E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s3
1001969-EN-04-2011-09Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
-2
Function description
][Funktionen_ein_zweikanalig _ohne Quer
Single-channel operation: no re-
dundancy in the input circuit, earth
faults in the reset circuit and input
circuit are detected.
Dual-channel operation without de-
tection of shorts across contacts:
redundant input circuit, detects
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
the reset circuit too.
][Funktionen_zweikanalig_mit Quer
Dual-channel operation with detec-
tion of shorts across contacts: re-
dundant input circuit, detects
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
the reset circuit too,
– shorts between contacts in the
input circuit.
][Funktionen_auto_manu_Start
Automatic reset: Unit is active once
the input circuit has been closed.
Manual reset: Unit is active once
the input circuit is closed and then
the reset circuit is closed.
][Funktionen_berStart_fall_Flanke
Monitored reset with falling edge:
Unit is active once
– the input circuit is closed and
then the reset circuit is closed
and opened again.
– the reset circuit is closed and
then opened again once the in-
put circuit is closed.
][Funktionen_berStart_steig_Flanke
Monitored reset with rising edge:
Unit is active once the input circuit
is closed and once the reset circuit
is closed after the waiting period
has elapsed (see technical details).
][Funktionen_Start_Anlauftest
Reset with start-up test: The unit
checks whether safety gates that
are closed are opened and then
closed again when supply voltage
is applied.
][Funktionen_Kontaktvervielfachung_PNOZsigma
Increase in the number of available
instantaneous safety contacts by
connecting contact expander mod-
ules or external contactors/relays;
A connector can be used to con-
nect 1 PNOZsigma contact ex-
pander module.
Timing diagram
][Zeitdiagramm_PNOZs_auto_manu_ueber1_ueber2_Semi
Key
Power: Supply voltage
Reset/Start: Reset circuit S12-S34
Input: Input circuits S11-S12,S 21-
S22
Output safe: Safety contacts 13-14,
23-24
Out semi: Semiconductor
outputY32
: Automatic reset
: Manual reset
: Monitored reset with rising edge
: Monitored reset with falling edge
a: Input circuit closes before reset
circuit
b: Reset circuit closes before input
circuit
t1: Switch-on delay
t2: Delay-on de-energisation
t3: Waiting period
t4: Waiting period reset circuit was
closed
Wiring
][Verdrahtung_Si_unverz
Please note:
Information given in the “Technical
details” must be followed.
Outputs 13-14, 23-24 are safety
contacts.
To prevent contact welding, a fuse
should be connected before the
output contacts (see technical de-
tails).
Calculation of the max. cable runs
lmax in the input circuit:
Rlmax = max. overall cable resist-
ance (see technical details)
Rl /km = cable resistance/km
Use copper wire that can withstand
60/75 °C.
Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
POWER
Input
Output safe
Reset/Start
t1t2t1t2t2
t1
t1t2
1 2
ab 3
Out semi
t1t2t2
t1
ab
t4t2t2
ab
t1
t1
t3
4
t3