22/10/2012 www.crouzet.com 22.5 mm DIN rail mounting TUR1 Part number 88865105 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator Option of connecting an external power supply to the control input 3-wire sensor control option Part numbers Functions Timing Output Nominal rating Connections Supply voltage 88 865 105 TUR1 A - At - B - C - H - Ht - Di - D - Ac - Bw 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 115 TAR1 A - At 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 125 TBR1 B 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 135 TCR1 C 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 145 THR1 H - Ht 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 155 TLR1 Li - L 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 175 TQR1 Q 0,1s100h 1 changeover relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 100 TUR4 A - At - B - C - H - Ht - Di - D - Ac - Bw 0,1s100h 1 changeover relay 8A Screw terminals 12 V AC / DC 88 865 103 TUR3 A - At - B - C - H - Ht - Di - D - Ac - Bw 0,1s100h 1 changeover relay 8A Screw terminals 12 240 V AC / DC 88 865 503 TURc3 A - At - B - C - H - Ht - Di - D - Ac - Bw 0,1s100h 1 changeover relay 8A Spring terminals 12 240 V AC / DC 88 865 185 TXR1 0,1s100h 1 change over relay 8A Screw terminals 24 V DC / 24 240 V AC 88 865 305 TU2R1 A - At - B - C - H - Ht - Di - D - Ac -Bw - 2 timed changeover relays 8A Screw terminals 24 V DC / 24 240 V AC 88 865 215 TA2R1 A - At 0,1s100h 2 changeover relays 8A Screw terminals 24 V DC / 24 240 V AC 88 865 265 TK2R1 K 0,6s160 s 2 change over relays 8A Screw terminals 24 V DC / 24 240 V AC 88 865 300 TU2R4 A - At - B - C - H - Ht - Di - D - Ac - Bw 0,1s100h 2 timed relays changeover relays 8A Screw terminals 12 V AC / DC 88 865 176 TQR6 0,1s100h 1 change over relays 8A Screw terminals 230 V440 V AC 88 865 303 TU2R3 A, B, C, H, Di, Ac, BW + (At, Ht, D) 0,1s100h 2 timed changeover relays 8A Screw terminals 12 230 V AC/DC 88 865 385 TX2R1 Ad - Ah - N - O - P - Pt - TL - Tt - W 0,1s100h 2 timed changeover relays 8A Screw terminals 24 V DC / 24 240 V AC Type Ad - Ah - N - O - P- Pt - TL - Tt - W Q : Star / Delta Specifications Timing Timing ranges (7 ranges) Repetition accuracy with constant parameters Drift Temperature Drift Voltage Display accuracy according to IEC/EN 61812-1 Minimum pulse duration typically (relay version) Minimum pulse duration typically (solid state version) Minimum pulse duration typically (relay version under load) Maximum reset time by de-energisation typically (relay version) Maximum reset time by de-energisation typically (solid state version) Immunity from micro power cuts : typical Supply Multi-voltage power supply Frequency (Hz) Operating range Operator factor Max. absorbed power 1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h TK2R1 : 0.6s - 2.5s - 20s - 160 s 0.5 % (IEC/EN 1812-1) 0,05 % / C 0.2 % / V 10 % / 25 C 30 ms 50 ms 100 ms 100 ms 350 ms > 10 ms Depending on version 50 / 60 85 to 110 % Un (85 to 120 % Un for 12V AC/DC) 100 % 0,6 W 24 V AC/DC 1,5 W 230 V AC 32 VA 230 V AC Output specification 1 or 2 changeover relays, AgNi (cadmium-free) Rated power Maximum breaking current Minimum breaking current Voltage breaking capacity Electrical life (operations) 2000 VA/80 W 2000 VA/80 W 8 A AC 8A DC 10 mA / 5 V DC 250 V AC/ DC 10 5 operations 8 A 250 V resistive Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 22/10/2012 Mechanical life (operations) Breakdown voltage acc. to IEC/EN 61812-1 Impulse voltage acc. to IEC/EN 60664-1, IEC/EN 61812-1 www.crouzet.com 5x106 2.5 kV /1 min / 1 mA / 50 Hz 5 kV, wave 1.2 / 50 s Solid state output Rated power Derating Maximum admissible current Minimum breaking current Leakage current Voltage breaking capacity Maximum voltage drop at terminals Electrical life (operations) Mechanical life (operations) Breakdown voltage acc. to IEC/EN 60664-1, IEC 60255-5 Input type 0,7 A AC/DC 20 C (0,5 A UL) 5 mA / C 20 A 10 ms 10 mA < 5 mA 250 V AC/ DC 3 wire 4V - 2 wire 8V 108 108 2.5 kV to 1 mA / 1 min Volt-free contact 3-wire PNP output control option residual voltage : 0.4V whatever the timer power supply General characteristics Conformity to standards IEC/EN 61812-1 IEC/EN 61000-6-1 IEC/EN 61000-6-2 IEC/EN 61000-6-3 IEC/EN 61000-6-4 CE, UL, cUL, CSA, GL -20 +60 -30 +60 Certifications Temperature limits use (C) Temperature limits stored (C) Installation category Voltage surge category (acc. to IEC/EN 60664-1) ) Creepage distance and clearance acc. to IEC/EN 60664-1 4 kV / 3 Protection (IEC/EN 60529) IP 20 IP 40 Degree of protection acc. to IEC/EN 60529 Front face IP 50 (except Tk2R1) Vibration resistance f = 10 55 Hz acc. to IEC/EN 60068-2-6 A = 0,35 mm Relative humidity no condensation acc. to IEC/EN 6006893 % sans condensation 2-30 Electromagnetic compatibility - Immunity to electrostatic Level III (Air 8 KV / Contact 6 KV) discharges acc to IEC/EN 61000-4-2 Immunity to radiated, radio-frequency, electromagnetic Level III 10V/m (80 M Hz to 1 G Hz) field acc. CEI/EN 61000-4-3 Immunity to rapid transient bursts acc. to IEC/EN 61000-4Level III (direct 2kV / Capacitive coupling clamp 1 KV) 4 Immunity to shock waves on power supply acc. to IEC/EN Level III (2 KV / common mode 2 KV/residual current mode 1KV) 61000-4-5 Immunity to radio frequency in common mode acc. to Level III (10V rms : 0.15 M Hz to 80 M Hz) IEC/EN 61000-4-6 Immunity to voltage dips and breaks acc. to IEC/EN 61000- 30 %/10 ms 4-11 60 %/100 ms > 95 %/5 s Mains-borne and radiated emissions acc. to EN 55022 Class B (CISPR22), EN55011 (CISPR11) Fixing : Symmetrical DIN rail 35 mm Connection capacity - without ferrule 2 x 2,5 mm2 Connection capacity - with ferrule 2 x 1,5 mm2 Spring terminals, 2 terminals per connection point flexible wire Spring terminals, 2 terminals per connection point - rigid wire Housing material Weight : casing 17,5 mm Weight : casing 22,5 mm Weight : plug-in casing 1,5 mm2 2,5 mm2 Self-extinguishing 60 g 90 g 80 g Display State displayed by 2 LEDs - Flashing green when on - Relay LED yellow during timing Green LED operation indicator Pulsing : - Timer on, no timing in process Permanently lit : - Relay waiting, no timing in process Dimensions (mm) Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected 22/10/2012 Curves Function A - 1 relay output Function A Delay on energisation Curves Function Ac - 1 relay output Function Ac Timing after closing and opening of control contact Curves Function At - 1 relay output Function At Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com 22/10/2012 Timing on energisation with memory Curves Fonction B - 1 relay output Function B Timing on impulse one shot Curves Function Bw - 1 relay output Function Bw Pulse output (adjustable) Curves Function C - 1 relay output Function C Timing after impulse Curves Function D - 1 relay output Function D Flip-flop Pause start Curves Function Di - 1 relay output Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com 22/10/2012 Function Di Flip-flop Pulse start Curves Function H - 1 relay output Function H Timing on energisation Curves Function Ht - 1 relay output Function Ht Delay on energisation with memory Connections 1 changeover relay output Functions A - At - B - C - H - Ht - Di - D - Ac - Bw Ad - Ah - N - O - P - Pt - TL - Tt - W Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected www.crouzet.com