Advanced Digital Temperature Controller E5AN-H/E5EN-H 1
Advanced Digital Temperature Controller
E5AN-H/E5EN-H(96 x 96 mm and 48 x 96 mm)
A New High-performance Controller:
High Resolution, High Speed, and High Input Accuracy.
With Logic Operations and preventive maintenance functions.
Plus Infrared Port on Front Panel.
High-resolution display with 5 digits/0.01°C display.
High-speed sampling cycle of 60 ms.
High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
Universal inputs on all models (thermocouple, PT, analog) to
handle various sensors with one Controller. Models also available
with Remote SP.
A PV/SV-status display function can be set to displaying
the PV or SV and the status of the Temperature Controller
(auto/manual, RUN/STOP and alarms).
Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
Preventive maintenance for relays using a Control Output ON/OFF
Counter.
Model available with position-proportional control
Main I/O Functions
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
Refer to Safety Precautions on page 22.
• Auto/manual switching
Temperature Controller
status display
• Simple program
function
• Logic operations
Control output ON/OFF
count alarm
PV change rate alarm
Models optional with
RS-485 or RS-232C
communications
Event Inputs
• None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
• Thermocouple/Pt input:
±0.1% of PV
• Analog input:
±0.1% FS
Sampling Period and control
update
• 60 ms
PF Key
(Programmable
key function)
Auxiliary Outputs
• Two
• Three
Remote SP Input
3-line Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit, 11 segment display with high resolution of 0.01°C
Infrared port
E5AN-H E5EN-H
Computer Support Software
CX-Thermo
USB
Control Output 1
(built-in)
• SSR outputs
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 2
(built-in)
• SSR outputs
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
2Advanced Digital Temperature Controller E5AN-H/E5EN-H
Lineup
Note: All controllers can be used for Heating, Cooling and Heating & Cooling control.
Model Number Structure
Model Number Legend
Controllers
1. Type
H: Advanced
2. 3. 4.Control mode, output 1 and output 2
AA: 2 slots for control output module
SS: 2 SSR outputs fitted
PRR: position (valve) control, 2 Relays fitted
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection
(For 1-phase heater applications, 1x CT)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10. Terminal Cover
-500: With Terminal Cover
Note: Casing color is black. White/Silver available on request.
Option Units
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
Output Units
1. Function
RN: relay
QN: pulse (PNP) 12 VDC
Q3: pulse (NPN) 12 VDC
Q4: pulse (PNP) 24 VDC
C3N: linear 4 to 20 mA
C3DN: linear 0 to 20 mA
V34N: linear 0 to 10 V
V35N: linear 0 to 5 V
E5AN-H/E5EN-H
Advanced Type 2 control outputs
1 control output 2 auxiliary outputs
2 auxiliary outputs
Terminal block Universal input
1 2 3 4 5 6 7 8 9 10
E5AN/E5EN-H@@@@@@M@-500
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
1
E53-@
1
E53-@
Advanced Digital Temperature Controller E5AN-H/E5EN-H 3
Ordering Information
E5AN-H
Note: Add power supply voltage to model to complete ordering code
(ie. E5AN-HAA2HBM-500 AC100-240 or E5AN-HAA2HBMD-500 AC/DC24)
Note: Heater alarm = heater burnout + SSR short detection + SSR overcurrent
Note: For output option modules (AA), see “output modules E53-_ N“ on page 2
Size Case
color
Power
supply
voltage
Control
method
Auxiliary
output Control output 1/2 Heater
burnout
Optional functions
Model
Event
inputs
Transfer
output
Remote
setpoint
1/4 DIN
96 × 96 × 78
(W × H × D)
Black
100 to
240 VAC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5AN-HAA2HBM-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5AN-HSS2HBM-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA2HHBFM-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS2HHBFM-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA3BFM-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS3BFM-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5AN-HPRR2BM-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HPRR2BFM-500
24 VAC/
VDC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5AN-HAA2HBMD-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5AN-HSS2HBMD-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA2HHBFMD-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS2HHBFMD-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA3BFMD-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS3BFMD-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5AN-HPRR2BMD-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HPRR2BFMD-500
4Advanced Digital Temperature Controller E5AN-H/E5EN-H
E5EN-H
Note: Add power supply voltage to model to complete ordering code (ie. E5EN-HAA2HBM-500 AC100-240 or E5EN-HAA2HBMD-500
AC/DC24
Note: Heater alarm = heater burnout + SSR short detection + SSR overcurrent
Note: For output option modules (AA), see "output modules E53-_ N" on page 2
Accessories (Order Separately)
USB-infrared Conversion Cable
USB-Serial Conversion Cable
Terminal Cover
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
CX-Thermo Support Software
Size Case
color
Power
supply
voltage
Control
method
Auxil-
iary
output
Control output 1/2 Heater
burnout
Optional Functions
Model
Event
inputs
Transfer
output
Remote
setpoint
1/8 DIN
48 × 96 × 78
(W × H × D)
Black
100 to
240 VAC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5EN-HAA2HBM-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5EN-HSS2HBM-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA2HHBFM-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS2HHBFM-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA3BFM-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS3BFM-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5EN-HPRR2BM-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HPRR2BFM-500
24 VAC/
VDC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5EN-HAA2HBMD-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5EN-HSS2HBMD-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA2HHBFMD-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS2HHBFMD-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA3BFMD-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS3BFMD-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5EN-HPRR2BMD-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HPRR2BFMD-500
Model
E58-CIFIR
Model
E58-CIFQ1
Connectable models Model
E5AN-H E53-COV16
E5EN-H
Connectable models Model
E5AN-H Y92S-P4
E5EN-H Y92S-P5
Hole diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
Model
EST2-2C-MV4
Advanced Digital Temperature Controller E5AN-H/E5EN-H 5
Specifications
Ratings
Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Sensor input
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control
output
Relay output
Output Unit (Install the Output Unit (sold separately).)
Voltage output
(for driving SSR)
Current output
Linear voltage output
Built-in SSR output 75 to 250 VAC, 1 A (resistive load)
Relay output for posi-
tion-proportional con-
trol
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations
min.
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
Auxiliary
output
Number of outputs 2 or 3 max.
Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Event
input
Number of outputs 2 (standard) or 4 (with an E53-AKB)
External contact input
specifications
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Logic
opera-
tions
Number of operations 8 max.
Operations
Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C,
and D are four inputs.)
Delay: ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
Output inversion: Possible
Output One work bit per operation
Work bit
assignment
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
Transfer
outputs
Number of outputs 1 max. (Depends on model. Models with transfer output (F in model number)
Output specifications Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
RSP
input
Number of inputs 1
Signal type Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Analog input scaling Scaling of signal to engineering units (EU)
19,999 to 30,000 (display: 30,000 max.)
Accuracy (±0.2% of FS) ±1 digit max.
Input sampling period 60 ms
Setting method Set digitally using keys on the front panel or by using the RSP input.
Indication method
11-segment digital display and individual indicators (7-segments display emulation also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Bank switching Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection,
40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions,
control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic
operations, automatic cooling coefficient adjustment
Ambient operating temperature 10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)
6Advanced Digital Temperature Controller E5AN-H/E5EN-H
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Platinum resistance
thermometer Thermocouple Analog input
Name Pt100 JPt100 K J T E L U N R S B W PL
II
4 to
20 m
A
0 to
20 m
A
1 to
5V
0 to
5V
0 to
10 V
Temperature range (°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100.0
200.0
2300.0
Usable in the following
ranges by scaling:
19999 to 32400,
1999.9 to 3240.0,
199.99 to 324.00, or
19.999 to 32.400
1800.0
1700.01700.0
1300.0 1300.0 1300.0
850.0 850.0 850.0
600.0
500.0 500.0 500.0
400.0 400.0 400.0 400.0 400.0
200.00 200.00 200.00 200.00
100.0 100.0
100.0
0.0 0.0 0.0 0.0 0.0 0.0
50.00 20.0 50.00100.0 20.0 50.00 50.00 100.0
200.0199.9 199.9 200.0 200.0199.9 200.0 200.0 199.9200.0
Setting
number 01224345 6 21 7 8 22 9 102311121314151617181920 25 26 27 28 29
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Advanced Digital Temperature Controller E5AN-H/E5EN-H 7
Alarm Outputs
Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
1.With set values 1, 4 and 5, the upper and lower limit values can be
set independently for each alarm type, and are expressed as “L”
and “H.”
2. Set value: 1, Upper- and lower-limit alarm
3. Set value: 4, Upper- and lower-limit range
4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
Case 3: Always OFF
5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
6. Displayed when there is a remote SP input.
Set
val-
ue
Alarm type
Alarm output operation
When X is
positive
When X is
negative
0Alarm function
OFF Output OFF
1
1
Upper- and lower-
limit 2
2 Upper limit
3 Lower limit
4
1
Upper- and lower-
limit range 3
5
1
Upper- and lower-
limit with standby
sequence 5
4
6
Upper-limit with
standby
sequence
7
Lower-limit with
standby
sequence
8Absolute-value
upper-limit
9Absolute-value
lower-limit
10
Absolute-value
upper-limit with
standby
sequence
11
Absolute-value
lower-limit with
standby
sequence
12 LBA (for alarm 1
only) ---
13 PV change rate
alarm ---
14
RSP absolute
value upper limit
6
15
RSP absolute
value lower limit
6
ON
OFF SP
LH
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
SP
LH
ON
OFF
SP
LH
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
LH
H < 0, L > 0
H < L
SP
Case 1
LH
H > 0, L < 0
H > L
SP
Case 2
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
H L
SP
LH
H > 0, L < 0
H L
SP
Case 3 (Always ON)
LH
H < 0, L > 0
H < L
SP
Case 1
LH
H > 0, L < 0
H > L
SP
Case 2
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
H L
SP
LH
H > 0, L < 0
H L
SP
Case 3 (Always ON)
8Advanced Digital Temperature Controller E5AN-H/E5EN-H
Characteristics
1. The indication accuracy of K thermocouples in the 200 to 1300°C range, T and N thermocouples at a temperature of
100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a
temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication
accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is
±0.3% of PV or ±3°C, whichever is greater, ±1 digit max.
The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1digit max.
2. Ambient temperature: 10°C to 23°C to 55°C, Voltage range: 15% to 10% of rated voltage
3. K thermocouple at 100°C max.: ±10°C max.
4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
Indication accuracy
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. 1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Influence of temperature
2
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. 3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Influence of voltage 2
Input sampling period 60 ms
Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s)
Control period 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range 19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
Weight E5AN-H Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
E5EN-H Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5AN-H and E5EN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-H or E5EN-H. 4
Standards
Approved
standards UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMC
EMI: EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Power Frequency Magnetic Field Immunity: EN 61000-4-8
Voltage Dip/Interrupting Immunity: EN 61000-4-11
Advanced Digital Temperature Controller E5AN-H/E5EN-H 9
USB-Serial Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
Note: The baud rate, data bit length, stop bit length, and vertical parity
can be individually set using the Communications Setting
Level.
Current Transformer (Order Separately)
Ratings
USB-Infrared Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
1. For heater burnout alarms, the heater current will be measured when
the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is lower than the set value
(i.e., heater burnout detection current value).
2. For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output assigned to the alarm 1 function
will turn ON if the heater current is higher than the set value (i.e., SSR
failure detection current value).
3. For heater overcurrent alarms, the heater current will be measured
when the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set value
(i.e., heater overcurrent detection current value).
Applicable OS Windows 2000, XP, or Vista
Applicable software Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H
USB interface standard Conforms to USB Specification 1.1.
DTE speed 38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Setup
Tool port (on bottom of Controller)
Power supply Bus power (Supplied from USB
host controller.)
Power supply voltage 5 VDC
Current consumption 70 mA
Ambient operating tempera-
ture
0 to 55°C (with no condensation or
icing)
Ambient operating humidity 10% to 80%
Storage temperature 20 to 60°C (with no condensation
or icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 100 g
Transmission line
connection method
RS-485, RS-422: Multipoint
RS-232C: Point-to-point
Communications RS-485 (two-wire, half duplex)
RS-422 (four-wire, half duplex) or RS-232C
Synchronization
method Start-stop synchronization
Protocol CompoWay/F, SYSWAY, or Modbus
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Transmission code ASCII (CompoWay/F, SYSWAY)
RTU (Modbus)
Data bit length 7 or 8 bits
Stop bit length 1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control None
Interface RS-485, RS-422, or RS-232C
Retry function None
Communications
buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
Dielectric strength 1,000 VAC for 1 min
Vibration resistance 50 Hz, 98 m/s2
Weight E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only) Armatures (2)
Plugs (2)
Applicable OS Windows 2000, XP, or Vista
Applicable software Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models E5AN-H/E5EN-H
USB interface standard Conforms to USB Specification 1.1.
DTE speed 38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Infrared
port (on front of Controller)
Power supply Bus power (Supplied from USB
host controller.)
Power supply voltage 5 VDC
Current consumption 80 mA
Ambient operating tempera-
ture
0 to 55°C (with no condensation or
icing)
Ambient operating humidity 10% to 80%
Storage temperature 20 to 60°C (with no condensation
or icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 130 g (with mounting
adaptor)
CT input
(for heater current detec-
tion)
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
Maximum heater current 50 A AC
Input current indication
accuracy ±5% FS ±1 digit max.
Heater burnout alarm set-
ting range 1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm setting
range 2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent alarm
setting range 3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
10 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Electrical Life Expectancy Curve
for Relays (Reference Values)
SSR Outputs (OUT1/OUT2) Ratings
Rated load voltage: 75 to 250 VAC
Rated load current: 1 A (resistive load)
Note: 1. The load current must be within the derating curve.
2. There is no zero-cross function.
Derating Curve for SSR Outputs (Reference Values)
Condition A: SSR outputs 100% ON
Condition B: SSR outputs 50% ON with 2-s control cycle
500
300
100
50
30
10
5
3
1
0123456
E5AN-H/E5EN-H
250 VAC, 30 VDC
(resistive load)
cosφ = 1
Switching current (A)
Life (× 104 operations)
1.5
1.25
1
0.75
0.5
0.25
0
10 0 10 20 30 40 50 5545 60
Ambient temperature (°C)
Load current I (A) OUT1/OUT2
Condition A
Condition B
Advanced Digital Temperature Controller E5AN-H/E5EN-H 11
External Connections
A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
Output Unit
Control outputs 1, 2
Relay Outputs
250 VAC, 5 A
(resistive load)
SSR Outputs
75 to 250 VAC, 1A
(resistive load)
Models with Position-
proportional Control
250 VAC, 1 A
(including inrush
current)
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
4 to 20 mA DC
(Load: 600 Ω max.)
4 to 20 mA DC
21
22
23
24
25
26
27
28
29
30
EV4
EV3
Transfer output
Remote SP input
DON’T USE
100 to 240 VAC
24 VAC/VDC (no polarity)
Input power
supply
Auxiliary output 2
Control output 1
Control output 2
CT2
CT1
CT2
DON’T
USE
DON’T
USE
Auxiliary output 1
Control outputs 1, 2
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
Auxiliary outputs 1, 2
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
Auxiliary output 3
Potentiometer
B
V
mA
DON’T
USE
DON’T
USE
B
A
C
W
O
DON’T
USE
DON’T
USE
DON’T
USE
Auxiliary output 3
14
15
16
mA V t/c Pt
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, or input alarm is sent
to the output to which the
alarm 1 function is assigned.
RDB
RDA
SG
SDB
SDA
EV1
EV2
Event Inputs
Communications
B (+)
A ()
DO NOT USE
B (+)
A ()
11
12
13
21
22
E53-EN03
RS-485
11
12
13
21
22
E53-EN01
RS-232C
SD
RD
SG
DO NOT USE
DO NOT USE
11
12
13
21
22
E53-AKB
11
12
13
21
22
E53-EN02
RS-422
Option UnitsControllers
12 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Nomenclature
Dimensions (Unit: mm)
PF
A/M
SUB3
HA
SUB2
OUT2
OUT1
CMW
RSP
STOP
MANU
SUB1
MV
SV
PV
Ir
E5AN-H
Operation indicators No.1 display
No.2 display
No.3 display
Up Key
Down Key
Temperature unit
Mode KeyLevel Key
Programmable
Function Key/
Auto/Manual Key
E5AN-H E5EN-H
Ir
PF
A/M
MV
SV
PV
SUB2
SUB3
STOPOUT1
RSP
MANU
CMWOUT2
SUB1
HA
E5EN-H
Operation indicators
Temperature unit
Operation indicators
Mode Key
Level Key
No.1 display
No.2 display
No.3 display
Up Key
Down Key
Programmable
Function Key/
Auto/Manual Key
Mounting Bracket
(Accessory)
Waterproof
Packing
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
96 × 96 112 91
79.2
6
2
92+0.8
0
92+0.8
0
92+0.8
0 (96 × number of units − 3.5)+1.0
0
120 min. Group mounting does not
allow waterproofing.
Mounted Separately Group Mounted
Recommended panel thickness is 1 to
8mm.
Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
E5AN-H
Group mounting is not possible if an SSR output is used for
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit
is used. For these combinations, maintain the following mounting
space between Controllers.
92+0.8
0
92+0.8
0
110 min.
120 min.
Advanced Digital Temperature Controller E5AN-H/E5EN-H 13
Mounting Bracket
(Accessory)
Waterproof
Packing
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
96 112
48
79.2
6
91
2
E5EN-H
92+0.8
0
92+0.8
0
45+0.6
0
120 min.
(48 × number of units − 2.5)+1.0
0
Group mounting does not
allow waterproofing.
Mounted Separately Group Mounted
Recommended panel thickness is 1 to 8 mm.
Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
When two or more Controllers are mounted, make sure
that the surrounding temperature does not exceed the
allowable operating temperature specified in the
specifications.
Group mounting is not possible if an SSR output is used for control
output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used.
For these combinations, maintain the following mounting space
between Controllers.
45+0.6
0
60 min.
120 min.
92+0.8
0
14 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Accessories (Order Separately)
(2,000) 54
4.6 dia.
35.8
17.8
USB connector (type A plug)
LED indicator: RD LED indicator: SD
USB-Infrared Conversion Cable
E58-CIFIR
USB-Infrared Conversion Cable
16
99.2
18.5
23.1
(75)
21.8
39
Mounting Adapter
(Accessory)
With Mounting Adapter Connected
Mounting Adapter
(2,100)
250 1,765
USB connector (type A plug) Serial connecto
r
LED indicator: RD
LED indicator: SD
USB-Serial Conversion Cable
E58-CIFQ1
Terminal Covers
E53-COV16 (Six Covers provided.)
10
1.2 3.2
44.8
Advanced Digital Temperature Controller E5AN-H/E5EN-H 15
Current Transformers
Waterproof Packing
Y92S-P4 (for DIN 96 × 96) Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Y92S-P5 (for DIN 48 × 96)
E54-CT3 Accessory
Armature
30
21
15 5.8 dia.
25 3
40
10.5
2.8
7.5
10
Two, 3.5 dia.
40 × 40
30
12 dia.
9
2.36 dia.
15
30
Two, M3 (depth 4)
Approx. 3 dia.
18
(22)
Approx. 6 dia.
Plug
Armature
Lead
E54-CT1
E54-CT3
Connection Example
Plug
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
Distortion
factor 10%
3%
1%
100 Ω
RL = 10 Ω
10
1
100 mV
10
1
100 μV
10
1 kΩ
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
3%
1%
1 kΩ
100 Ω
50 Ω
RL = 10 Ω
500 Ω
Distor-
tion
factor
10%
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
10
1
100 mV
10
1
100 μV
10
16 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Advanced Digital Temperature Controller E5AN-H/E5EN-H 17
Operation
E5EN-H / E5AN-H
1. You can return to the operation level by executing a software reset.
2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
3. From the manual control level, key operations can be used to move to the operation level only.
4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H)
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999
and above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).
These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays.
No.1 display Meaning Action Status at error
Control output Alarm output
s.err (S. Err) Input error
Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the
input type. OFF Operates as above
the upper limit.
e333 (E333)
A/D
converter
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF OFF
e111 (E111) Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF OFF
Start in manual mode.
Press the O Key or the
PF Key for at least 1 s. 4
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
25.0
100.0
c
a-m
25.0
100.0
c
Power ON
Manual
Control Level
Manual
mode
Operation
Level
Press the O Key
for at least 1 s.
Input password.
Input password while
amov is displayed.
(Set value 169)
Press the
O Key less than 1 s.
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
Control stops.
Press the
O Key for less than 1 s.
Press the O+
M Keys for at
least 1 s.
Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)
Protect Level
Control in progress
Level change
Not displayed for some models
Control stopped
Start in automatic mode.
Adjustment
Level
PF Key 5
PF Key
5
Initial Setting
Level
Monitor/Setting
Item Level
Advanced Function
Setting Level
Calibration Level
Press the PF Key
for at least 1 s.
Communica-
tions Setting
Level
Press the
O Key less than 1 s.
Press the
O Key less
than 1 s.
Press the O Key
for at least 1 s.
PID Setting
Level
Bank Setting
Level
Press the
O Key less
than 1 s.
3
4
1
2
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
18 Advanced Digital Temperature Controller E5AN-H/E5EN-H
PID Setting Level
d. pid
3
d. pid
2
d. pid
1
d.pid
8
Display PID Selection
PID1
M
M
M
M
M
M
1. oll
-5.0
M
M
M
M
PID 8 Proportional Band
M
M
M
M
M
8.p
8.0
l
-5 . 0
8.d
40 . 0
h
105 . 0
M
M
M
8.ol
8. ol
1. p
8.0
1. i
2 33.0
1.d
40 . 0
1.olh
1 05.0
1.aut
1 320.0
1.csc
1. 0 0
1. lba
0
8.i
2 33. 0
8. aut
13 20.0
sc
1. 0 0
8. c
8.lba
0
c
c
Power ON
c
c
d.bnk
2
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
0.lsp
0. 0
0.pid
1
0. s p r
off
0. 0
-1 0.a
1h
0.0
0. a
1l
0.0
0.a
0. 0
-2
0.a
2h
0.0
0. a
2l
0.0
0. a
0.0
-3 0.a
3h
0.0
0. a
3l
0.0
0.a
1
0. s o k
off
0.w t b
2l
0.0
7. a
0.0
-3 7.a
3h
0. 0
7. a
3l
0. 0
7. a
1
7. s o k
of f
7. w t b
7.lsp
0.0
7.pid
1
7.s p r
of f
1h
0. 0
7. a
1l
0. 0
7.a
2h
0.0
7. a
d.bnk
7
-1
7.a
0.0
d. bnk
2
d.bnk
1
d.bnk
0
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
0.0
-2
7.a
c
M
M
c
c
c
c
Manual Control
Level
Operation
Level
Initial Setting
Level
Advanced
Function Setting
Level
Communica-
tions Setting
Level
Adjustment
Level
Protect Level Monitor/Setting
Item Level
PID Setting
Level
Bank Setting
Level
Bank Setting Level
Press the O Key less than 1 s.
Press the O Key less than 1 s. Press the O Key less than 1 s.
PID2
PID3
PID8
PID 8 Integral Time
PID 8 Derivative Time
PID 8 MV Upper Limit
PID 8 MV Lower Limit
PID 8 Automatic Selection
Range Upper Limit
PID 8 Cooling Coefficient
PID 8 LBA Detection Time
Display Bank Selection
Bank0
Bank1
Bank2
Bank7
Bank 7 SP
Bank 7 PID
Set No.
Bank 7 SP
Ramp Set Value
Bank 7
Alarm Value 1
Bank 7
Alarm Value
Upper Limit 1
Bank 7
Alarm Value
Lower Limit 1
Set either of these parameters
Set either of these parameters
Set either of these parameters
Bank 7
Alarm Value 2
Bank 7
Alarm Value
Upper Limit 2
Bank 7
Alarm Value
Lower Limit 2
Bank 7
Alarm Value 3
Bank 7
Alarm Value
Upper Limit 3
Bank 7
Alarm Value
Lower Limit 3
Bank 7 Soak Time
Bank 7 Wait Band
E5EN-H / E5AN-H
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157).
Advanced Digital Temperature Controller E5AN-H/E5EN-H 19
25.0
c
al1l
0.0
c
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
25.0
c
25.0
0.0
c
a-m
bank
0
rsp
0.0
sp-m
0.0
ct1
0.0
ct2
0.0
lcr1
0.0
lcr2
0.0
prst
rset
sktr
0
r-s
run
al-1
0.0
c
al-2
0.0
c
al2h
0.0
c
al2l
0.0
c
al-3
0.0
c
al3h
0.0
al3l
0.0
o
0.0
c-o
0.0
v-m
0.0
al1h
0.0
c
PF PF
PF
PF
25.0
0.0
c
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
l.adj
at
off
cmwt
off
irda
off
spmd
lsp
ct1
0.0
ins
0.00
c
insh
0.00
c
insl
0.00
c
p
8.0
c
i
233.0
d
40.0
c-sc
1.00
c-db
0.0
of-r
50.0
hys
1.0
chys
1.0
soak
1
wt-b
off
mv-s
0.0
mv-e
0.0
sprt
off
ol-h
105.0
ol-l
-5.0
db
2.0
oc-h
0.8
sqrp
0.0
M
orl
M
0.0
M
M
M
M
M
M
M
M
ct2
0.0
lcr1
0.0
lcr2
0.0
hb1
0.0
hb2
0.0
hs1
50.0
hs2
50.0
oc1
50.0
oc2
50.0
M
100.0
Starting in manual mode.
Power ON
Starting in
automatic
mode.
Manual Control Level
PID
Control
only
PV/MV
Press the O Key less than 1 s.
Operation Level
Adjustment Level
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
AT Execute/Cancel
Communications
Writing
Heater Current 1
Value Monitor
Heater Burnout
Detection 1
Heater Overcurrent
Detection 1
Heater Current 2
Value Monitor
Heater Burnout
Detection 2
Heater Overcurrent
Detection 2
Leakage Current 1
Monitor
Leakage Current 2
Monitor
HS Alarm 1
HS Alarm 2
Temperature Input Shift
1-point shift
2-point shift
Upper Limit
Temperature
Input Shift Value
Lower Limit
Temperature
Input Shift Value
Proportional Band
Integral Time
PID settings
Derivative Time
Cooling Coefficient
Heating/cooling
Dead Band
Manual Reset Value
Clear the offset during
stabilization of P or PD
control.
Hysteresis (Heating)
Hysteresis (Cooling)
Hysteresis settings
Soak Time
Wait Band
MV at Stop
MV at PV Error
SP Ramp Set Value
MV Upper Limit
MV Lower Limit
MV Change Rate Limit
Process Value
Added when Additional
PV display is ON.
Process Value/
Set Point
Auto/Manual Switch
PID control only.
Added when
auto/manual select
addition is ON.
Set Point During
SP Ramp
Heater Current 1 Value
Monitor
Heater Current 2 Value
Monitor
Leakage Current 1
Monitor
Leakage Current 2
Monitor
Program Start
Soak Time Remain
Press the O
and M Keys for
at least 3 s.
RUN/STOP
Alarm Value 1
Set either of these parameters.
Alarm Value
Upper Limit 1
Alarm Value
Lower Limit 1
Alarm Value 2
Set either of these parameters.
Alarm Value
Upper Limit 2
Alarm Value
Lower Limit 2
Alarm Value 3
Alarm Value
Upper Limit 3
Alarm Value
Lower Limit 3
Set either of these parameters.
MV Monitor (Heating)
MV Monitor (Cooling)
Press the PF Key
for at least 1 s.
Press the O
Key or the PF
Key for at least
1 s. 1
Press
the O
Key for
at least
3 s.
Set either
of these
param-
eters.
Extraction of Square
Root
Low-cut Point
Press the O
and M Keys for
at least 1 s.
PF Key 2
PF Key 2
Monitor/Setting Item Level
(E5AN-H/E5EN-H only)
Monitor/Setting
Item Display 1
Monitor/Setting
Item Display 2
Monitor/Setting
Item Display 3
Monitor/Setting
Item Display 4
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
Infrared Communications Use
SP Mode
Position Proportional
Dead Band
Open/Close Hysteresis
Bank No.
Remote SP Monitor
Valve Opening
Monitor
1
1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
20 Advanced Digital Temperature Controller E5AN-H/E5EN-H
M
M
M
M
M
M
M
pmov
0
oapt
0
icpt
0
wtpt
off
pfpt
off
pmsk
on
prlp
0
M
M
M
M
M
M
M
psel
cwf
u-no
1
bps
9.6
len
7
sbit
2
prty
even
sdwt
20
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300.0
c
sl-l
-200.0
c
cntl
pid
s-hc
stnd
st
on
ptrn
off
cp
20
c-cp
20
alt1
2
alt2
2
alt3
2
tr-t
off
tr-h
100.0
tr-l
0.0
o1-t
4-20
clfl
flot
calb
off
mot
30
off
sqr
amov
0
M
M
pbnk
7
M
alh1
0.2
c
M
alh2
0.2
c
M
alh3
0.2
c
M
M
M
M
ev-1
none
ev-2
stop
ev-3
none
ev-4
none
M
ev-b
1
M
orev
or-r
ST (Self-tuning)
Protect Level Communications
Setting Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
Move to Protect Level:
Displayed only when a password
is set. Restricts moving to protect
level.
Operation/Adjustment
Protect:
Restricts displaying and
modifying menus in
operation, adjustment, and
manual control levels.
Initial Setting/
Communications Protect:
This protect level restricts
movement to the initial setting,
communications setting, and
advanced function setting levels.
Setting Change Protect:
Protects changes to setups
by operating the front panel
keys.
Password to Move to
Protect Level:
Password setting
PF Key Protect
Restricts PF key operation
(E5AN-H/E5EN-H only)
Parameter Mask Enable:
Displayed only when a
parameter mask is set.
Protocol Setting:
Switches between
CompoWay/F (SYSWAY)
and Modbus.
Communications Unit No.
Communications
Baud Rate
CompoWay/F
(SYSWAY) only
Communications
Data Length
Communications
Stop Bits
Communications Parity
Send Data Wait Time
Press the O Key for at least 1 s.
Press the O Key less than 1 s.
Initial Setting Level
Input Type
Scaling Upper Limit
Scaling Lower Limit
Decimal Point
For input type of analog
Temperature Unit
°C, °FFor input type of
temperature
SP Upper Limit
SP Lower Limit
Limit the set point
PID ON/OFF
Standard or
Heating/Cooling
For input type of
temperature,
standard control, or
PID
Program Pattern
When assigning PID or
control output to ON/OFF
output
Control Period (Heating)
Control Period (Cooling)
Set the ON/OFF
output cycle.
Direct/Reverse Operation
Alarm 1 Type
Alarm 1
Hysteresis
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Press the O Key less than 1 s.
Alarm 2 Type
Alarm 3 Type
Alarm 2
Hysteresis
Alarm 3
Hysteresis
Transfer Output Type
Linear output
Transfer Output
Upper Limit
Transfer Output
Lower Limit
Linear Current Output
Linear output
Bank Numbers Used
Event Input
Assignment 1
Event Input
Assignment 2
Event Input
Assignment 3
Event Input
Assignment 4
Extraction of Square
Root Enable
Move to Advanced Function
Setting Level:
Displayed when initial
setting/ communications
protect is set to 0.
Move by setting password (169).
Valid Program Bank
Closed/Floating
Motor Calibration
Travel Time
Advanced Digital Temperature Controller E5AN-H/E5EN-H 21
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
init
off
M
M
M
M
M
M
M
spru
m
rest
a
sb1n
n-o
sb2n
n-o
sb3n
n-o
hbh
0.1
hbu
on
hbl
off
M
a3lt
ret
o-dp
M
M
M
M
M
M
M
M
M
M
M
M
M
M
off
off
off
M
M
M
st-b
15.0
c
alfa
0.65
at-g
at-h
lcma
20.0
inf
0.0
pvad
off
a1lt
off
a2lt
off
prlt
3
sero
off
colr
red
rlrv
off
pv-b
5.0
c
M
cjc
on
M
M
M
M
M
M
M
M
M
M
M
M
istp
ins1
mvse
off
amad
on
rt
off
hsu
on
hsl
off
hsh
0.1
lba
0
lbab
3.0
c
out1
o
out2
none
8.0
clbal p-db
0.0
M
M
M
M
M
M
M
M
M
M
M
M
M
rspu
off
rsph
1300.0
rspl
-200.0
sptr
off
rseo
off
pidh
0.50
manl
off
pmvd
off
pvrp
17
csca
off
pidi
pv
pfd1
1
pfd2
0
pfd3
0
pfd4
0
pfd5
0
spdp
4
odsl
o
pvdp
on
pvst
off
svst
off
ra1m
0
ra2m
0
ra1
0
ra2
0
rac
0
cmov
0
c
c
c
c
M
M
M
M
M
0
a1on
0
a2on
0
a3on
0
a1of
a2of
0
a3of
0
M
M
M
M
sub1
alm1
sub2
alm2
csel
on
t-u
m
sub3
alm3
M
M
ocl
off
ocu
on
och
0.1
M
pf
a-m
0.8
1.0
M
alsp
sp-m
M
M
M
d.ref
0.25
0
RT
Press the O Key for at least 1 s.
Advanced Function Setting Level
Parameter Initialization
SP Ramp Time Unit
Standby Sequence
Reset
Auxiliary Output 1
Open in Alarm
Auxiliary Output 2
Open in Alarm
Auxiliary Output 3
Open in Alarm
HB ON/OFF
Heater Burnout
Latch
Heater Burnout
Hysteresis
ST Stable Range
AT Calculated Gain
α
AT Hysteresis
Limit Cycle MV
Amplitude
Input Digital Filter
Additional PV Display
MV Display
Automatic Display
Return Time
Alarm 1 Latch
Alarm 2 Latch
Alarm 3 Latch
Move to Protect Level
Time
Input Error Output
Cold Junction
Compensation
Method
MB Command
Logic Switching
PV Change Color
PV Stable Band
Alarm 1 ON Delay
Alarm 2 ON Delay
Alarm 3 ON Delay
Alarm 1 OFF Delay
Alarm 2 OFF Delay
Alarm 3 OFF Delay
Input Shift Type
MV at Stop and Error
Addition
Auto/Manual Select
Addition
HS Alarm Use
HS Alarm Latch
HS Alarm Hysteresis
LBA Detection Time
LBA Level
LBA Band
Control Output 1
Assignment
Control Output 2
Assignment
Auxiliary Output 1
Assignment
Auxiliary Output 2
Assignment
Auxiliary Output 3
Assignment
(E5AN/E5EN-H only)
Character Select
Soak Time Unit
Alarm SP Selection
Manual MV
Limit Enable
PV Rate of Change
Calculation Period
Automatic Cooling
Coefficient Adjustment
Heater Overcurrent
Use
Heater Overcurrent
Latch
Heater Overcurrent
Hysteresis
Move to Calibration
Level
PF Setting
Monitor/Setting Item 1
Monitor/Setting Item 2
Monitor/Setting Item 3
Monitor/Setting Item 4
Monitor/Setting Item 5
"PV/SP" Display
Screen Selection
MV Display Selection
PV Decimal Point
Display
PV Status Display
Function
SV Status Display
Function
Display Refresh
Period
Control Output 1
ON/OFF Count
Monitor
Control Output 2
ON/OFF Count
Monitor
Control Output 1
ON/OFF Count
Alarm Set Value
Control Output 2
ON/OFF Count
Alarm Set Value
ON/OFF Counter
Reset
Power ON
Manual Control
Level
Operation
Level
Initial Setting
Level
Adjustment
Level
Protect Level Monitor/Setting
Item Level
PID Setting
Level
Bank Setting
Level
Remote SP Enable
Remote SP
Upper Limit
Remote SP
Lower Limit
SP Tracking
Remote SP Input
Error Output
PID Set Automatic
Selection Data
PID Set Automatic
Selection Hysteresis
PV Dead Band
Direct Setting of
Position Proportional MV
Advanced
Function Setting
Level
Communica-
tions Setting
Level
22 Advanced Digital Temperature Controller E5@N/E5@N-H
Safety Precautions
!CAUTION
1. An SELV circuit is one separated from the power supply with
double insulation or reinforced insulation, that does not exceed
30 V r.m.s. and 42.4 V peak or 60 VDC.
2. A class 2 power supply is one tested and certified by UL as having
the current and voltage of the secondary output restricted to
specific levels.
3. The tightening torque for E5CN-U is 0.5 N·m.
Precautions for Safe Use
Be sure to observe the following precautions to prevent malfunction
or adverse affects on the performance or functionality of the product.
Not doing so may occasionally result in faulty operation.
1. This product is specifically designed for indoor use only.
Do not use this product in the following places:
Places directly subject to heat radiated from heating equipment.
Places subject to splashing liquid or oil atmosphere.
Places subject to direct sunlight.
Places subject to dust or corrosive gas (in particular, sulfide gas
and ammonia gas).
Places subject to intense temperature change.
Places subject to icing and condensation.
Places subject to vibration and large shocks.
2. Use and store the product within the rated ambient temperature
and humidity.
Gang-mounting two or more Temperature Controllers, or mounting
Temperature Controllers above each other may cause heat to build
up inside the Temperature Controllers, which will shorten their
service life. In such a case, use forced cooling by fans or other
means of air ventilation to cool down the Temperature Controllers.
3. To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
4. Be sure to wire properly with correct polarity of terminals.
5. Use the specified size (M3.5, width 7.2 mm or less) crimped
terminals for wiring. To connect bare wires to the terminal block,
use stranded or solid copper wires with a gage of AWG24 to
AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm2).
(The stripping length is 5 to 6 mm.) Up to two wires of the same
size and type or two crimp terminals can be inserted into a single
terminal.
6. Do not wire the terminals that are not used.
7. To avoid inductive noise, keep the wiring for the product’s terminal
block away from power cables carry high voltages or large
currents. Also, do not wire power lines together with or parallel to
product wiring. Using shielded cables and using separate conduits
or ducts is recommended.
Attach a surge suppressor or noise filter to peripheral devices that
generate noise (in particular, motors, transformers, solenoids,
magnetic coils, or other equipment that have an inductance
component).
When a noise filter is used at the power supply, first check the
voltage or current, and attach the noise filter as close as possible
to the product.
Allow as much space as possible between the product and devices
that generate powerful high frequencies (high-frequency welders,
high-frequency sewing machines, etc.) or surge.
8. Use this product within the rated load and power supply.
9. Make sure that the rated voltage is attained within two seconds of
turning ON the power using a switch or relay contact. If the voltage
is applied gradually, the power may not be reset or output
malfunctions may occur.
10.Make sure that the Temperature Controller has 30 minutes or
more to warm up after turning ON the power before starting actual
control operations to ensure the correct temperature display.
Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to
electric shock.
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or filings from installation to enter the
product. Doing so may occasionally result in electric
shock, fire, or malfunction.
Do not use the product where subject to flammable or
explosive gas. Otherwise, minor injury from explosion
may occasionally occur.
Do not leave the cable for the Support Software
connected to the product. Malfunction may occur due to
noise in the cable.
Do not use the Temperature Controller or Conversion
Cable if it is damaged. Doing so may occasionally result
in minor electric shock or fire.
Never disassemble, modify, or repair the product or touch
any of the internal parts. Minor electric shock, fire, or
malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This product is UL listed as Open Type Process
Control Equipment. It must be mounted in an
enclosure that does not allow fire to escape externally.
b) More than one disconnect switch may be required to
de-energize the equipment before servicing the
product.
c) Signal inputs are SELV, limited energy. 1
d) Caution: To reduce the risk of fire or electric shock, do
not interconnect the outputs of different Class 2
circuits. 2
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Always consider the application conditions and use the
output relays within their rated load and electrical life
expectancy. The life expectancy of output relays varies
considerably with the output load and switching
conditions.
Tighten the terminal screws to between 0.74 and
0.90 N·m. 3 Loose screws may occasionally result in
fire.
Set the parameters of the product so that they are
suitable for the system being controlled. If they are not
suitable, unexpected operation may occasionally result in
property damage or accidents.
A malfunction in the product may occasionally make
control operations impossible or prevent alarm outputs,
resulting in property damage. To maintain safety in the
event of malfunction of the product, take appropriate
safety measures, such as installing a monitoring device
on a separate line.
A semiconductor is used in the output section of long-life
relays. If excessive noise or surge is impressed on the
output terminals, a short-circuit failure is likely to occur. If
the output remains shorted, fire will occur due to
overheating of the heater or other cause. Take measures
in the overall system to prevent excessive temperature
increase and to prevent fire from spreading.
Do not allow pieces of metal or wire cuttings to get inside
the cable connector for the Support Software. Failure to
do so may occasionally result in minor electric shock, fire,
or damage to equipment.
Do not allow dust and dirt to collect between the pins in
the connector on the Conversion Cable. Failure to do so
may occasionally result in fire.
When inserting the body of the Temperature Controller
into the case, confirm that the hooks on the top and
bottom are securely engaged with the case. If the body of
the Temperature Controller is not inserted properly, faulty
contact in the terminal section or reduced water
resistance may occasionally result in fire or malfunction.
When connecting the Control Output Unit to the socket,
press it in until there is no gap between the Control
Output Unit and the socket. Otherwise contact faults in
the connector pins may occasionally result in fire or
malfunction.
Advanced Digital Temperature Controller E5@N/E5@N-H 23
11.When executing self-tuning, turn ON power to the load (e.g.,
heater) at the same time as or before supplying power to the
product. If power is turned ON to the product before turning ON
power to the load, self-tuning will not be performed properly and
optimum control will not be achieved.
12.A switch or circuit breaker must be provided close to the product.
The switch or circuit breaker must be within easy reach of the
operator, and must be marked as a disconnecting means for this
unit.
13.Always turn OFF the power supply before pulling out the interior of
the product, and never touch nor apply shock to the terminals or
electronic components. When inserting the interior of the product,
do not allow the electronic components to touch the case.
14.Do not use paint thinner or similar chemical to clean with. Use
standard grade alcohol.
15.Design the system (e.g., control panel) considering the 2 seconds
of delay that the product's output to be set after power ON.
16.The output may turn OFF when shifting to certain levels. Take this
into consideration when performing control.
17.The number of EEPROM write operations is limited. Therefore,
use RAM write mode when frequently overwriting data during
communications or other operations.
18.Always touch a grounded piece of metal before touching the
Temperature Controller to discharge static electricity from your
body.
19.Do not remove the terminal block. Doing so may result in failure or
malfunction.
20.Control outputs (for driving SSR) that are voltage outputs are not
isolated from the internal circuits. When using a grounded
thermocouple, do not connect any of the control output terminals
to ground. (Doing so may result in an unwanted circuit path,
causing error in the measured temperature.)
21.When replacing the body of the Temperature Controller, check the
condition of the terminals. If corroded terminals are used, contact
failure in the terminals may cause the temperature inside the
Temperature Controller to increase, possibly resulting in fire. If the
terminals are corroded, replace the case as well.
22.Use suitable tools when taking the Temperature Controller apart
for disposal. Sharp parts inside the Temperature Controller may
cause injury.
23.Before connecting an Output Unit, confirm the specifications and
thoroughly read relevant information in the datasheet and manual
for the Temperature Controller.
24.Check the orientation of the connectors on the Conversion Cable
before connecting the Conversion Cable. Do not force a
connector if it does not connect smoothly. Using excessive force
may damage the connector.
25.Do not place heavy object on the Conversion Cable, bend the
cable past its natural bending radius, or pull on the cable with
undue force.
26.Do not connect or disconnect the Conversion Cable while
communications are in progress. Product faults or malfunction
may occur.
27.Make sure that the Conversion Cable's metal components are not
touching the external power terminals.
28.Do not touch the connectors on the Conversion Cable with wet
hands. Electrical shock may result.
29.Before using infrared communications, correctly attach the
enclosed Mounting Adapter to the cable for the Support Software.
When connecting the infrared port on the cable to the Support
Software into the Adapter, insert the connector to the specified
line. Communications may not be possible if the connector is not
connected properly.
Precautions for Correct Use
Service Life
1. Use the product within the following temperature and humidity
ranges:
Temperature: 10 to 55°C (with no icing or condensation)
Humidity: 25% to 85%
If the product is installed inside a control board, the ambient
temperature must be kept to under 55°C, including the temperature
around the product.
2. The service life of electronic devices like Temperature Controllers
is determined not only by the number of times the relay is switched
but also by the service life of internal electronic components.
Component service life is affected by the ambient temperature: the
higher the temperature, the shorter the service life and, the lower
the temperature, the longer the service life. Therefore, the service
life can be extended by lowering the temperature of the
Temperature Controller.
3. When two or more Temperature Controllers are mounted
horizontally close to each other or vertically next to one another,
the internal temperature will increase due to heat radiated by the
Temperature Controllers and the service life will decrease. In such
a case, use forced cooling by fans or other means of air ventilation
to cool down the Temperature Controllers. When providing forced
cooling, however, be careful not to cool down the terminals
sections alone to avoid measurement errors.
Measurement Accuracy
1. When extending or connecting the thermocouple lead wire, be sure
to use compensating wires that match the thermocouple types.
2. When extending or connecting the lead wire of the platinum
resistance thermometer, be sure to use wires that have low
resistance and keep the resistance of the three lead wires the
same.
3. Mount the product so that it is horizontally level.
4. If the measurement accuracy is low, check to see if input shift has
been set correctly.
Waterproofing
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66
Rear case: IP20, Terminal section: IP00
(E5CN-U: Front panel: IP50, rear case: IP20, terminals: IP00)
Operating Precautions
1. It takes approximately two seconds for the outputs to turn ON from
after the power supply is turned ON. Due consideration must be
given to this time when incorporating Temperature Controllers in a
sequence circuit.
2. When using self-tuning, turn ON power for the load (e.g., heater)
at the same time as or before supplying power to the Temperature
Controller. If power is turned ON for the Temperature Controller
before turning ON power for the load, self-tuning will not be
performed properly and optimum control will not be achieved.
3. When starting operation after the Temperature Controller has
warmed up, turn OFF the power and then turn it ON again at the
same time as turning ON power for the load. (Instead of turning
the Temperature Controller OFF and ON again, switching from
STOP mode to RUN mode can also be used.)
4. Avoid using the Controller in places near a radio, television set, or
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller.
Others
1. The disk that is included with the Conversion Cable is designed for
a computer CD-ROM driver. Never attempt to play the disk in a
general-purpose audio player.
2. Do not connect or disconnect the Conversion Cable connector
repeatedly over a short period of time. The computer may
malfunction.
3. After connecting the Conversion Cable to the computer, check the
COM port number before starting communications. The computer
requires time to recognize the cable connection. This delay does
not indicate failure.
4. Do not connect the Conversion Cable through a USB hub. Doing
so may damage the Conversion Cable.
5. Do not use an extension cable to extend the Conversion Cable
length when connecting to the computer. Doing so may damage
the Conversion Cable.
6. The E5AN-H/E5EN-H use the same port for communications
through the infrared port and the Support Software port. Do not
attempt to use communications through the Support Software port
when the infrared port is being used.
24 Advanced Digital Temperature Controller E5@N/E5@N-H
Mounting
Mounting to a Panel
For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting
several Controllers. Waterproof packing is not necessary when there
is no need for the waterproofing function.
E5EN/E5AN
1. Insert the E5AN/E5EN into the square mounting hole in the panel
(thickness: 1 to 8 mm). Attach the Mounting Brackets provided with
the product to the mounting grooves on the top and bottom
surfaces of the rear case.
2. Use a ratchet to alternately tighten the screws on the top and
bottom Mounting Brackets little by little to maintain balance, until
the ratchet turns freely.
Mounting the Terminal Cover
E5AN/E5EN
Slightly bend the E53-COV16 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
Removing the Temperature Controller from the
Case
The Temperature Controller can be removed from the case to perform
maintenance without removing the terminal leads. This is possible
for only the E5CN, E5AN, and E5EN, and not for the E5CN-U.
Check the specifications of the case and Temperature Controller
before removing the Temperature Controller from the case.
E5AN/E5EN
1. Insert a flat-blade screwdriver into the two tool insertion holes (one
on the top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel
and rear case (two on the top and two on the bottom), and use it to
pry and pull out the front panel slightly. Then, pull out on the front
panel gripping both sides. Be sure not to impose excessive force
on the panel.
3. When inserting the body of the Temperature Controller into the
case, make sure the PCBs are parallel to each other, make sure
that the sealing rubber is in place, and press the E5AN/E5EN
toward the rear case until it snaps into position. While pressing the
E5AN/E5EN into place, press down on the hooks on the top and
bottom surfaces of the rear case so that the hooks securely lock in
place. Make sure that electronic components do not come into
contact with the case.
Precautions when Wiring
Separate input leads and power lines in order to prevent external
noise.
Use wires with a gage of AWG24 (cross-sectional area:
0.205 mm2) to AWG14 (cross-sectional area: 2.081 mm2) twisted-
pair cable (stripping length: 5 to 6 mm).
Use crimp terminals when wiring the terminals.
Tighten the terminal screws to a torque of 0.74 to 0.90 N·m,
however the terminal screws on the E5CN-U must be tightened to
a torque of 0.5 N·m.
Use the following types of crimp terminals for M3.5 screws.
Do not remove the terminal block. Doing so will result in
malfunction or failure.
Mounting Bracket
(Accessory)
Mounting Bracket
(Accessory)
Panel
Panel
Waterproof
packing
(Accessory)
Waterproof
packing
(Accessory)
E53-COV16
Terminal Cover
(Accessory)
E5EN
E5AN
E53-COV16
Terminal Cover
(Accessory)
Slightly bend the
E53-COV16
Terminal Cover in
the direction shown
by the arrows to
attach it to the
terminal block.
E53-COV16
Terminal Cover
(Accessory)
(1)
(1)
(2)
(3)
(1)
(1)
(2)
(3)
Tool insertion
hole Tool insertion
hole
E5AN E5EN
7.2 mm max.
7.2 mm max.
Advanced Digital Temperature Controller E5@N/E5@N-H 25
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
In the interest of product improvement, specifications are subject to change without notice.Cat. No. H05E-EN-01A
OMRON EUROPE B.V.
Wegalaan 67-69,
NL-2132 JD, Hoofddorp,
The Netherlands
Phone: +31 23 568 13 00
Fax: +31 23 568 13 88
www.industrial.omron.eu
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
05/2008