SIMATIC NET Preface, Contents Industrial Ethernet OMC Introduction 1 Functions 2 Network Topologies with OMCs 3 Interfaces and Displays 4 Installation 5 Technical Specifications 6 Further Support 7 Notes on the CE Mark 8 Glossary 9 Index 10 References 11 Operating Instructions Release 8 / 2001 C79000-G8976-C164-01 Classification of Safety-Related Notices This document contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: Danger indicates that death or severe personal injury will result if proper precautions are not taken. ! Warning ! Caution indicates that death or severe personal injury can result if proper precautions are not taken. with warning triangle indicates that minor personal injury can result if proper precautions are not taken. Caution without warning triangle indicates that damage to property can result if proper precautions are not taken. Notice indicates that an undesirable result or status can occur if the relevant notice is ignored. Note highlights important information on the product, using the product, or part of the documentation that is of particular importance and that will be of benefit to the user. 2 Industrial Ethernet OMC C79000-G8976-C164-01 Trademarks SIMATIC, SIMATIC NET and SINEC are registered trademarks of Siemens AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners. Safety Instructions Regarding your Product Before you use the product described here, read the safety instructions below thoroughly. Qualified Personnel Only qualified personnel should be allowed to install and work on this equipment . Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards. Correct Usage of Hardware Products Please note the following regarding the correct usage of hardware products: Caution This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. Before you use the supplied sample programs or programs you have written yourself, make certain that no injury to persons nor damage to equipment can result in your plant or process. EU Directive: Do not start up until you have established that the machine on which you intend to run this component complies with the directive 89/392/EEC. Industrial Ethernet OMC C79000-G8976-C164-01 3 Prior to Startup Before putting the product into operation, note the following warning: Caution Before installation and startup, read the instructions in the appropriate documentation. For ordering data of the documentation, please refer to catalogs or contact your local Siemens representative. 4 Industrial Ethernet OMC C79000-G8976-C164-01 Preface Purpose of the Operating Instructions These Operating Instructions support you when configuring, commissioning, and troubleshooting networks including the Optical Media Converters OMC TP11 and OMC TP11-LD. The Package The OMC includes the following components: * OMC device * 6-pin plug-in terminal block * Fittings (fixing brackets, screws) for wall mounting or installation in a 19" cabinet * Product Information Mounting the OMC Follow the instructions in Chapter 5 of these operating instructions. Validity of the Operating Instructions These operating instructions are valid for the following devices: 5 * OMC TP11 * OMC TP11-LD Industrial Ethernet OMC C79000-G8976-C164-01 Preface Further Documentation The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks" manual contains information on other SIMATIC NET products that you can operate in conjunction with OMCs in an Industrial Ethernet network. You can download this manual from Customer Support on the Internet under entry number 1172207: http://www4.ad.siemens.de/view/cs/de/1172207 Finding Information To help you to find information quickly, the appendix includes the following sections in addition to the table of contents: * Glossary * Index Guide to the Manual To help you to find specific information quickly, these operating instructions include the following parts: * At the front of the operating instructions you will find a complete table of contents. * The chapters have headings in the left margin with an overview of the contents of the paragraphs in the section. * Following the appendix, you will find a Glossary in which the most important specialist terms used in the instructions are defined. * At the back of the operating instructions, you will find an index with which you can find topics quickly. Audience These Operating Instructions are intended for persons involved in configuring, commissioning, and troubleshooting networks including the OMC TP11 and OMC TP11-LD. 6 Industrial Ethernet OMC C79000-G8976-C164-01 Preface Personnel Qualification Requirements Only qualified personnel should be allowed to install and work on this equipment. Qualified personnel as referred to in the operating instructions or in the warning notes are defined as persons who are familiar with the installation, assembly, startup and operation of this product and who possess the relevant qualifications for their work, e.g.: * Training in or authorization for connecting up, grounding or labeling circuits and devices or systems in accordance with current standards in safety technology; * Training in or authorization for the maintenance and use of suitable safety equipment in accordance with current standards in safety technology; * First Aid qualification. Standards and Approvals The OMC meets the requirements for the CE mark. For more detailed information about approvals and standards, refer to the appendix. Industrial Ethernet OMC C79000-G8976-C164-01 7 Contents 1 Introduction .....................................................................................................................9 1.1 OMC TP11..........................................................................................................10 1.2 OMC TP11-LD....................................................................................................12 2 Functions .......................................................................................................................13 3 Network Topologies with OMCs ..................................................................................14 4 Interfaces and Displays ................................................................................................18 5 4.1 TP Port ...............................................................................................................19 4.2 FO Port ...............................................................................................................21 4.3 Signaling Contact and Power Supply .................................................................22 4.4 Displays ..............................................................................................................24 Installation and Maintenance .......................................................................................25 5.1 Components of the Product................................................................................26 5.2 Installation...........................................................................................................27 5.3 Cleaning..............................................................................................................32 5.4 Maintenance .......................................................................................................33 6 Technical Specifications ..............................................................................................34 7 Further Support .............................................................................................................37 8 Notes on the CE Mark ...................................................................................................41 9 Glossary .........................................................................................................................43 10 Index ............................................................................................................................44 11 References .....................................................................................................................45 8 Industrial Ethernet OMC C79000-G8976-C164-01 Introduction 1 The OSM/ESM V2 (/5/) product generation allows you to structure powerful Fast Ethernet networks in an industrial environment. However, nodes can only be attached to the network over twisted-pair ports; in other words electrically. To remove this restriction, the OSM/ESM product range has been expanded with the addition of the OMC TP11 and OMC TP11-LD media converters. The OMCs open up new areas of application, such as: 9 * FO right up to the machine: Fast FO node attachment (100 Mbps full duplex) over FO ports of the OSMs and media converters in areas with high levels of electromagnetic interference. * Spanning of long distances (LD, long-distance): FO cable sections up to 26 km to a single remote station. Industrial Ethernet OMC C79000-G8976-C164-01 Introduction 1.1 OMC TP11 Possible Attachments * A network component, such as an ESM electrical switch module or a DTE over the twisted-pair port (RJ-45 socket) * A network component, such as an OSM optical switch module or a DTE over a second OMC at the optical port (2 BFOC sockets) Figure 1: OMC TP11 10 Industrial Ethernet OMC C79000-G8976-C164-01 Introduction Properties of the OMC TP11 Electrical port 100 Mbps (full duplex) TP connector technology (RJ-45 socket with MDI-X Pinning (Medium Dependent Interface-Cross Over)) Max. cable length 6 m (TP Cord or TP XP Cord) Optical port 100 Mbps FO ports (full duplex) BFOC female connectors Maximum distance between two OMC TP11 modules or to an OSM ITP62-LD Industrial Ethernet OMC C79000-G8976-C164-01 3000 m (multimode graded-index fiber) 11 Introduction 1.2 OMC TP11-LD Possible Attachments The OMC TP11-LD is suitable for spanning extremely long distances. With the monomode fiber, distances up to 26 km between two OMC TP11-LD or between an OMC TP11-LD and OSM ITP62-LD can be spanned. Properties of the OMC TP11-LD Electrical port 100 Mbps (full duplex) TP attachment technology (RJ-45 socket with MDI-X Pinning (Medium Dependent Interface-Cross Over)) Max. cable length 6 m (TP Cord or TP XP Cord) Optical port 100 Mbps FO ports (full duplex) BFOC female connectors Maximum distance between two 26 km (monomode fiber) OMC TP11-LD Note The OMC TP11-LD can only be linked with the OMC TP11-LD or OSM ITP62-LD over its optical port. Linking the optical port with an OMC TP11, OSM ITP62, OSM ITP53 or OSM TP62 is not permitted. 12 Industrial Ethernet OMC C79000-G8976-C164-01 Functions 2 Converting between 100BaseTX and 100BaseFX The OMC is used to link standard 100BaseTX Ethernet over twisted-pair (TP) cable and 100BaseFX Ethernet over FO cable. All data is forwarded transparently from the optical port to the electrical port and vice versa. Notice The devices attached to OMCs must support 100 Mbps and full duplex. Setting the Transmission Rate or Duplex Mode * An OMC is connected optically to an OSM FO port: In this configuration, if the device connected to the TP interface of the OMC is capable of autonegotiation and the full duplex mode, the device is configured automatically for 100 Mbps and full duplex. Using components of the OSM family and devices capable of autonegotiation and full duplex makes a plug-andplay configuration possible. * Two OMCs are interconnected over an FO cable: If two devices with activated autonegotiation are connected to the two OMCs, the autonegotiation procedure taking place at both ends at the same time may prevent a link from being established. To prevent this, one or both of the TP devices must be permanently set to 100 Mbps and full duplex. Link Fault Transfer The link status of the FO link is transferred to the TP port and vice versa. This means that the OMC can also be used in redundant rings or in standby sections for the redundant linking of subnets. 13 Industrial Ethernet OMC C79000-G8976-C164-01 Network Topologies with OMCs 3 Using the media converters OMC TP11 and OMC TP11-LD, the following applications can be implemented. Attachment of Individual Remotely Located DTEs over OMC-FOC-OMC to a Twisted-Pair Network 10/100 Mbps max. 100 m PC ESM ESM 100 Mbps TP XP Cord max. 6 m OMC 100 Mbps fiber-optic max. 3 km / 26 km OMC S7-400 S7-300 100 Mbps TP Cord max. 6 m Notice Since two OMCs are connected over FO cable, one of the two TP devices (in the figure: S7-400 CP or ESM port to the OMC) must be permanently set to 100 Mbps and full duplex. 14 Industrial Ethernet OMC C79000-G8976-C164-01 Network Topologies with OMCs Attachment of Remotely Located Subnets over OSM-FOC-OMC to a Twisted-Pair Network PC 10/100 Mbps max. 100 m OMC 100 Mbps TP XP Cord max. 6 m ESM ESM 100 Mbps fiber-optic max. 3 km / 26 km OSM 10/100 Mbps max. 100 m S7-400 S7-300 The ESM port to the OMC sets itself automatically to 100 Mbps and full duplex. Manual setting of the ESM port to the OMC is not necessary. Industrial Ethernet OMC C79000-G8976-C164-01 15 Network Topologies with OMCs Including FO Cable Sections in a Twisted-Pair Network, for Example in an ESM Ring 10/100 Mbps max. 100 m OMC OMC ESM ESM PC ESM 100 Mbps fiber-optic max. 3 km / 26 km Notice To keep to the specified failover times in a redundant configuration, both TP devices connected to the OMCs must be permanently set to 100 Mbps and full duplex. 16 Industrial Ethernet OMC C79000-G8976-C164-01 Network Topologies with OMCs Redundant Linking of OSM/ESM Subnets Located a Long Distance Apart over OMC TP11 or OMC TP11-LD OSM/ESM ring 1 Stby cable OSM/ESM in Stby mode OMC TP11-LD OMC TP11-LD Fiber-optic 100 Mbps max. 26 km OMC TP11-LD OMC TP11-LD OSM/ESM ring 2 Notice To keep to the specified failover times in a redundant configuration, all TP devices connected to the OMCs must be permanently set to 100 Mbps and full duplex. Industrial Ethernet OMC C79000-G8976-C164-01 17 Interfaces and Displays 18 4 Industrial Ethernet OMC C79000-G8976-C164-01 Interfaces and Displays 4.1 TP Port Pinning On the OMC, the TP port is implemented as an RJ-45 with MDI-X Pinning (Medium Dependent Interface-Cross Over) socket. Notice TP Cords or TP-XP Cords with a maximum length of 6 m can be connected to the TP port. Other attachments (connections via outlets, longer TP Cords) are not permitted. Link Control The attached cable segments are monitored according to the 100BASETX standard for short circuits or wire breaks. A fault on the link is signaled by the port status displays of the OMC and of the devices connected to the TP and FO ports. Duplex Mode The OMC is capable of full duplex mode; in other words data can be transferred in both directions at the same time. The optical interfaces of the OMC also operate in full duplex mode so that TP devices connected to these ports must also be set to this mode. Note Both devices connected to the OMC (FO and TP) must be set to full duplex mode. If the devices do not support autonegotiation, full duplex mode must be configured manually. Autonegotiation Using the autonegotiation mechanism according to the IEEE standard 802.3, a TP device capable of autonegotiation and full duplex is automatically set to 100 Mbps and full duplex. Industrial Ethernet OMC C79000-G8976-C164-01 19 Interfaces and Displays Note 20 * It is not possible to link two OMCs over their TP interfaces. * The OMC can be used along with products of the OSM/ESM family in redundant rings or in standby links (see Network Topologies OMC, Part 3). To keep to the specified failover times in a redundant configuration, both TP devices connected to the OMCs must be permanently set to 100 Mbps and full duplex. * If two OMCs are interconnected over an FO cable and if two devices with activated autonegotiation are connected over their TP ports, the autonegotiation procedure taking place at both ends at the same time may prevent a link from being established. To prevent this, one or both of the TP devices must be permanently set to 100 Mbps and full duplex. Industrial Ethernet OMC C79000-G8976-C164-01 Interfaces and Displays 4.2 FO Port The FO port has a BFOC/2.5(ST) female connector. The connected cable is monitored for wire breaks complying with the IEEE 802.3 100BaseFX standard. A break on the FO cable is always signaled by the port status displays of the OMC and of the two attached devices. (Status LED of the port goes off). Industrial Ethernet OMC C79000-G8976-C164-01 21 Interfaces and Displays 4.3 Signaling Contact and Power Supply The attachment of the power supply and the signaling contact is made using a 6-pin plug-in terminal block with a screw securing mechanism. L1 + +24V DC F1 M M F2 L2 + +24V DC Figure 2: Terminal Block ! Warning Industrial Ethernet OMCs are designed for operation with safety extra-low voltage. This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can be connected to the power supply terminals and the signaling contact. The power supply unit to supply the OMC must comply with NEC Class 2 (voltage range 18 - 32 V, current requirement 1 A) The signaling contact can carry a load of maximum 100 mA (safety extra-low voltage (SELV), DC 24V). 22 Industrial Ethernet OMC C79000-G8976-C164-01 Interfaces and Displays Power Supply The power supply can be connected redundantly. Both inputs are isolated. There is no load distribution. With redundant power supply, the power supply unit with the higher output voltage supplies the OMC alone. The power supply is connected over a high resistance with the enclosure to all an ungrounded setup. Signaling Contact The following is signaled via a floating signaling contact (relay contact) when contact is broken: * The failure of one or both power supplies. Notice Both power supplies are always monitored (L1 and L2). If only one power supply exists, this must be applied via L1 and L2 otherwise the signaling contact will signal an error. * The incorrect link status of a port (in other words, the port is not correctly attached or there are no link test pulses coming from the partner device). Industrial Ethernet OMC C79000-G8976-C164-01 23 Interfaces and Displays 4.4 Displays Fault display (red LED) Status Meaning On The OMC has detected an error. The signaling contact opens at the same time. The signaled errors are described in Chapter 4.3. Off No errors detected by the OMC. Power display (green LEDs) The status of the redundant power supply is signaled by two green LEDs: Status Meaning On Power supply L1 or L2 is connected Off Power supply L1 or L2 is not connected or <14 V Port status display (green/yellow LEDs) The status of the ports is signaled by two LEDs: Status 24 Meaning Port 1 LED green TP link exists, no data reception Port 1 LED yellow TP link exists, receiving data at TP port Port 1 LED off No TP link exists Port 2 LED green FO link exists, no data reception Port 2 LED yellow FO link exists, receiving data at FO port Port 2 LED off No FO link exists Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance 25 5 Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance 5.1 Components of the Product Unpacking, Checking the Consignment 1. Check that the consignment includes the following components: - OMC device - Mounting brackets, screws and terminal block - Product Information 2. Check each component for any damage. ! 26 Warning Do not install damaged components! Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance 5.2 Installation There are several ways of installing the OMC: * Installation on a 35 mm standard rail * Installation on a SIMATIC S7-300 rail * Installation in a 19" cabinet (along with other OMCs and OSMs/ESMs) * Wall mounted Note * Remember that the OMC must only be installed horizontally (ventilation slits top/bottom see Figure 4). To ensure adequate convection, there must be a clearance of at least 5 cm above and below the ventilation slits. You should also make sure that the permitted ambient temperature range is not exceeded. * The optical transmitter and receiver elements are sensitive to contamination. You should therefore only remove the dust protection caps from the BFOC sockets immediately before plugging in the FO connector. If you remove the connector, cover the sockets immediately with the dust protection caps. * During installation and operation, make sure that you adhere to the installation instructions and safety-related notices in this description and in the SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks manual /2/. Preparations Remove the terminal block from the OMC and wire up the power supply and signal lines as described in Section 4.3. Industrial Ethernet OMC C79000-G8976-C164-01 27 Installation and Maintenance Standard Rail Mounting 1. Install the OMC on a 35 mm standard rail complying with DIN EN 50022. 2. Fit the OMC on to the rail from above and press in the bottom of the device until the catch engages. 3. Connect the electrical and optical cables and the terminal block for the power supply. Figure 3: Installing the OMC on a DIN Standard Rail 28 Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance Removing from a Standard Rail To remove the OMC from the rail, first disconnect the FO and TP cables and pull off the terminal block. Then pull down the device and release it from the rail. Figure 4. Removing from the Standard Rail Industrial Ethernet OMC C79000-G8976-C164-01 29 Installation and Maintenance Installation on a SIMATIC S7-300 Rail 1. First fix one of the two supplied brackets to the right (OMC mounted on the right) or the left (OMC mounted on the left) side of the OMC. 2. Fit the guide on the top of the OMC casing into the S7 rail. 3. Screw the OMC to the bottom of the standard rail. Installation in a 19" Cubicle To install in the 19" cubicle, you require the two securing brackets supplied. You can achieve the 19'' width * with eight OMCs * with one OSM / ESM and four OMCs Follow the steps outlined below: 1. First screw the OMCs or ESMs/OSMs to the supplied mounting plates at the rear. 2. Fit two of the supplied brackets to the sides 3. Secure the devices using the brackets in the 19" cubicle. Please note that the OMC must be grounded with low resistance via the two holding brackets. Note To install in a 19'' cubicle, you require a Torx screwdriver size T10 x 80. 30 Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance Wall Mounting To install an OMC on a wall, follow the steps below: 1. Fit the supplied mounting brackets on the sides of the OMC. 2. Secure the device to the wall using the brackets. 3. Connect the device to protective earth with a low-resistance connection via one of the brackets. The table below shows how to secure the module depending on the wall type. Wall Type Mounting Concrete wall Use four wall plugs 6 mm in diameter 30 mm long (drillhole 6 mm diameter, 45 mm deep). Use screws 4.5 mm in diameter and 40 mm long. Metal wall Use screws 4 mm in diameter and at least 15 mm long. (min. 2 mm thick) Sandwich type plaster wall (min. 15 mm thick) Use an anchoring plug with at least 4 mm diameter. Note The module must be secured to the wall so that the mounting can carry at least four times the weight of the module. Industrial Ethernet OMC C79000-G8976-C164-01 31 Installation and Maintenance 5.3 Cleaning The OMC casing can be cleaned, when necessary with a dry cloth. 32 Industrial Ethernet OMC C79000-G8976-C164-01 Installation and Maintenance 5.4 Maintenance If a fault develops, please send the module to your SIEMENS service department for repair. The devices cannot be repaired on site. Industrial Ethernet OMC C79000-G8976-C164-01 33 Technical Specifications 6 Attachments Attachment of DTEs or Network Components over Twisted Pair 1 x RJ-45 with MDI-X Pinning (Medium Dependent Interface-Cross Over) on OMC TP11 and OMC TP11-LD The ports operate at 100 Mbps, full duplex (100BaseTX) Attachment of other network components or OMCs over FO cable 2 BFOC sockets on the OMC TP11 and OMC TP11-LD (100 Mbps, full duplex complying with 100BaseFX) Connector for power supply and signaling contact 1 x 6-pin plug-in terminal block Electrical Data 34 Power supply (redundant inputs isolated) 2 supplies DC 24 V (DC 18 to 32 V) safety extra-low voltage (SELV) Power loss at DC 24 V 3.6 W Load on the signaling contact DC 24 V / max. 1000 mA safety extralow voltage (SELV) Current consumption at rated voltage 150 mA Overcurrent protection at input PTC resettable fuse (0.6 A / 60 V) Industrial Ethernet OMC C79000-G8976-C164-01 Technical Specifications Permitted Cable Lengths FO link between two OMCs OMC TP11: 0-3000m (62.5/125 m or 50/125m glass fiber; 1 dB/km at 1300 nm; 600 MHz*km; 6 dB max. permitted FO cable attenuation at 3 dB link power margin) OMC TP11-LD: 0-26000m (10/125 m monomode fiber; 0.5 dB/km at 1300 nm; 13 dB max. permitted FO cable attenuation at 2 dB TP Connection 0-6 m with TP cord Permitted Ambient Conditions/EMC Operating temperature 0C to +60C Storage/transport temperature -40C to +80C Relative humidity in operation 95% (no condensation) Operating altitude Max. 2000 m Noise emission EN 55081 Class A Noise immunity EN 50082-2 Degree of protection IP 20 Laser protection Class 1 complying with IEC 60825 -1 Industrial Ethernet OMC C79000-G8976-C164-01 35 Technical Specifications Mechanical Design Dimensions (W x H x D) in mm 54 x 136.5 x 69 Weight in g 500 Installation options Standard rail S7-300 rail Wall mounted Installation in 19" cubicle Only horizontal installation permitted (ventilation slits top/bottom) Product and Ordering Data OMC TP11 and OMC TP11-LD * OMC device * Mounting brackets, screws and terminal block * Product Information Order numbers: 36 OMC TP11 6GK1100-2AB00 OMC TP11-LD 6GK1100-2AC00 "Industrial Twisted Pair and Fiber Optic Networks" Manual 6GK1970-1BA10-0AA1 Industrial Ethernet OMC C79000-G8976-C164-01 Further Support 7 Who to Contact If you have technical questions about using the described product and your problem is not dealt with in the documentation or in the integrated help system, please contact your Siemens representative or dealer. You will find the addresses: 37 * in our catalog IK PI * on the Web (http://www.ad.siemens.de/net) Industrial Ethernet OMC C79000-G8976-C164-01 Further Support Automation and Drives, Service & Support Service & Support from A&D is available round the clock worldwide. The languages spoken are German and English. French, Italian, and Spanish are also spoken on the authorization hotline. Johnson City Nuremberg Singapore Service & Support Technical Support Authorization Hotline Europe and Africa (Nuremberg) Mo. To Fr. 7:00 to 17:00 (local time, GMT +1) Phone: +49 - (0) 180 - 5050 - 222 Fax: +49 - (0) 180 - 5050 - 223 E-mail: techsupport@ad.siemens.de Europe and Africa (Nuremberg) Mo. To Fr. 7:00 to 17:00 (local time, GMT +1) Phone: +49 - (0) 911 - 895 - 7200 Fax: +49 - (0) 911 - 895 - 7201 E-mail: authorization@nbgm.siemens.de America (Johnson City) Mo. To Fr. 8:00 to 19:00 (local time, GMT -5) Phone: +1 - (0) 423 - 262 - 2522 Fax: +1 - (0) 423 - 262 - 2231 E-mail: simatic.hotline@sea.siemens.com Asia and Australia (Singapore) Mo. To Fr. 8:30 to 17:30 (local time, GMT +8) Phone: +65 - (0) 740 - 7000 Fax: +65 - (0) 740 - 7001 E-mail: simatic.hotline@sae.siemens.com.sg SIMATIC Premium Hotline Worldwide (Nuremberg) Workdays 0:00 to 24:00 (local time, GMT +1) Phone: +49 - (0) 911 - 895 - 7777 Fax: +49 - (0) 911 - 895 - 7001 E-mail: techsupport@ad.siemens.de 38 Fast callback guaranteed within a maximum of two hours (charged, only with the SIMATIC Card) Industrial Ethernet OMC C79000-G8976-C164-01 Further Support Service & Support on the Internet On the World Wide Web, you will find the very latest information on the entire SIMATIC product range, for example, answers to frequently asked questions (FAQs), Tips and Tricks, software updates, and user information. In addition to this free information, you can also order the following, for which a charge is made: * Software products * Sample application programs These are charged to the SIMATIC CARD. Internet address: http://www.siemens.de/automation/service&support You can also formulate a question for the SIMATIC Knowledge Manager that will find the solution in the knowledge database. If you are working in an area without an online connection, part of the free information area is available on the "SIMATIC Customer Support Knowledge Base" CD. Industrial Ethernet OMC C79000-G8976-C164-01 39 Further Support Training for SIMATIC NET Who to Contact about Training Courses: Siemens AG Trainings-Center fur Automatisierungs- und Antriebstechnik A&D PT 49 Kursburo Ostliche Rheinbruckenstrae 50 76181 Karlsruhe Germany Phone: Fax: Internet: +49 - (0) 721 - 595 - 2917 +49 - (0) 721 - 595 - 6087 http://www.sitrain Certification The products of SIMATIC NET are manufactured and marketed using a quality management system complying with DIN ISO 9001 and certified by DQS (certificate registration no. 2613). The DQS certificate is recognized in all IQNet countries (Reg. No. 2613). 40 Industrial Ethernet OMC C79000-G8976-C164-01 Notes on the CE Mark 8 Product name: SIMATIC NET OMC TP11 6GK1100-2AB00 OMC TP11-LD 6GK1100-2AC00 The SIMATIC NET products listed above meet the requirements of the following EU directives: EMC Directive Directive 89/336/EEC "Electromagnetic Compatibility" Area of Application The products are designed for use in an industrial environment: Area of Application Industry Requirements Noise emission Noise immunity EN 50081-2 : 1993 EN 50082-2 : 1995 Installation Guidelines * 41 The products meet the requirements if you adhere to the installation and safety instructions contained in this description and in the "SIMATIC NET Industrial Ethernet TP and Fiber-Optic Networks" manual. Industrial Ethernet OMC C79000-G8976-C164-01 Notes on the CE Mark Conformity Certificates The EU declaration of conformity is available for the responsible authorities according to the above-mentioned EU directive at the following address: Siemens Aktiengesellschaft Bereich Automatisierungs- und Antriebstechnik Industrielle Kommunikation (A&D PT2) Postfach 4848 D-90327 Nurnberg Germany Notes for the Manufacturers of Machines This product is not a machine in the sense of the EU directive on machines. There is therefore no declaration of conformity for the EU directive on machines 89/392/EEC. If the product is part of the equipment of a machine, it must be included in the procedure for obtaining the declaration of conformity by the manufacture of the machine. 42 Industrial Ethernet OMC C79000-G8976-C164-01 Glossary 9 Autonegotiation Procedure standardized by IEEE 802.3 in which the transmission parameters (for example 10/100 Mbps, full/half duplex) are negotiated automatically between the devices. Autosensing See Autonegotiation BFOC Bayonet Fiber-Optic Connector (ST-compatible). EMC Electromagnetic compatibility ESM Electrical Switching Module. SIMATIC NET Ethernet switch with electrical ports FOC Fiber-optic cable LD Long Distance MDI-X MDI-X Pinning (Medium Dependent Interface-Cross Over) OMC Optical Media Converter OSM Optical Switching Module. SIMATIC NET Ethernet switch with optical and electrical ports Signaling contact Floating relay contact via which the error states detected by the OMC can be signaled. TP Port Twisted-pair port 43 Industrial Ethernet OMC C79000-G8976-C164-01 Index A Ambient conditions, permitted..................35 Attachments .............................................34 Authorization hotline .................................38 C Cable lengths, permitted ..........................35 Customer Support ....................................38 D Design, mechanical..................................36 Displays ..............................................18, 24 E Electrical data...........................................34 F FO ports ...................................................21 I Installation in cubicle Schrank ..................30 Installation, S7-300 rail.............................30 Interfaces .................................................18 10 M Mounting, standard rail ............................ 28 N Network Topologies ................................. 14 O OMC TP11............................................... 10 OMC TP11-LD ......................................... 12 P Power supply ........................................... 23 Product and ordering data ....................... 36 S Signaling contact ..................................... 23 T Technical specifications........................... 34 Technical Support.................................... 38 TP port ..................................................... 19 W Wall mounting.......................................... 31 L Link control ...............................................19 44 Industrial Ethernet OMC C79000-G8976-C164-01 References 11 /1/ SIMATIC NET Industrial Ethernet OSM/ESM Network Management, Release 08/2001 Available at http://www4.ad.siemens.de/view/cs/de/8677203 on the Web. /2/ SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks, Release 05/2001 Order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian /3/ SINEC H1 Manual for Triaxial Networtks, Release 04 Order number 6GK1970-1AA20-0AA0 (German/English) 45 Industrial Ethernet OMC C79000-G8976-C164-01