Product Data Sheet
A Regal Brand
www.marathonsp.com 1
144X551
Replace “x” with 1, 2, or 3 for number of poles
Power Terminal Block
380 Amps 600 Volts AC/DC
Wire Range
Line: (1) 500 kcmil - #4 AWG
Load: (6) #2 - #14 AWG
Electrical Ratings
380 amps
600V per UL 1059 & CSA 22.2 No.158, Class B & C requirements
Short circuit current ratings (SCCR): See SCCR section below for speci cations.
CU7AL - 75°C connector terminal rating with copper or aluminum wire
Factory & Field Wiring
Agency Compliance
UR - UL Recognized Terminal Block, Evaluated to UL 1059, File No.XCFR2.E62806
CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
CE compliant to IEC 60947-7-1
Material Information
Insulator base:
Phenolic
Flammability rating of insulator base UL94V0
Insulator base temperature rating: -40°C to 150°C (UL RTI)
Connector: aluminum, tin plated
Terminal set screws: aluminum, tin plated
Connector mounting screws: steel, zinc plated
RoHS compliant
www.marathonsp.com 2PDS 0074 REV-D 01/13/17
Termination Speci cations
Aluminum wire range: 500 kcmil - #4 AWG
Wire strip length: 1 5/16in. (33mm)
Terminal screw drive: 3/8 in. (9.5mm) hex
Line Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
500 kcmil 42.4 N·m (375 lbf·in) 1 B, C
400 - 2 42.4 N·m (375 lbf·in) 1 B, C, G, H, I (DLO)
4 42.4 N·m (375 lbf·in) 1 B, C
1 For information on copper stranded wire classes please visit:
http://www.marathonsp.com/ exible-stranded-wire.php
2 Multiple wire rating applies to classes B, C, & I only
Solid copper wire range: #10 - 14
Aluminum wire range: #2 - #8 AWG
Wire strip length (load side): Top Row: 3/4 in. (19mm)
Bottom Row: 1 3/16 in (30mm)
Terminal screw drive: slotted
Load Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
2 AWG 5.6 N·m (50 lbf·in) 1 B, C
4 - 6 5.1 N·m (45 lbf·in) 1 B, C, G, H, I (DLO)
8 4.5 N·m (40 lbf·in) 1-2 2B, C, G, H, I (DLO)
10 4 N·m (35 lbf·in) 1 - 2 B, C, I (DLO)
12 - 14 4 N·m (35 lbf·in) 1-4 B, C
1-2 I (DLO)
www.marathonsp.com 3PDS 0074 REV-D 01/13/17
Short Circuit Current Ratings (SCCR)
The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of
the default rating of 10,000A.
Other conductor combinations within the “Terminal Speci cations” noted are suitable for achieving a
SCCR of 10,000A (the default rating of terminal blocks).
Enclosure size – Investigated with a minimum 16x12x6 enclosure. Use in smaller enclosures is subject to
end use evaluation.
Wire
Class
Suitable
Conductors
Max Overcurrent Protection Fuse Required
Amp Rating / Class SCCR RMS
Sym. Amps
600V. Max
Line Load J T RK1 RK5 G CC
B, C 500 - 3/0 2 - 8 500 500 400 200 60 30 100,000
B, C 500 - 4 2 - 10 200 200 200 100 60 30 100.000
G, H, I 350 - 2 4 - 14 150 150 100 30 60 30 100,000
(*) 500 - 4 2 - 14 None 10,000
SCCR With Fuses
Installation & Accessories
Mounting (Panel):
For use with #10 fastener.
Torque mounting fastener to 25-30 lbf·in (2.8 - 3.4 N·m).
Covers:
Flat covers available upon request
Catalog Number: CH144x (replace “x” with number of poles)
Covers are clear polycarbonate
Accessory covers are not intended to provide insulation for electrical spacings.
Marker Strip: white vinyl strip with mounting screws available.
Printing options available, consult customer service for speci cations.
* Any wire class evaluated (see terminal speci cation section)
www.marathonsp.com 4PDS 0074 REV-D 01/13/17
Drawing