Product Data Sheet 132X572 CH Replace "X" with 1, 2 or 3 for number of poles Power Splicer Block 175 Amps, 600 Volts (AC/DC) 1,000V AC/DC CE (IEC 60947-7-1) Wire Range: Line side: (1) 2/0 - #14 AWG Load Side: (1) 2/0 - #14 AWG See tables below for SCCR wire ranges, flexible stranded and multiple wire approvals. Insulator base adders and 1 pole product can be snapped together through integral dovetails to create variable pole power blocks. 7.5 x 35 mm din rail or panel mountable Electrical Ratings: * 175A copper wire, 135A aluminum wire (Based on NEC Table 310-16, 75C columns) * CE Rated Voltage (Ui): 1,000 V AC/DC per IEC 60947-7-1 * Rated Impulse Voltage (Uimp): 6,000V * Material Group: IIIa * Pollution Degree: 3 * UL/CSA Voltage Rating: 600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial) * Factory and Field Wiring Short Circuit Current Ratings (Copper wire only): Wire Class B, C G, H, I, K Suitable Conductors (kcmil/AWG) Line Load 2/0 - 6 2/0 - 6 1-6 1-6 Overcurrent Protection Fuse Required Class/Max Amp Rating G CC J T RK1 RK5 200 200 200 100 60 30 150 150 100 30 60 30 SCCR, RMS SYM Amps Volts Max 100,000 100,000 600 600 * Short Circuit Current Rating investigated in 16 x 12 x 6 enclosure. Use in smaller enclosure is subject to end-use evaluation. Mechanical Ratings: * Insulator base and cover temperature: -40C/F to 125C (257F) UL RTI* * Flammability rating of insulator base and cover: UL 94 V-0 * Use outside these ratings needs to be judged in the end-use application. Materials: * Connector: High conductivity aluminum, tin plated * Insulator base: Glass filled polycarbonate (thermoplastic) * Terminal set screws: Aluminum, tin plated * Connector mounting screw: Steel, zinc plated * Hinged Cover: Glass filled polycarbonate (thermoplastic) Agency Approvals: * UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806 * CSA Certified, CSA C22.2 No. 158, File No. LR19766 (Wire Classes B & C only) * CE compliant to IEC 60947-7-1 * RoHS Compliant Wire Approvals: Line and Load Side Wire Approvals: Wire Size 2/0 AWG 1/0 1 2 4 6 8 10 12 14 N-m 13.6 13.6 13.6 13.6 13.6 13.6 4.5 4.0 4.0 4.0 Torque In. lbs 120 120 120 120 120 120 40 35 35 35 Solid 1 1 1 Copper Wire Stranding Classes - Number of Conductors Class K Class B Class C Class G Class H Class I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Aluminum stranded wire range: 2/0- #6 AWG * Wire strip length, line and load side taps - 3/4" * Hex key required : 5/16" For information on copper stranded wire classes, please reference: http://www.marathonsp.com/CatalogPDFs/Flexible-Stranded-Wire.pdf Mounting: * Panel mountable: #10 fastener, torque to 25-30 in. lb. * Din mountable Accessories: * End bracket for din rail mounting :MSK35 * Marker Strips. Printing available. Consult factory. * Din Rail (35 x 7.5 mm, 2 m long, slotted): MN35-2 1 Pole 2 Pole 3 Pole WWW.MARATHONSP.COM 1-419-352-8441 PDS 0096 REV C 11/29/11