DATASHEETAC Line ReactorsRWK 212
3-phase Line Reactor for Motor Drive & Power Quality Applications
Provision of 4% impedanceReduction of mains harmonicsReduction of commutation notchesProtection of motor drive electronicsLimitation of inrush currentsImprovement of true power factorPerformance indicators
1
Technical specifications
Maximum continuous operating voltage 3 x 500/288 VACDesign corresponding to EN 61558-2-20 (VDE 0570-2-20), UL 508C, CSA C22.2NO.14Operating frequency DC to 60 HzImpedance 4% @ 400 VAC, 50 Hz & rated currentTypical harmonics reduction See table on next pageHigh potential test voltage P –> E 3000 VAC for 3 secP –> P 3000 VAC for 3 secInsulation class T40/N (200°C) for ≤400 A typesT40/F (155°C) for ≥500 A typesT40/H (180°C) for 1500 A typesProtection category IP 00 (KL types according to VBG 4)Rated currents 4 to 1500 A @ 40°COverload capability 2 x rated current at switch on for 30 seconds1.5 x rated current for 1 minute, once per hourFlammability corresponding to UL 94 V-2 or betterTemperature range (operation and storage) -25°C to +100°C (25/100/21)MTBF @ 40°C/400 V (Mil-HB-217F) >500,000 hoursApprovals
UL 508C up to 400 A. For use with AC or DC drives(power conversion equipment) only
Features and benefits
Ensure reliability, performance and a long service lifeof electrical consumersReduction of mains harmonics and commutationnotchesHelp to meet international power quality standardssuch as IEEE-519 or EN 61000-3-2Protection of motor drive electronics and dc linkcapacitors against mains transientsReduction of inrush and peak currentsReduction of conducted LF emissionImprovement of conducted LF immunityPrevention from nuisance tripping caused by powerline voltage spikesImprovement of true power factor
Typical applications
Motor drives and various adjustable speed drivesystems, such as:ElevatorsRobotsMachineryProcess automation equipment
Typical electrical schematic
2ReactorsSchaffner Group Datasheets 13 Feb 2019Reactor selection table
Reactor Rated current Typical drive Nominal Typical Input/Output Weight Earthing bolt
@ 40°C power rating* inductance power loss** connections Total
[A] [kW] [mH] [W] [kg]
RWK 212-4-KL 41.57.323KL2.1AMP 6,3 x 0,8RWK 212-7-KL 734.236KL2.5M4RWK 212-11-KL 1142.637KL2.5M4RWK 212-16-KL 167.51.859KL3.9M5RWK 212-21-KL 21111.466KL5.4M5RWK 212-29-KL 2915169KL5.4M5RWK 212-35-KL 3518.50.8470KL5.9M5RWK 212-46-KL 46220.6499KL11M8RWK 212-60-KL 60300.49138KL15M8RWK 212-75-KL 75370.39133KL15M8RWK 212-95-KL 95450.3166KL22M10RWK 212-124-KS 124550.23172KS25M10RWK 212-156-KS 156750.19249KS25M10RWK 212-182-KS 182900.16245KS32M10RWK 212-230-KS 230110/1320.13301KS35M10RWK 212-280-KS 2801600.1335KS41M10RWK 212-330-KS 3301600.09386KS56M10RWK 212-400-S 4002000.073692S57M10RWK 212-500-S 5002500.058761S67M10RWK 212-600-S 6003150.049825S76M10RWK 212-680-S 6803550.043876S80M10RWK 212-790-S 7904000.037956S90M10RWK 212-910-S 9104500.0321022S107M10RWK 212-1100-S 11006300.0261036S135M10RWK 212-1310-S 13107250.0231050S100M10RWK 212-1500-S 15008300.0201000S225M10Customized line reactors with different electrical and mechanical specifications are available on request.*Calculated at rated current, 400 VAC and cos phi=0.8. The exact value depends upon the efficiency of the drive, the motor and the entire application.**Power loss at 25°C/50 Hz, considering a typical harmonic spectrum of a motor drive with B6U rectifier bridge.
Harmonics reduction
Line reactors are a cost-effective way for the limitation of mains harmonics. The harmonics reduction capability is related to the reactor impedance. A higherimpedance translates directly into lower harmonic currents, but of course also into a larger component with a higher voltage drop − and vice versa.4% impedance reactors like RWK 212 provide an excellent cost/benefit ratio and are particularly beneficiary in the most diverse motor drive applications.The table below shows various reactor impedance values and their calculated effect in terms of harmonics reduction.
Harmonic number/Input impedance (uk) vs. remaining harmonics [%]
0.5% 1% 2% 3% 4% 5% 6% 7% 8% 9% 10%
5th 80604640343230282624237th 603722161312111098.37.511th 181297.36.35.85.254.34.2413th 107.55.84.94.23.93.63.33.1532.817th 7.35.23.632.42.22.10.90.70.50.419th 64.22.82.220.80.70.40.30.250.2%THID 102.572.252.344.1337.3134.9632.6530.3528.0425.9224.68Reading example: a 4% impedance reactor typically reduces the THID to ~37% of the fundamental.
3ReactorsSchaffner Group Datasheets 13 Feb 2019Mechanical data
4 to 46 A types60 to 95 A types124 to 330 A types400 to 1500 A types
4ReactorsSchaffner Group Datasheets 13 Feb 2019Dimensions
A B C D E F G
4 A 100max. 70max. 11556434.8 x 92.5 mm²7 and 11 A 125max. 80max. 130100555 x 82.5 mm²16 A 155max. 80max. 15513056.58 x 124 mm²21 A 155max. 95max. 15513070.58 x 124 mm²29 A 155max. 95max. 15513071.58 x 124 mm²35 A 155max. 105max. 170130708 x 1210 mm²46 A 190max. 120max. 19517077.58 x 1210 mm²60 A 210max. 155max. 240175978 x 1216 mm²75 A 210max. 160max. 249175978 x 1235 mm²95 A 230max. 185max. 2751801228 x 1235 mm²124 and 156 A 240max. 210max. 21019012911 x 15Ø10182 A 265max. 210max. 23021511411 x 15Ø10230 A 30021027024013111 x 15Ø12280 A 30021827024013911 x 15Ø12330 A 30025527024016611 x 15Ø12400 A 42020539037013311 x 15Ø11500 A 42021539037014011 x 15Ø14600 A 42022539037014911 x 15Ø14680 A 42022539037015011 x 15Ø14790 A 42024039037016211 x 15Ø18910 A 42025539037017711 x 152 x Ø111100 A 42029039037020011 x 152 x Ø111310 A 42025549037017211 x 152 x Ø141500 A 55140061349026613 x 184 x Ø13All dimensions in mm; 1 inch = 25.4 mmTolerances according: ISO 2768-m/EN 22768-mPlease visit www.schaffner.com to find more details on filter connectors.
5ReactorsSchaffner Group Datasheets 13 Feb 2019
TofindyourlocalpartnerwithinSchaffner‘sglobal network: www.schaffner.com© 2018 Schaffner GroupThecontentofthisdocumenthasbeencarefullycheckedandunderstood.However,neitherSchaffnernoritssubsidiariesassumeanyliabilitywhatsoeverforanyerrorsorinaccuraciesofthisdocumentandtheconsequencesthereof.Publishedspecifica-tionsaresubjecttochangewithoutnotice.Productsuitabilityforanyareaofapplicationmustultimatelybedeterminedbythecustomer.Inallcases,productsmustneverbeoperatedoutsidetheirpublishedspecifications.Schaffnerdoesnotguaranteetheavailabilityofallpublishedproducts.ThisdisclaimershallbegovernedbysubstantiveSwisslawandresultingdisputesshallbesettledbythecourtsattheplaceofbusinessofSchaffnerHoldingAG.Latestpublicationsandacompletedisclaimercanbedownloa-dedfromtheSchaffnerwebsite.Alltrademarks recognized.
Headquarters, global
innovation and development
SwitzerlandSchaffner Group
Nordstrasse 114542 LuterbachT +41 32 681 66 26info@schaffner.com
Sales and application centers
ChinaSchaffner EMC Ltd. Shanghai
T20-3 C, No 565 Chuangye Road,Pudong district201201 ShanghaiT +86 21 3813 9500cschina@schaffner.comwww.schaffner.com.cnFinlandSchaffner Oy
Sauvonrinne 19 H08500 LohjaT +358 50 468 7284finlandsales@schaffner.comFranceSchaffner EMC S.A.S.
16-20 Rue Louis Rameau95875 BezonsT +33 1 34 34 30 60F +33 1 39 47 02 28francesales@schaffner.comGermanySchaffner Deutschland GmbH
Schoemperlenstrasse 12B76185 KarlsruheT +49 721 56910F +49 721 569110germanysales@schaffner.comIndiaSchaffner India Pvt. Ltd
REGUS WORLD TRADE CENTREWTC, 22nd Floor Unit No 2238, BrigadeGateway Campus, 26/1, Dr. Rajkumar RoadMalleshwaram (W)560055 BangaloreT +91 80 67935355indiasales@schaffner.comItalySchaffner EMC S.r.l.
Via Ticino, 3020900 Monza (MB)T +39 039 21 41 070italysales@schaffner.comJapanSchaffner EMC K.K.
1-32-12, Kamiuma, Setagaya-ku7F Mitsui-seimei Sangenjaya Bldg.154-0011 TokyoT +81 3 5712 3650F +81 3 5712 3651japansales@schaffner.comwww.schaffner.jpSingaporeSchaffner EMC Pte Ltd.
#05-09, Kg Ubi Ind. Estate408705 SingaporeT +65 6377 3283F +65 6377 3281singaporesales@schaffner.comSpainSchaffner EMC España
Calle Caléndula 93, Miniparc III, Edificio EEl Soto de Moraleja, Alcobendas28109 MadridT +34 917 912 900F +34 917 912 901spainsales@schaffner.comSwedenSchaffner EMC AB
Tegeluddsvägen 76, 2tr115 28 StockholmT +46 8 5050 2425swedensales@schaffner.comwww.schaffner.comSwitzerlandSchaffner EMV AG
Nordstrasse 114542 LuterbachT +41 32 681 66 26switzerlandsales@schaffner.comTaiwan R.O.C.Schaffner EMV Ltd.
20 Floor-2, No 97, Section 1, XinTai 5th Road22175 XiZhi District New Taipei City 22175T +886 2 2697 5500F +886 2 2697 5533taiwansales@schaffner.comwww.schaffner.com.twThailandSchaffner EMC Co. Ltd.
Northern Region Industrial Estate67 Moo 4 Tambon Ban KlangAmphur Muangg P.O. Box 1451000 LamphunT +66 53 58 11 04F +66 53 58 10 19thailandsales@schaffner.comUnited KingdomSchaffner Ltd.
5 Ashville Way, Molly Millars LaneWokinghamRG41 2PL BerkshireT +44 118 9770070F +44 118 9792969uksales@schaffner.comUSASchaffner EMC Inc.
52 Mayfield AvenueEdison, New JerseyT +1 732 225 9533F +1 732 225 4789usasales@schaffner.comwww.schaffnerusa.comSchaffner North America
6722 Thirlane Road24019 Roanoke, VirginiaT +1 276 228 7943F +1 276 228 7953Schaffner North America
823 Fairview Road24382 Wytheville, VirginiaT +1 276 228 7943F +1 276 228 7258