926252535 QZ-2-13-D-2-35
35 9926251535 QZ-1-13-D-2-35 40 9926252540 QZ-2-13-D-2-40
40 9926251540 QZ-1-13-D-2-40 50 9926252550 QZ-2-13-D-2-50
50 9926251550 QZ-1-13-D-2-50 60 9926252560 QZ-2-13-D-2-60
60 9926251560 QZ-1-13-D-2-60
6
9926 Series Supplemental Circuit Breakers
Circuit Breakers
Hydraulic Magnetic Type
AC Voltages 240/480V
Trip curve 2 for general purpose
applications
UL 1077 recognized
VDE, CSA, and CE Approved
Just 13 mm wide
Mounts to 35 mm DIN-rail
Factory fitted auxiliary or trip alarm
Single, double and triple pole versions
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
130
105
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve 2
Ambient Temperature 30°C
9926 Series–Supplemental Trip Curve
9926 Series
Triple Pole
9926 Series
Double Pole
9926 Series
Single Pole
Accessories
Type Part No.
Bus bar (1 pole, insulated 1m) 67101904
Bus bar (2 pole, insulated 1m) 67101972
Bus bar (3 pole, insulated 1m) 67101971
Bus bar end cap, 1 pole 67101973
Bus bar end cap, 2 pole or 3 pole 67101974
Power lug, straight 67101960
Power lug, 90° 67101961
Lock-out handle 67101913
Ordering Data
Technical Data
Voltage 277/480 VAC @ 50/60 Hz
Current
minimum 0.5 A
maximum 60 A
Interrupting capacity 5 kA @ 277/480 V, 5 kA @ 120 V, 5 kA @ 240 V
Dielectric strength 1500 V, 50/60 Hz
Insulation resistance 100 MM
Operating life 10000 mechanical operations
Operating temperature -40…+65°C
Wire size*
1-15A: 14 AWG min., 10 AWG max.
20-25A: 10 AWG min.
Torque 20 in.-lb
Approval
UL 1077 Recognized, VDE (EN 60947-2), CSA C22.2 No. 235, CE Approved
*Wire sizes: gauges specified are the minimum allowable as per CSA and UL standards.
The 9926 circuit breakers do not have provisions for marking tags. A possible solution is to cut the adhesive
SchS2 tag rail to length (approximately 20 mm on a single pole unit so the current rating remains visible or
approximately 30 mm on a two pole unit).The SchS2 accepts DEK, WS and ESG 8/17 marking tags.
The part number for adhesive SchS2 is 1720600000.
Additional trip curves and
amp ratings are available
upon request.
Trip Curves—Hydraulic
Magnetic Type Typical
time/current characteristics
at 30ºC
9926 Series Supplemental – dimensions in mm (in.)
65
(2.56)
60
(2.36)
22.5
(0.86)
25.9
(0.94)
45
(1.77)
44
(1.73)
63.8
(2.51)
73
(2.87)
5.0
(0.2)
13
(0.51)
92.8
(3.65)
26
(1.02)
13
(0.51)
13
(0.51)
39
(1.54)
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
130
105
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve 2
Ambient Temperature 30°C
7
Trip Curves—Hydraulic
Magnetic Type Typical
time/current characteristics
at 30ºC
Type: Double Pole Trip
Current
Ratings
(amps) Part No. Description
19926272501 QZ-T-2-13-D-2-01
29926272502 QZ-T-2-13-D-2-02
59926272505 QZ-T-2-13-D-2-05
10 9926272510 QZ-T-2-13-D-2-10
15 9926272515 QZ-T-2-13-D-2-15
20 9926272520 QZ-T-2-13-D-2-20
25 9926272525 QZ-T-2-13-D-2-25
Type: Double Pole Combo
Current
Ratings
(amps) Part No. Description
19926282501 QZ-AT-2-13-D-2-01
29926282502 QZ-AT-2-13-D-2-02
59926282505 QZ-AT-2-13-D-2-05
10 9926282510 QZ-AT-2-13-D-2-10
15 9926282515 QZ-AT-2-13-D-2-15
20 9926282520 QZ-AT-2-13-D-2-20
25 9926282525 QZ-AT-2-13-D-2-25
9926 Series
Double Pole Trip
(Alarm Contact)
9926 Series
Double Pole Combination
(Auxiliary & Alarm Contact)
Type: Double Pole Aux
Current
Ratings
(amps) Part No. Description
19926262501 QZ-A-2-13-D-2-01
29926262502 QZ-A-2-13-D-2-02
59926262505 QZ-A-2-13-D-2-05
10 9926262510 QZ-A-2-13-D-2-10
15 9926262515 QZ-A-2-13-D-2-15
20 9926262520 QZ-A-2-13-D-2-20
25 9926262525 QZ-A-2-13-D-2-25
9926 Series
Double Pole
w/ Auxiliary Contact
Type: Single Pole Aux
Current
Ratings
(amps) Part No. Description
19926261501 QZ-A-1-13-D-2-01
29926261502 QZ-A-1-13-D-2-02
59926261505 QZ-A-1-13-D-2-05
10 9926261510 QZ-A-1-13-D-2-10
15 9926261515 QZ-A-1-13-D-2-15
20 9926261520 QZ-A-1-13-D-2-20
25 9926261525 QZ-A-1-13-D-2-25
9926 Series
Single Pole
w/ Auxiliary Contact
Type: Single Pole Trip
Current
Ratings
(amps) Part No. Description
19926271501 QZ-T-1-13-D-2-01
29926271502 QZ-T-1-13-D-2-02
59926271505 QZ-T-1-13-D-2-05
10 9926271510 QZ-T-1-13-D-2-10
15 9926271515 QZ-T-1-13-D-2-15
20 9926271520 QZ-T-1-13-D-2-20
25 9926271525 QZ-T-1-13-D-2-25
9926 Series
Single Pole Trip
(Alarm Contact)
Type: Single Pole Combo
Current
Ratings
(amps) Part No. Description
19926281501 QZ-AT-1-13-D-2-01
29926281502 QZ-AT-1-13-D-2-02
59926281505 QZ-AT-1-13-D-2-05
10 9926281510 QZ-AT-1-13-D-2-10
15 9926281515 QZ-AT-1-13-D-2-15
20 9926281520 QZ-AT-1-13-D-2-20
25 9926281525 QZ-AT-1-13-D-2-25
9926 Series
Single Pole Combination
(Auxiliary & Alarm Contact)
9926 Series Supplemental Circuit Breakers with Contacts
Type: Triple Pole Trip
Current
Ratings
(amps) Part No. Description
19926273501 QZ-T-3-13-D-2-01
29926273502 QZ-T-3-13-D-2-02
59926273505 QZ-T-3-13-D-2-05
10 9926273510 QZ-T-3-13-D-2-10
15 9926273515 QZ-T-3-13-D-2-15
20 9926273520 QZ-T-3-13-D-2-20
25 9926273525 QZ-T-3-13-D-2-25
Type: Triple Pole Combo
Current
Ratings
(amps) Part No. Description
19926283501 QZ-AT-3-13-D-2-01
29926283502 QZ-AT-3-13-D-2-02
59926283505 QZ-AT-3-13-D-2-05
10 9926283510 QZ-AT-3-13-D-2-10
15 9926283515 QZ-AT-3-13-D-2-15
20 9926283520 QZ-AT-3-13-D-2-20
25 9926283525 QZ-AT-3-13-D-2-25
9926 Series
Triple Pole Trip
( Alarm Contact)
9926 Series
Triple Pole Combination
(Auxiliary & Alarm Contact)
Type: Triple Pole Aux
Current
Ratings
(amps) Part No. Description
19926263501 QZ-A-3-13-D-2-01
29926263502 QZ-A-3-13-D-2-02
59926263505 QZ-A-3-13-D-2-05
10 9926263510 QZ-A-3-13-D-2-10
15 9926263515 QZ-A-3-13-D-2-15
20 9926263520 QZ-A-3-13-D-2-20
25 9926263525 QZ-A-3-13-D-2-25
9926 Series
Triple Pole
w/ Auxiliary Contact
Circuit Breakers
Auxiliary switch, Trip alarm,
Combination of both
AC Voltages 240/480V
Trip curve 2 for general purpose
applications
UL 1077 recognized
VDE, CSA, and CE Approved
Just 13 mm wide
Mounts to 35 mm DIN-rail
Factory fitted auxiliary or trip alarm
Single, double and triple pole versions
9926 Series–Supplemental Trip Curve
Technical Data
Voltage 277/480 VAC @ 50/60 Hz
Current
minimum 0.5 A
maximum 60 A
Interrupting capacity 5 kA @ 277/480 V,
5 kA @ 120 V, 5 kA @ 240 V
Dielectric strength 1500 V, 50/60 Hz
Insulation resistance 100 MM
Operating life 10000
mechanical operations
Operating temperature -40…+65°C
Wire size*
1-15A: 14 AWG min., 10 AWG max.
20-25A: 10 AWG min.
Torque 20 in.-lb
Approval
UL 1077 Recognized, VDE (EN 60947-2),
CSA C22.2 No. 235, CE Approved
*Wire sizes: gauges specified are the minimum allow-
able as per CSA and UL standards.
The 9926 circuit breakers do not have provisions for
marking tags. A possible solution is to cut the adhesive
SchS2 tag rail to length (approximately 20 mm on a
single pole unit so the current rating remains visible or
approximately 30 mm on a two pole unit). The SchS2
accepts DEK, WS and ESG 8/17 marking tags.The
part number for adhesive SchS2 is 1720600000.
8
9926 Series Supplemental Circuit Breakers–GFCI
Trip Curves—Hydraulic Magnetic
Type Typical
time/current characteristics
at 30ºC
Type: Single Pole GFCI
Current
Ratings
(amps) Part No. Description
59926291105 QF17A2505 - CB W/GFI
10 9926291110 QF17A2510 - CB W/GFI
15 9926291115 QF17A2515 - CB W/GFI
20 9926291120 QF17A2520 - CB W/GFI
25 9926291125 QF17A2525 - CB W/GFI
30 9926291130 QF17A2530 - CB W/GFI
50 9926291150 QF17A2550 - CB W/GFI
9926 Series
GFCI
Ground Fault Current Interrupt
CE approved
UL1077 and UL1053 recognized
Small frame size (26mm wide)
Single pole plus switched neutral
earth leakage protection
Trip point is unaffected by ambient
temperature
Current ratings up to 50A
Trip indication
(mid trip handle position)
Trip curve 2 for general purpose
applications
Ordering Data
9926 Series–AC version Trip Curve
9926 Series GFCI – dimensions in mm (in.)
Technical Data
Standard Ampere Ratings (A) 5 to 50A
Sensitivity (mA) 30 (CE) / 22 (UL)
Number of Poles 1 + N
Equipment Type Earth Leakage/GFCS
Rated Voltage (V) 230 (CE) / 240 (UL)
Rated Interrupting/ 5 kA
Withstand Capacity (kA)
Weight (kg) 0.26
Trip Curve (standard) 2
Operating Temperature -40 to +65ºC
Approval
UL 1077 and UL 1053, CE
1000
Tripping Time
Seconds Minutes
100
10
1
10
1
0.1
0.01
0.001
100
130
105
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current
Operating Characteristics
Curve 2
Ambient Temperature 30°C
82.4
(3.24)
93
(3.66)
73
(2.87)
65
(2.56)
26
(1.02)
26
(1.02)
16.4
(0.646)
35.7
(1.406)
8.0
(0.315)
44
(1.73)
68.8
(2.71)
71.4
(2.81)
7.8
(0.307)
57(2.24)
9
9926251000
Amperage
Trip Curves
"00" - 0.5A
"01" - 1A
"02" - 2A
"60" - 60A
Typ e
"5" - Base Breaker
"6" - With Auxiliary Contact
"7" - With Trip Alarm Contact
"8" - Combo Aux/Trip Contact
"9" - GFCI
Poles
1 Pole
2 Pole
3 Pole
"0" - Branch AC KM (Standard)
"1" - Branch AC OP (Instantaneous)
"2" - Branch AC 1 (Fast)
"4" - Branch 80VDC 1 (Fast)
"5" - Supplemental 2 (Standard)
"6" - Branch 125VDC OP (Instantaneous)
"7" - Branch 80VDC OP (Instantaneous)
"8" - Branch 125VDC U2 (Standard)
"9" - Branch 80VDC U2 (Standard)
/
Part Number Table - Example
To order 9926 Series Single Pole Circuit Breaker
Part No. 9926251100
Current Rating of 1.0 amp
Internal Resistance per Pole of 1.1 ohms
Trip Curve – M1, Medium (Standard)
9926 Series Mounting Options and Accessories
D
O
W
N
D
O
W
N
V
E
R
T
4
5
4
5
V
E
R
T
4
5
U
P
H
O
R
I
Z
H
O
R
I
Z
4
5
U
P
9
3
%
9
5
%
1
0
0
%
1
0
5
%
1
0
7
%
1
0
5
%
1
0
0
%
9
5
%
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
O
F
F
O
N
Mounting Options
If the product is not vertically mounted in the normal DIN-rail
mounting orientation, a rating factor must be applied. Figure 1
shows a diagram of the rating factor to apply. The published
curves for these circuit breaker products are produced with
the circuit breaker in the vertical mounting position. The rating
factor only applies to the must hold and must trip points of the
curve as the other parts (instantaneous trip point) stay largely
unaffected.
It is important to note that in environments that are exposed to
a high degree of vibration, the cables that connect to the circuit
breaker must be securely held in place, as the breaker is not
designed to carry the weight of the cables. A maximum of 35N
can be applied to the terminal area, in a direction perpendicular
to the mounting axis.
Accessories
Technical Data
Current Rating 80A max.
Voltage 500V max.
Short Circuit Strength 25kA
Type Part No.
Bus bar (1 pole, insulated 1m) 67101904
Bus bar (2 pole, insulated 1m) 67101972
Bus bar (3 pole, insulated 1m) 67101971
Type Part No.
Bus bar end cap, 1 pole 67101973
Bus bar end cap, 2 pole or 3 pole 67101974
Technical Data
Current Rating 85A max.
Wire Size 10 AWG min., 4 AWG max.
Dimensions A: 6 mm B: 32 mm
Type Part No.
Power lug, straight 67101960
Power lug, 90° 67101961
Type Part No.
Lock-out handle 67101913