AMP-TRAP®Form 101
A50P SEMICONDUCTOR PROTECTION FUSES
Features/Benefits
Low l2tminimizes damage to protected components on
short circuit
Controlled arc voltage reduces stress to circuit
components during fuse clearing
Choice of mounting types helps in equipment design
A50P Amp-trap® Form 101 Semiconductor
Protection fuses were developed for DC drives,
uninterruptable power supplies and similar applica-
tions requiring better protection (lower l2t) and
superior reliability. The A50P is typically used for
replacement.
HIGHLIGHTS:
Very Fast Acting
Current Limiting
Low l2t
Indicator Options
Available
APPLICATIONS:
Protection of DC
drives, UPS and other
equipment of 500
volts or less
A50 P100 - 4 TI
Amp-trap®Fuse
Rated Volts - 500
Style
Amperes*
Mounting Types*
Ferrule
Blades, bolt-in
Integral Blown-Fuse
Indicator
Trigger Indicator
Trigger Actuator
* For ampere ratings and types not listed, consult the factory.
Catalog Numbering System
A
50
P
100
1
4
TI
TA
FUSE FUSE BLOCK
AMPERE MOUNTING CATALOG
RATING TYPE NUMBER
10-30 1 70306
35-60 1DS 60306J
35-60 4 P243G
70-200 4 P243E
225-600 4 P266C
Single Pole Fuse Blocks for A50P Fuses
AC: 10-1200A
500VAC, 100kA I.R.
DC: 35-1000A
450VDC, 79kA I.R.
L/R = 10ms
Ratings
UL Recognized
Component
AC: UL Guide No.
JFHR2 (10-800A)
DC: UL Guide No.
JFHR2 (35-800A)
Approvals
* Contact technical services for applications data.
D 21
D
AMPERE CATALOG OUTLINE AMPERE CATALOG OUTLINE AMPERE CATALOG OUTLINE
RATING NUMBER FIG. RATING NUMBER FIG. RATING NUMBER FIG.
10 A50P10-1 1 175 A50P175-4 3 450 A50P450-4 3
15 A50P15-1 1 175 A50P175-4TI 3 450 A50P450-4TI 3
20 A50P20-1 1 200 A50P200-4 3 500 A50P500-4 3
25 A50P25-1 1 200 A50P200-4TA 4 500 A50P500-4TI 3
30 A50P30--1 1 200 A50P200-4TI 3 600 A50P600-4 3
35 A50P35-4 2 225 A50P225-4 3 600 A50P600-4TA 4
40 A50P40-4 2 250 A50P250-4 3 600 A50P600-4TI 3
50 A50P50-4 2 250 A50P250-4TA 4 700 A50P700-4 5
60 A50P60-4 2 250 A50P250-4TI 3 700 A50P700-4TA 6
70 A50P70-4 3 275 A50P275-4 3 700 A50P700-4TI 5
80 A50P80-4 3 300 A50P300-4 3 800 A50P800-4 5
90 A50P90-4 3 300 A50P300-4TA 4 800 A50P800-4TA 6
100 A50P100-4 3 300 A50P300-4TI 3 800 A50P800-4TI 5
100 A50P100-4TI 3 325 A50P325-4 3 900 A50P900-4 3
125 A50P125-4 3 350 A50P350-4 3 1000 A50P1000-4 3
125 A50P125-4TA 4 350 A50P350-4TI 3 1000 A50P1000-4TI 3
125 A50P125-4TI 3 400 A50P400-4 3 1200 A50P1200-4 3
150 A50P150-4 3 400 A50P400-4TA 4 1200 A50P1200-4TI 3
150 A50P150-4TI 3 400 A50P400-4TI 3
Standard Fuse Ampere Ratings, Catalog Numbers
For ampere ratings and styles not listed, call Technical Services.
Dimensions
OUTLINE MOUNTING FIG. DIMENSIONS - INCHES (mm)
REF. TYPE A B C D E F G H
A50P10 to 30 1 1 2.00 0.56 - - - - - -
(50.8) (14.2) - - - - - -
A50P35 to 60 1DS* 1 2.25 0.81 - - - - - -
(57.2) (20.6) - - - - - -
A50P35 to 60 4 2 3.19 0.81 1.63 2.50 2.25 0.34 0.72 0.13
(81.0) (20.6) (41.4) (63.5) (57.2) 8.6) (18.3) (3.3)
A50P70 to 100 4 3 3.63 1.00 2.13 2.94 2.81 0.31 0.75 0.13
(92.2) (25.4) (54.1) (74.7) (71.4) (7.9) (19.1) (3.3)
A50P125 to 200 4, 4TA** 3, 4** 3.63 1.22 2.13 2.94 2.81 0.31 1.00 0.19
(92.2) (31.0) (54.1) (74.7) (71.4) (7.9) (25.4) (4.8)
A50P225 to 400 4, 4TA** 3, 4** 4.34 1.50 2.09 3.41 2.78 0.41 1.00 0.25
(110) (38.1) (53.1) (86.6) (70.6) (10.4) (25.4) (6.4)
A50P450 to 600 4, 4TA** 3, 4** 4.47 2.00 2.22 3.53 2.91 0.41 1.50 0.25
(114) (50.8) (56.4) (89.7) (73.9) (10.4) (38.1) (6.4)
A50P700 to 800 4, 4TA** 5, 6** 6.47 2.50 2.22 4.63 4.31 0.53 2.00 0.38
(164) (63.5) (56.4) (118) (109) (13.5) (50.8) (9.7)
A50P900 to 1200 4 3 6.97 3.00 3.22 4.97 *** 0.63 2.38 0.44
(177) (76.2) (81.8) (126) *** (16.0) (60.5) (11.1)
* Use with 60306J fuse block.
** Optional Trigger Actuator (TA)
*** Mounting hole is round, diameter F.
Figure 2
Figure 5 Figure 6
Figure 3 Figure 4
Figure 1
AMP-TRAP®Form 101
A50P SEMICONDUCTOR PROTECTION FUSES
D 22