Data sheet...
Surge protection
SPD II 2 R PV 600VDC
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date April 29, 2013 5:59:25 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 36 mm Height 100 mm
Depth 73.5 mm Net weight 274 g
Temperatures
Operating temperature -40 °C...+70 °C Storage temperature -40 °C...+85 °C
General data
Colour Light Grey Design Installation housing; 2TE
Height with TS 35 74 mm Lightning arrester No
Mounting rail TS 35, TS 35 x 15, TS 35
x 7.5
Optical function display green = OK; red = arrester
is defective - replace
Protection degree IP 20 UL 94 flammability rating V-0
Insulation coordination acc. to EN 50178
Pollution severity 2 Surge voltage category III
technical data
Max. continuous voltage, Uc (DC) 550 V Total discharge current Itotal 100 kA
Discharge current, max. (8/20 µs) 50 kA Protection level UP (typ.) ≤ 2000 V
Signalling contact 250 V / 0,5 A, 48 VDC /
0,1 A
Colour
Light Grey
AC/DC/UC DC Response time ≤ 100 ns
Connection data
Clamping range, rated connection 25 mm² Clamping range, rated connection, min. 4 mm²
Clamping range, rated connection, max.
35 mm²
Wire connection cross section, stranded,
rated connection, min. 2.5 mm²
Wire connection cross section, stranded,
rated connection, max. 25 mm²
Tightening torque, min.
2.5 Nm
Tightening torque, max. 3 Nm Stripping length, rated connection 15 mm
Connection data, remote alert
Connection type [remote alert] pluggable Max. torque [remote alert] 0.22 Nm
Stripping length [remote alert]
5 mm
Cross-section for connected wire, solid
core, min. [remote alert] 0.5 mm²
Cross-section for connected wire, solid
core, max. [remote alert] 1.5 mm²
Photovoltaic technical data
Maximum continuous operating voltage
UCPV mode +/-, -/PE, +/PE 550 V DC
Protection level Up at In (per module)
2200 V
Protection level Up mode (+/- , -/PE , +/
PE) 4000 V