Edison®
JDL
Class J 600 Volt, 70 to 600A
Dual-Element, Time-Delay Fuses
Form No. JDL 70-600
Page 1 of 2
Data Sheet #1304
07-10-07
BU-SB07255
Catalog Symbol: JDL
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Volts: 600Vac (or less)
Amps: 70 to 600A
IR: 200kA RMS Sym
300kA RMS Sym. (self certified)
Agency Information: CE, UL. Listed – Class J, Guide
JDDZ, File E162363, CSA Certified, HRCI-J Class J per CSA
C22.2 No. 248.8, Class 1422-02, File 53787
Features
True dual-element fuses with a minimum 10 second
time-delay at 500% overload.
Long time-delay minimizes needless fuse openings due
to temporary overloads and transient surges.
Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other
overload protective devices fail.
High interrupting rating to safely interrupt overcurrents
up to 300kA (self certified).
High degree of current-limitation due to the fast
speed-of-response to short-circuits.
Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
Reduces let-through thermal and magnetic forces in
order to protect low withstand rated components.
Proper sizing provides “No Damage” Type “2”
coordinated protection for NEMA and IEC motor control
in accordance with IEC Standard 947-4-1.
Dual-element fuses have lower resistance than ordinary
fuses, hence they run cooler.
Dimensions (inches)
Lower watts loss reduces power consumption.
Unique dimensions assure that another class of fuse
with a lesser voltage rating, interrupting rating or
current-limiting ability cannot be substituted.
Space-saving package for equipment down sizing.
Catalog Numbers (amps)
JDL70 JDL125 JDL250 JDL500
JDL80 JDL150 JDL300 JDL600
JDL90 JDL175 JDL350
JDL100 JDL200 JDL400
JDL110 JDL225 JDL450
Carton Quantity and Weight
Carton Weight per Carton
Amps Quantity lbs kg
70–100 5 1.69 0.77
110–200 5 4.21 1.91
225–400 1 1.67 0.76
450–600 1 2.80 1.27
Edison®
JDL
Class J 600 Volt, 70 to 600A
Dual-Element, Time-Delay Fuses
Form No. JDL 70-600
Page 2 of 2
Data Sheet #1304
07-10-07
BU-SB07255
Current Limitation Curves Time-Current Characteristic Curves– Average
Melt
The only controlled copy of this document is the electronic read-only version maintained by Cooper Bussmann. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, with-
out notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Class J Fuse Blocks (600V) Catalog Data
Box Lug w/ Maximum
Amps Poles Retaining Clip Wire Size
70–100 3 J60100-3CR 1/0 CU/AL
101–200 1 J60200-1CR 250MCM CU/AL
201–400 1 J60400-1CR 500MCM CU/AL
401–600 1 J60600-1CR (2) 500MCM CU/AL