Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (19.10.05) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description Ordering Key
Type: Dupline®
Housing
Receiver
No. of channels
Output type
Remote Relay Output
Type G 8830 1143
• Small sized single relay output
• Load: 13 A/250 VAC
• Withstands 130A inrush current
• Powered via Dupline®
• Address coding by GAP 1605
The Dupline®decentral recei-
ver has a build-in SPST relay
for control of a load of up to
13 A/250 VAC. The module is
especially designed for the
use in building automation
applications where it allows a
Type Selection
Ordering no.
1 channel
13 A/250 VAC
G 8830 1143
flexible installation concept
featuring a separate power
and signal (control) bus. The
compact size of the module
makes it possible to fit it in a
junction box or directly behind
a power outlet.
Output Specifications
Output 1 SPST relay
Contact ratings (AgSnO2) µ (micro gap)
Resistive load AC 1 13 A/250 VAC
Minimum load (recommended) 100 mA/12 V
Lifetime see table to the right
Operating frequency 60 operations/minute
Response time 1 pulse train
G 8830 1143
Load Typical number
of operations
250 V, 12 A, cos ϕ =1 1.0 x 105
250 V, 8 A, cos ϕ =1 3.5 x 105
250 V, 4 A, cos ϕ =1 5.0 x 105
250 V, 3 A, cos ϕ =1 7.5 x 105
230 V, 550 W
filament lamps
Iin 40 Apeak
Ioff = 2.5 A 2.0 x 105
230 V, 1000 W
filament lamps
Iin 71.5 Apeak
Ioff = 4.5 A 7.0 x 104
230 V, 900 W
fluorescent tubes
(25 x 36 W)
parallel compensated,
30 µF 1.0 x 104
230 V, compressor
Iin 21 Apeak
Ioff =3.5 A
cos ϕ = 0.5 1.7 x 105
250 V, 8 A, cos ϕ = 0.3 1.0 x 105
Relay data VAC
Supply Max. current (A)
250 VDC 350 mA
100 VDC 500 mA
50 VDC 1,1 Amp
24 VDC 13 Amp
Relay data VDC
resistive load
Max. DC load breaking capacity
300
200
100
50
40
30
20
10
0,1 0,2 0,5 1 2 5 10 20
DC current (A)
DC voltage (Vdc)
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (19.10.05)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
S
Out 1
Orange Brown
White Black
Wiring Diagrams
G 8830 1143
Insulation Voltage
Live parts - Dupline®4 kVAC rms (6 mm)
Enclosure - Live parts 2 kVAC rms (3 mm)
Enclosure - Dupline®2 kVAC rms (3 mm)
Supplied by Dupline®
Normal consumption 1,1 mA
Charge consumption 3,1 mA (for max 1 s after
relay state change)
Power-on delay Typ. 2 s
Power-off delay 1 s
Power dissipation at max. load 0.7 W
General Specifications
Fail-safe mode In case of interruption of the
Dupline®connection, the
channel will be forced into a
specific optional status as
either active high or active
low.
Environment
Pollution degree 3 (IEC 60664)
Operation temperature -20° to +50°C (-4° to 122°F)
Storage temperature -5 to +85°C (-58° to 185°F)
Humidity (non-condensing) 20 to 80%
Housing
Material Noryl GFN 1, black
Dimensions (h x w x d) 26 x 39 x 17 mm
Mode of Operation
The output address and fail-
polarity may be coded by
means of the code program-
mer GAP 1605, with GAP-
THP-CAB cable.
Upon loss of Dupline®carrier
the output goes to the prede-
fined fail-polarity.
Supply Specifications
Wire Connections
Bus: White = Dupline®signal, D+
Black = Dupline®negative, D-
Output: Brown = Relay contact set
Orange = Relay contact set
Bus wires: 2 x 0,75 mm2,
250 V isolation, single core, 150 mm
Output wires: 2 x 1,5 mm2,
250 V isolation, single core, 150 mm
39
26
17
Dimensions
D+ D-
Programming cable
to GAP 1605 GAP-TPH-CAB
Accessories