22.5 mm DIN rail mounting TUR1 Part number 88865105
Multi
-function or mono-function
Multi
-range
Multi
-voltage
Screw or spring terminals
LED status indicator
Option of connecting an external power supply to the control input
3-wire sensor control option
Part numbers
Specifications
Type
Functions
Timing
Output
Connections
Supply voltage
88 865 105
TUR1
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 115
TAR1
A - At
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 125
TBR1
B
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 135
TCR1
C
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 145
THR1
H
-
Ht
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 155
TLR1
Li
- L
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 175
TQR1
Q
0,1s→100h
1 changeover relay
Screw terminals
24VDC/24→240VAC
88 865 100
TUR4
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
1 changeover relay
Screw terminals
12 V AC / DC
88 865 103
TUR3
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
1 changeover relay
Screw terminals
12→240VAC/DC
88 865 503
TURc3
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
1 changeover relay
Spring terminals
12→240VAC/DC
88 865 185
TXR1
Ad - Ah -
N
-
O
-
P
-
Pt
-
TL
-
Tt
-
W
0,1s→100h
1 change over relay
Screw terminals
24VDC/24→240VAC
88 865 305
TU2R1
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac -Bw
-
2 timed changeover relays
Screw terminals
24VDC/24→240VAC
88 865 215
TA2R1
A - At
0,1s→100h
2 changeover relays
Screw terminals
24VDC/24→240VAC
88 865 265
TK2R1
K
0,6s→160s
2 change over relays
Screw terminals
24VDC/24→240VAC
88 865 300
TU2R4
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
0,1s→100h
2 timed relays changeover relays
Screw terminals
12 V AC / DC
88 865 176
TQR6
Q : Star / Delta
0,1s→100h
1 change over relays
Screw terminals
230V→440VAC
88 865 303
TU2R3
A, B, C, H, Di, Ac, BW + (At, Ht, D)
0,1s→100h
2 timed changeover relays
Screw terminals
12→230VAC/DC
88 865 385
TX2R1
Ad - Ah -
N
-
O
-
P
-
Pt
-
TL
-
Tt
-
W
0,1s→100h
2 timed changeover relays
Screw terminals
24VDC/24→240VAC
Timing
Timing ranges (7 ranges)
1 s - 10 s -
1 min
-
10 min
- 1 h - 10 h - 100 h
TK2R1 : 0.6s
- 2.5s - 20s - 160 s
Repetition accuracy with constant parameters
±
0.5 % (IEC/EN 1812
-1)
Drift Temperature
±
0,05 % / °C
Drift Voltage
±
0.2 % / V
Display accuracy according to IEC/EN 61812
-1
±
10 % / 25 °C
Minimum pulse duration typically (relay version)
30 ms
Minimum pulse duration typically (solid state version)
50 ms
Minimum pulse duration typically (relay version under
load)
100 ms
Maximum reset time by de
-energisation typically (relay
version)
100 ms
Maximum reset time by de
-energisation typically (solid
state version)
350 ms
Immunity from micro power cuts : typical
> 10 ms
Supply
Multi
-voltage power supply
Depending on version
Frequency (Hz)
50 / 60
Operating range
85 to 110 % Un
(85 to 120 % Un for 12V AC/DC)
Operator factor
100 %
Max. absorbed power
0,6 W 24 V AC/DC
1,5 W 230 V AC
32 VA 230 V AC
Output specification
1 or 2 changeover relays, AgNi (cadmium-free)
2000 VA/80 W
Rated power
2000 VA/80 W
Maximum breaking current
8 A AC 8A DC
Minimum breaking current
10 mA / 5 V DC
Voltage breaking capacity
250 V AC/ DC
Electrical life (operations)
10 5 operations 8 A 250 V resistive
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Mechanical life (operations)
5x106
Breakdown voltage acc. to IEC/EN 61812
-1
2.5 kV /1 min / 1 mA / 50 Hz
Impulse voltage acc. to IEC/EN 60664
-
1, IEC/EN 61812
-1
5 kV, wave 1.2 / 50
μ
s
Solid state output
Rated power
0,7 A AC/DC
20 °C (0,5 A UL)
Derating
5 mA / °C
Maximum admissible current
20A≤10ms
Minimum breaking current
10 mA
Leakage current
< 5 mA
Voltage breaking capacity
250 V AC/ DC
Maximum voltage drop at terminals
3 wire 4V - 2 wire 8V
Electrical life (operations)
108
Mechanical life (operations)
108
Breakdown voltage acc. to
IEC/EN 60664
-
1, IEC 60255
-5
2.5 kV to 1 mA / 1 min
Input type
Volt-free contact
3-wire PNP output control option residual voltage : 0.4V whatever the timer power supply
General characteristics
Conformity to standards
IEC/EN 61812
-1
IEC/EN 61000
-6-1
IEC/EN 61000
-6-2
IEC/EN 61000
-6-3
IEC/EN 61000
-6-4
Certifications
CE, UL, cUL, CSA, GL
Temperature limits use (°C)
-
20→+60
Temperature limits stored (°C)
-
30→+60
Installation category
(acc. to IEC/EN 60664
-1) )
Voltage surge category
Creepage distance and clearance acc. to IEC/EN 60664
-1
4 kV / 3
Protection (IEC/EN 60529)
IP 20
IP 40
Degree of protection acc. to IEC/EN 60529 Front face
(except Tk2R1)
IP 50
Vibration resistance
acc. to IEC/EN 60068
-2-6
f = 10
55 Hz
A = 0,35 mm
Relative humidity
no condensation acc. to IEC/EN 60068
-
2-30
93 % sans condensation
Electromagnetic compatibility
-
Immunity to electrostatic
discharges acc to IEC/EN 61000
-4-2
Level III (Air 8 KV / Contact 6 KV)
Immunity to radiated, radio
-frequency, electromagnetic
field acc. CEI/EN 61000
-4-3
Level III 10V/m (80 M Hz to 1 G Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000
-4-
4
Level III (direct 2kV / Capacitive coupling clamp 1 KV)
Immunity to shock waves on power supply acc. to IEC/EN
61000-4-5
Level III (2 KV / common mode 2 KV/residual current mode 1KV)
Immunity to radio frequency in common mode acc. to
IEC/EN 61000
-4-6
Level III (10V rms : 0.15 M Hz to 80 M Hz)
Immunity to voltage dips and breaks acc. to IEC/EN 61000
-
4-11
30 %/10 ms
60 %/100 ms >
95 %/5 s
Mains
-
borne and radiated emissions acc. to EN 55022
(CISPR22), EN55011 (CISPR11)
Class B
Fixing : Symmetrical DIN rail
35 mm
Connection capacity - without ferrule
2 x 2,5 mm
2
Connection capacity - with ferrule
2 x 1,5 mm
2
Spring terminals, 2 terminals per connection point
-
flexible wire
1,5 mm
2
Spring terminals, 2 terminals per connection point
-
rigid
wire
2,5 mm
2
Housing material
Self-extinguishing
Weight : casing 17,5 mm
60 g
Weight : casing 22,5 mm
90 g
Weight : plug
-in casing
80 g
Display
State displayed by 2 LEDs
- Flashing green when on
-
Relay LED yellow during timing
Green LED operation indicator
Pulsing :
-
Timer on, no timing in process
Permanently lit :
- Relay waiting, no timing in process
Dimensions (mm)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Curves
Function A - 1 relay output
Function A
Delay on energisation
Curves
Function Ac - 1 relay output
Function Ac
Timing after closing and opening of control contact
Curves
Function At - 1 relay output
Function At
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Timing on energisation with memory
Curves
Fonction B - 1 relay output
Function B
Timing on impulse one shot
Curves
Function Bw - 1 relay output
Function Bw
Pulse output (adjustable)
Curves
Function C - 1 relay output
Function C
Timing after impulse
Curves
Function D - 1 relay output
Function D
Flip
-flop
Pause start
Curves
Function Di - 1 relay output
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Function Di
Flip
-flop
Pulse start
Curves
Function H - 1 relay output
Function H
Timing on energisation
Curves
Function Ht - 1 relay output
Function Ht
Delay on energisation with memory
Connections
1 changeover relay output
Functions
A - At -
B
-
C
-
H
-
Ht
-
Di
-
D
- Ac - Bw
Ad - Ah -
N
-
O
-
P
-
Pt
-
TL
-
Tt
-
W
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com