BEHLMAN
INVERTER SPECIFICATIONS
Sine Wave Output:
INV1200-48, INV1200-125, INV1200-250,
INV1200i-48, INV1200i-125, INV1200i-250
Modified Sine Wave Output:
INV1210-48, INV1210-125
INV1210i-48, INV1210i-125
INPUTS DC - 48 VDC +/- 20%, 125 VDC +/- 20% or 250 VDC +/- 20%;
Maximum DC burden (full load): 40 amps DC @ 38 VDC, 15 amps DC @ 100 VDC, 7.5amps DC @ 200 VDC.
OUTPUT
Power: 1200 VA
Voltage: 120 VAC +/- 5%, 60 Hz, Isolated and floating
Option i: 230 VAC =/- 5%, 50 Hz, Isolated and Floating. Requires 2nd 3.5"H chassis.
Crest Factor: 3 : 1
Regulation: +/- 2%
Waveform: INV1200: Sine wave output. INV1210: Modified Sine Wave output
Distortion: Less than 3% THD typical, INV1200.
Power Factor: 100% of rated output into any power factor load.
Efficiency: 80 % typical
PROTECTION CIRCUITS
Input: Circuit breaker, 48VDC & 125VDC. Fuse for 250VDC.
Short Circuit Protection: Short circuit overload electronically latches output to protect load.
Thermal Protection: Internal temperature sensor prevents heat damage.
MECHANICAL SPECIFICATIONS
Dimensions: High strength Rack Mount chassis, 3.5"H x 17"W x 17"D.
Weight: 25 lbs.. Option i adds 15 lbs.
Input Connections: Barrier type terminals with # 8 screws
Output Connections: Two NEMA 5-15 receptacles. Option - TB: Barrier type terminals
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature: 0 to +55 EC.
Humidity: Up to 95% non-condensing
SWC: Designed to meet IEEE C37.90.1
Fast Transient: Designed to meet IEEE C37.90.1
EMI: Designed for immunity to conducted & radiated EMI.
RFI: Designed to meet IEEE C37.90.2-1997
Seismic Designed to meet IEEE 693-1997 Annex L
OPTIONS
D1 - AC INPUT WITH, INDICATORS AND ALARMS
AC Mains Input of 120VAC, 60 Hz. Includes ATransfer Circuit@ to switch, in 2 msec typical, from DC input
to AC input upon loss of DC. Includes AC fuse; (3) indicators for AC IN, DC IN, Inverter ON; (3) form AC@
contacts for the following: NO DC IN, NO AC IN, Inverter Fail.
A1: AC Mains is primary input with ATransfer@ to DC input upon loss of AC. Alarms and indicators same as D1.
TB: Barrier type terminals, # 6 screws.
BEHLMAN
4532 Telephone Road Suite 103 Ventura, CA 93003 80 Cabot Court Hauppauge, NY 11788
(805)642-0660 (800)456-2006 Fax(805)642-0790 E-mail: sales@behlman.com (631)435-0410 (800)874-6727 Fax(631)951-4341
Web-site: www.behlman.com INV1200SS_June 13, 2001