POWER
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
SPECIAL FEATURES
3000 W output power
40 W/cu-in
Optional customer provided air
1U x 3U form factor
N+1 redundant
Internal OR-ing
5 V housekeeping
High efciency 89% @ 200 Vac,
100% load
Variable speed “smart fans”
Two year warranty
COMPLIANCE
POE Isolation
EMI Class B - EN55022
EN61000 Immunity
SAFETY
UL/cUL 60950
CSA 60950
Nemko TUV
CB Report
Electrical Specications
Input
Input range (operating) 180 - 264 Vac
90 - 140 Vac
Nominal input 200 Vac
110 Vac
Input through Card Edge Connection
on same end as DC output
Frequency 47 to 63 Hz
Input fusing Internal 25 A fuses Both lines fused
Inrush current ≤40 A peak Either hot or cold start
Power factor 0.97 typical Meets EN61000-3-2
Harmonics
Meets IEC 1000-3-2 requirements
@ 50% load
Input current 19 A max input current
Holdup time 10 ms minimum At full rated load
Leakage current 1.4 mA At 240 Vac
Power line transient MOV directly after the fuse
Note: HPS3000-9-001 variant available for applications with higher airow requirements
Data Sheet
HPS3000 Series Data Sheet
Output
Output rating
48 V @ 62.0 A
5 Vsb @ 3.0 A
180 - 264 Vac
48 V @ 29.4 A
5V @ 3 A
90 - 140 Vac
Set point 48 V Programmable 96-117% through I2C serial bus
Total regulation range 48 V ± 5%
5 Vsb ± 4%
Line/load/transient when measured at output connection
Rated load 3000 W maximum @ 200 Vac Input
1500 W maximum @ 110 Vac Input
No derating over operating temp range
Minimum load 48 V @ 0.0 A
5 Vsb @ 0.0 A
No loss of regulation
Output noise
480 mV max P-P
100 mV max P-P
48 V output
5 Vsb output
Measured with a 0.1μF Ceramic and 10 μF Tantalum capacitor
on any input
Output voltage overshoot ± 5% maximum Nominal Voltage Setting
Transient response 5% maximum deviation 50% load step @ 1 A/us
Step load valid between 10% to 100% of output rating.
Max units in parallel Up to 4 Total power in 1U 19” rack is 12 KW
Short circuit protection 120% - 130% of rated output Output to return
Output isolation Per POE specs >2000 Vac
Forced load sharing Within ± 6.25 A of all shared outputs Digital sharing control
Over current protection (OCP) 120% to 130%
110% to 140%
48 V output
5 Vsb output
Over voltage protection (OVP) 110% to 133%
110% to 125%
48 V output
5 Vsb output
Over temperature protection
10 - 15 deg C above safe operating area
Both PFC and output converter monitored
5 Vsb will operate under overtemperature condition.
Built in hysteresis
Environmental Specications
Vibration/Shock: Non-operational 5G Sine sweep from 5 Hz to 500 Hz, dwelling at resonant frequencies for 1 hour each
Operating Temperature: - 10 ° to +40 °C
Storage Temperature: - 40 ° to +85 °C
Cooling External fans with Fan Fail and Fan Speed control
Operating Relative Humidity: 5% to 95% non-condensing
Storage Relative Humidity: 5% to 95% non-condensing
Operating Altitude Up to 10,000 feet above sea level
Storage Altitude: Up to 30,000 feet above sea level
RoHS Compliant: Yes
HPS3000 Series Data Sheet
Module Information
(All units in mm)
HPS3000-9
HPS3000 Series Data Sheet
Module Information
(All units in mm)
HPS3000-9-001
HPS3000 Series Data Sheet
Pin Assignments
Bottom
Pin
1AC LINE 9+48 Vdc out 17 +48 Vdc RTN 25 Reserved
2AC LINE 10 +48 Vdc out 18 +48 Vdc RTN 26 PRESENT#
3n.c. 11 +48 Vdc out 19 +48 Vdc RTN 27 DCOK/PWOK#
4AC NEUTRAL 12 +48 Vdc out 20 +48 Vdc RTN 28 SDA
5AC NEUTRAL 13 +48 Vdc out 21 +48 Vdc RTN 29 HVCC
6n.c. 14 +48 Vdc out 22 +48 Vdc RTN 30 PSON#
7n.c. 15 +48 Vdc out 23 n.c. 31 #ALERT
8n.c. 16 +48 Vdc RTN 24 V_STBY 32 ISHARE
Pin Assignments
Top
Pin
64 AC LINE 56 +48 Vdc out 48 +48 Vdc RTN 40 Reserved
63 AC LINE 55 +48 Vdc out 47 +48 Vdc RTN 39 ACOK#
62 n.c. 54 +48 Vdc out 46 +48 Vdc RTN 38 SMBUS_ALERT_OUT
61 AC NEUTRAL 53 +48 Vdc out 45 +48 Vdc RTN 37 SCL
60 AC NEUTRAL 52 +48 Vdc out 44 +48 Vdc RTN 36 A2
59 n.c. 51 +48 Vdc out 43 +48 Vdc RTN 35 PSKILL
58 n.c. 50 +48 Vdc out 42 n.c. 34 A1
57 n.c. 49 +48 Vdc RTN 41 SYS_GND 33 A0
HPS3000 Series Data Sheet
TPWOK_Off_
AC Input
Main Vout
Timing Diagram
TAC_On_Delay
TVout_Holdup
TPWOK_On
AC Input
ON / OFF Cycle
AC_OK
PS_ON
3.3 V Vout
PWOK
PSON
ON / OFF
Cycle
Tsb_On
TSB_Vout
TPWOK_Delay
TPWOK_Off_
TPWOK_Off_
TPWOK_On
TPWOK_Off_
TPWOK_On
TACOK_Delay
TPSON_On_Delay
TPSON_PWOK
TPWOK_Off
AC On
AC On
HPS3000 Series Data Sheet
Signals and Controls - All Models
PSON#
The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal that turns on the 48 V power rail. When this
signal is not pulled low by the system, or left open, the 48 V output turns off. The 5 Vsb output remains on. This signal is pulled to a standby
voltage by a pull-up resistor internal to the power supply. The power supply fan(s) shall operate at the lowest speed.
PSON# Signal Characteristic
Signal Type Accepts an open collector/drain input from the system. Pulled-up to the 5 Vsb located in power supply.
PSON# = Low ON
PSON# = Open OFF
MIN MAX
Logic level low (power supply ON) 0 V 0.4 V
Logic level high (power supply OFF) 2.40 V 3.40 V
Source current, Vpson = low -- 4 mA
Power up delay: Tpson_on_delay 5 msec 400 msec
Timing Signal Denitions
Turn ON/OFF Timing
Item Description Min Max Units
Tvout_rise 48 V Output rise time 5 300 msec
Tsb_on_delay Delay from AC being applied to 5 Vsb being within regulation. 1500 msec
Tac_on_delay Delay from AC being applied to all output voltages being within regulation. 2000 msec
Tvout_holdup Time all output voltages, including 5 Vsb, stay within regulation after loss of AC. 10 msec
Tpwok_holdup Delay from loss of AC to de-assertion of PWOK 5 msec
Tpson_on_delay Delay from PSON# active to output voltages within regulation limits. 5400 msec
Tpson_pwok Delay from PSON# de-active to PWOK being de-asserted. 50 msec
Tacok_delay Delay from loss of AC input to de-assertion of ACOK#. 10 msec
Tpwok_on Delay from output voltages within regulation limits to PWOK asserted at turn on. 100 1000 msec
Tpwok_off Delay from PWOK de-asserted to 48 V dropping out of regulation limits. 11000 msec
Tpwok_low Duration of PWOK being in the de-asserted state during an off/on cycle using AC
or the PSON# signal.
100 msec
Tsb_vout Delay from 5 Vsb being in regulation to 48 V being in regulation at AC turn on. 50 2000 msec
HPS3000 Series Data Sheet
Signals and Controls - All Models
PWOK# (Power Good)
PWOK# is a power good signal and will be pulled LOW by the power supply to indicate that both the outputs are above the regulation limits of the
power supply. When any output voltage falls below regulation limits or when AC power has been removed for a time sufciently long so that power
supply operation is no longer guaranteed, PWOK will be de-asserted to a HIGH state. The start of the PWOK# delay time shall be inhibited as long
as the 48 V output is in current limit or the 5 Vsb output is below the regulation limit.
PSON# Signal Characteristic
Signal Type Open collector/drain output from power supply. Pullup to 5 Vsb external to the power supply.
PWOK = High ON
PWOK = LOW OFF
MIN MAX
Logic level low voltage, Isink=4mA 0 V 0.8 V
Logic level high voltage, Isource=200μA 2.0 V 4.80 V
Sink current, PWOK = low 4 mA
Source current, PWOK = high 2 mA
PWOK delay: Tpwok on 100 msec 1000 msec
PWOK rise and fall time 100 μsec
Power down delay: Tpwok off 1 msec 1000 msec
Power Supply Present Indicator (PRESENT#)
The PRESENT# signal is primarily used to provide a mechanism by which the host system can sense the number of power supplies physically
present (operational or not). This pin is connected to ground in the power supply.
AC INPUT Present Indicator (ACOK#)
The AC OK# signal is used to indicate presence of AC input to the power supply. This signal shall be connected to 5 Vsb through a resistor on the
host system side. A logic “Low” level on this signal shall indicate AC input to the power supply is present. A Logic “High” on this signal shall
indicate a loss of AC input to the power supply.
Table 12 ACOK# Signal Characteristics
Signal Type Pull-up to 5 Vsb through a resistor in the host system.
PRESENT# = Low Present
PRESENT# = High Not present
MIN MAX
Logic level low voltage, Ising=4mA 0 V 0.8 V
Logic level high voltage, Isink=50μA 2.0 V 4.80 V
Sink current, PRESENT# = Low 4 mA
Source current, PRESENT# = High 50 μA
HPS3000 Series Data Sheet
WORLDWIDE OFFICES
Americas
2900 S.Diablo Way
Tempe, AZ 85282
USA
+1 888 412 7832
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
+44 (0) 1384 842 211
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
+852 2176 3333
For more information: www.artesyn.com/power
For support: productsupport.ep@artesyn.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Artesyn
Embedded Technologies assumes no responsibility, and disclaims all liability for damages resulting from use of
this information or for any errors or omissions. Artesyn Embedded Technologies, Artesyn and the Artesyn
Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc. All other
names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners.
© 2015 Artesyn Embedded Technologies, Inc.
www.artesyn.com
HPS3000 Series DS 01-30-2015
MTBF
The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specication @ 25 °C and 40 °C, ambient, at full load.
With the power supply installed in a system in a 25 °C ambient environment and operating at full load, capacitor life shall be 10 years, minimum for
ALL electrolytic capacitors contained within this power supply. The power supply shall demonstrate a MTBF level of > 500,000 hours.
Quality Assurance
Full QAV testing shall be conducted in accordance with Artesyn Embedded Technologies Standards with reports available upon request.
Warranty
Artesyn Embedded Technologies shall warrant the power supply to be free of defects in materials and workmanship for a minimum period of two
years from the date of shipment, when operated within specications. The warranty shall be fully transferable to the end owner of the equipment
powered by the supply.
Ordering Information
Model Number Main Output Main Output Current Standby Output Standby Current
HPS3000-9 48 Vdc 62.0 A 5.0 V 3.0 A
HPS3000-9-001 48 Vdc 62.0 A 5.0 V 3.0 A
Signals and Controls - All Models
LED INDICATORS
There will be a green POWER LED (PWR) to indicate that AC is applied to the PSU and standby voltage is available when blinking. This same LED
should go solid when the 48 V output is enabled and operational.
There will be an Amber Power Supply Fail LED (FAIL) to indicate that the power supply has failed and a replacement of the unit is necessary. Faults
including UVP, OVP, OTP, or Fan Fail when PSON# is asserted “Logic Low” shall cause the amber LED to turn on. The LED can be turned off by
recycling PSON# signal or by an AC power interruption more than 1 second. The LED shall be off when PSON# is not asserted “Logic Low”. Refer
to table 13 for conditions of the LED’s:
Table 13 LED Indicators
Power Supply Condition Power LED (GREEN) Fail LED (AMBER)
No AC power to PSU OFF OFF
AC present / Standby Output On Blinking OFF
Power supply 48 V output ON and OK ON OFF
Power supply failure (includes overvoltage,
overtemperature)
OFF ON
Current limit ON Blinking
Note: HPS3000-9-001 version is recommended for applications where higher airow is required.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Artesyn Embedded Technologies:
HPS3000-9-001