48
PRODUCT CATALOGUE - STEGOCOOLING
FILTER FAN PLUS
FPI/FPO 018 | up to 97 m³/h (124 x 124 mm)
TECHNICAL DATA
Axial fan, ball bearing service life L10 at +40 °C (+104 °F): min. 37,000 h
fan body aluminium, rotor metal
Connection 2 stranded wires, 300 mm
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 124 x 124+1 mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1 4 mm).
Additional use of screws possible if needed1.
Filter mat G3 acc. to DIN EN 779, average arrestance Aa 84 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100 °C, self-extinguishing class F1,
moisture resistant to 100 % RH, reusable
Operating/Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request
AIRFLOW DIRECTION "IN": FILTER FAN FPI 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01871.0-30 AC 230 V, 50/60 Hz 52 m³/h 42 m³/h 120 mA 19 W 49 db (A) 66 mm 0.8 kg G3
01871.9-30 AC 115 V, 50/60 Hz 62 m³/h 51 m³/h 230 mA 18 W 53 db (A) 66 mm 0.8 kg G3
AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118
Art. No. Depth in enclosure Weight (approx.) Air outlet
11871.0-00 35 mm 0.3 kg air-flap outlet technology
Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components.
The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure
thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations
and protects electronic components from overheating.
The Filter Fan Plus series uses a new air-flap outlet technology for the air outlet and thus reaches a high degree
of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the
application there are two systems that are available – the FPI or FPO system. The FPI system is a standard installation
with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow
direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located
in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of
an intake filter and exit filter fan. The Filter Fan Plus series has been designed for indoor use.
> New air-flap outlet technology for
high airflow
> Easy mounting
> Protection type test/Environmental
rating by independent testing institutes
(VDE and UL)
> Two systems for optimal airflow
(FPI/FPO)
> Standard enclosure cut-out sizes
(5 sizes)
> One filter mat
1 Drilling marks for screw mounting are indicated on mounting frame.
warmcold
Exit Filter FPI 118
Filter Fan FPI 018
Air-flaps
Filter mat
SYSTEM FPI
19.03.2019 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
48TECHNICAL DATASHEET
49
FPI 118FPI 018 FPO 118FPO 018
25
124
152 66
35
25
124
25
124
152 66
35
25
124
25
124
152 66
35
25
124
152
79
25
124
124
25
22
152
79
25
124
124
25
22
152
79
25
124
22
124
+1
0
124
+1
0
STEGO - PRODUCT CATALOGUE COOLING
FILTER MAT FM 086
Filter class 118 x 118 mm Average arrestance Aa1 packing unit
G3 acc. to DIN EN 779 Art. No. 08634.0-00 84 % 5 pieces
AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with intake filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01881.0-00 AC 230 V, 50/60 Hz 97 m³/h 47m³/h 120 mA 19 W 49 db (A) 79 mm 0.9 kg air-flaps
01881.9-00 AC 115 V, 50/60 Hz 117 m³/h 58 m³/h 230 mA 18 W 52 db (A) 79 mm 0.9 kg air-flaps
AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118
Art. No. Depth in enclosure Weight (approx.) Filter mat
11881.0-30 22 mm 0.2 kg G3 acc. to DIN EN 779, average arrestance Aa 84 %
TECHNICAL DRAWINGS
warmcold
Filter Fan FPO 018
Intake Filter FPO 118
Air-flaps
Filter mat
SYSTEM FPO
ENCLOSURE CUT-OUT ENCLOSURE CUT-OUT
19.03.2019 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application. www.stego.de | www.stego.co.uk | www.stegonorden.se
49
TECHNICAL DATASHEET