IPN = 100 A
Features
Closed loop (compensated)
current transducer using the Hall
effect
Printed circuit board mounting
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domain
Industrial.
Current Transducer LA 100-TP
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
IPN Primary nominal current rms 100 A
IPM Primary current, measuring range 0 .. ± 150 A
RM Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 12 V @ ± 100 A max 0 50 0 42
@ ± 120 A max 0 22 0 14
with ± 15 V @ ± 100 A max 0 110 20 102
@ ± 150 A max 0 33 20 25
ISN Secondary nominal current rms 50 mA
KN Conversion ratio 1 : 2000
VC Supply voltage (± 5 %) ± 12 .. 15 V
IC Current consumption 10 (@ ± 15 V) + IS mA
X Accuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %) ± 0.45 %
Accuracy - Dynamic performance data
@ ± 12 .. 15 V (± 5 %) ± 0.70 %
εL Linearity error < 0.15 %
Typ Max
IO Offset current @ IP = 0, TA = 25°C ± 0.10 mA
IOM Magnetic offset current 1) @ IP = 0 and specied RM,
after an overload of 3 x IPN ± 0.15 mA
IOT Temperature variation of IO - 25°C .. + 85°C ± 0.05 ± 0.30 mA
- 40°C .. - 25°C ± 0.10 ± 0.50 mA
tra Reaction time to 10 % of IPN step < 500 ns
tr Response time 2) to 90 % of IPN step < 1 µs
di/dt di/dt accurately followed > 200 A/µs
BW Frequency bandwidth (- 1 dB) DC .. 200 kHz
TA Ambient operating temperature - 40 .. + 85 °C
General data
TS Ambient storage temperature - 40 .. + 90 °C
RS Secondary coil resistance @ TA = 70°C 120
 @ TA = 85°C 128
m Mass 24 g
Standards 3) EN 50178
Notes: 1) Result of the coercive eld of the magnetic circuit
2) With a di/dt of 100 A/µs
3) A list of corresponding tests is available.
16045
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 2/3
090616/8
Current Transducer LA 100-TP
Isolation characteristics
Vd Rms voltage for AC isolation test, 50 Hz, 1 min 2.5 kV
Vw Impulse withstand voltage 1.2/50 µs 7.5 kV
Min
dCp Creepage distance 7.5 mm
dCI Clearance distance 7.5 mm
CTI Comparative Tracking Index (group IIIa) 175
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
Over voltage category OV 3
Pollution degree PD2
Non-uniform eld
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
EN 50178 IEC 61010-1
dCp, dCI,
Rated isolation voltage
Nominal voltage
Single isolation
600 V
600 V
Reinforced isolation
300 V
300 V
Vw
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 3/3
090616/8
Connection
Dimensions LA 100-TP (in mm. 1 mm = 0.0394 inch)
Front view
Top view Left view
Mechanical characteristics
General tolerance ± 0.2 mm
Fastening & connection of primary bus bar
6.4 x 1.6 mm
Recommended PCB hole 3.8 mm
Fastening & connection of secondary 3 pins
0.6 x 0.7 mm
Recommended PCB hole 0.9 mm
Remarks
I S is positive when IP ows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100°C.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Secondary terminals
Terminal + : supply voltage + 12 .. 15 V
Terminal - : supply voltage - 12 .. 15 V
Terminal M : measure