9
SYSMAC Remote Master Modules C200H-RM
01
Wired and Fiber-optic Remote I/O
Systems Match Your Distance Needs
1Wired remote I/O systems offer up to
200 m maximum distance using
shielded twisted pair wire, Belden #9271
or equivalent
1Fiber-optic remote I/O systems prevent
electrical noise from fouling long-
distance communication signals
1Transmission distance with fiber-optic
cables depends on core material: 20 m
for all plastic; 200 m for plastic clad
1Master modules connect to slave racks
or remote I/O relay or transistor blocks
Ordering Information
3WIRED REMOTE I/O SYSTEM
Classification Description Specification Part number
Remote master For CS1, C200H, C200H Alpha systems Useupto2mastersperCPU C200H-RM201
Transmission line Shielded twisted pair cable Belden #9271 or equivalent Commercially available
3FIBER-OPTIC REMOTE I/O SYSTEM
Classification Description Specification Part number
Remote master For CS1, C200H, C200H Alpha systems Useupto2mastersperCPU C200H-RM001-PV1
Transmission media APF (all plastic) fiber-optic cable
(user must assemble connectors) 20 m (65 ft), without connectors B500-PF212
Connectors, brown (includes 2) For cables 0 to 10 m length 3G5A2-CO001
Connectors, black (includes 2) For cables 8 to 20 m length 3G5A2-CO002
HPCF (plastic clad) fiber-optic cable,
i
d
/
t
d
50 m (164 ft) FCS-HCR-LB-501
(
)
,
indoor/outdoor use
(
u
s
e
r
m
u
s
t
a
s
s
e
m
b
l
e
c
o
n
n
e
c
t
o
r
s
)
100 m (328 ft) FCS-HCR-LB-102
(
user mus
t
assem
b
l
e connec
t
ors
)
500 m (1640 ft) FCS-HCR-LB-502
1 km (3280 ft) FCS-HCR-LB-103
Zipcord style, orange, without connectors 50 m (164 ft) FCS-HCR-CO-501
Connectors for SYSMAC BUS Order two, one for each end S3200-COCH82
Termination kit for HPCF cable -- -- -- FCS-CAK6230-US
3REMOTE SLAVE RACKS
For part numbers and configuration information, refer to the CS1 or C200H Alpha Programmable Controller Catalogs, or
C-Series Wired
Remote I/O Manual
(W120) or
C-Series Fiber-optic Remote IO Manual
(W136).
C200H-RM
01 C200H-RM
01
2
Specifications
3COMMUNICATIONS SPECIFICATIONS
Communications method Half-duplex
Coding method Manchester coding method
Connection method RS-485
Communications baud rate 187.5 kbps
Communications cable C200H-RM201: 2-conductor cable: Belden #9271 or VCTF (JIS L3306)
C200H-RM001: Fiber-optic cable: all plastic or hard plastic clad fiber media
Communications
d
i
t
Wired Belden #9271 or VCTF cable: 200 m (656 ft)
distance Fiber-optic All plastic fiber (APF): 20 m (65.6 ft)
Hard plastic fiber (HPCF): 200 m (656 ft)
Max. number of connecting nodes 32 (512 words max.)
Error control checks Manchester code check, frame length check, and parity check
3MODULE SPECIFICATIONS
Current consumption C200H-RM201 wired master: 0.25 A
C200H-RM001 fiber-optic master: 0.2 A
Number of I/O points 512 max.
Number of occupied words 512 max.
Omron PLC model CS1, C200HX (-ZE), C200HG (-ZE), C200HE (-ZE), C200HS
Max. number of Slaves per Master 32
Approved standards UL 508 (E95399), CSA C22.2 No. 142 (LR51460)
Note: For detailed specifications on wired or fiber-optic SYSMAC BUS systems, refer to the following manuals:
C-Series Wired Remote I/O
W120
C-Series Fiber-optic Remote I/O
W136
Dimensions
Unit: mm (inch)
Note: Refer to the
C200HX, C200HG, C200HE
,
C200HS
,or
CS1 Operation Manual
for
details on the dimensions when the Master Module is installed in the PLC Backplane.
100 (3.94)
130
(5.12)
35 (1.38)
RM201
C200H-RM201C200H-RM001-PV1
C200H-RM
01 C200H-RM
01
Cat. No. GC RIO-1 04/00 Specifications subject to change without notice. Printed in U.S.A.
OMRON ELECTRONICS, INC.
OneEastCommerceDrive
Schaumburg, IL 60173
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
1-800-55-OMRON
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V
8
416-286-6465
9
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
3G5A2-CO001 FCS-HCR-CO-501 FCS-HCR-LB-103