30W Ultra Slim Step Shape DIN Rail HDR-30 series Bauar t gepruft Sicherheit egel ma ge od o s be wac g UL508 UL62368-1 www. tuv.com ID 2000000000 EN61558 R33100 RoHS TPTC004 AS/NZS60950-1 IEC62368-1 Features Ultra slim design with 35mm(2SU) width Universal input 85~264VAC(277VAC operational) No load power consumption<0.3W Isolation class Pass LPS (Limited power source) DC output voltage adjustable Protections : Short circuit / Overload / Over voltage Cooling by free air convection (working temperature:-30~+70C) DIN rail TS-35/7.5 or 15 mountable Over voltage category LED indicator for power on 3 years warranty Applications Household control system Building automation Industrial control system Factory automation Electro-mechanical apparatus Description HDR-30 is one economical ultra slim 30W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 35mm(2SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-30 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30 and 70 under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1, UL508,UL62368-1, EN61558-2-16) make HDR-30 a very competitive power supply solution for household and industrial applications. Model Encoding HDR - 30 - 12 Output voltage Rated wattage Series name File Name:HDR-30-SPEC 2019-11-25 HDR-30 30W Ultra Slim Step Shape DIN Rail series SPECIFICATION MODEL OUTPUT INPUT HDR-30-5 HDR-30-12 HDR-30-15 HDR-30-24 HDR-30-48 DC VOLTAGE 5V 12V 15V 24V 48V RATED CURRENT 3A 2A 2A 1.5A 0.75A CURRENT RANGE 0 ~ 3A 0 ~ 2A 0 ~ 2A 0 ~ 1.5A 0 ~ 0.75A RATED POWER 15W 24W 30W 36W 36W RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 120mVp-p 150mVp-p 240mVp-p VOLTAGE ADJ. RANGE 10.8 ~ 13.8V 13.5 ~ 18V 21.6 ~ 29V 43.2 ~ 55.2V 4.5 ~ 5.5V VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% 1.0% 1.0% LINE REGULATION 1.0% 1.0% 1.0% 1.0% 1.0% LOAD REGULATION 1.0% 1.0% 1.0% 1.0% 1.0% SETUP, RISE TIME 500ms, 50ms/230VAC HOLD UP TIME (Typ.) 30ms/230VAC VOLTAGE RANGE 85 ~ 264VAC (277VAC operational ) FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 82% 89% 90% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 0.88A/115VAC 0.48A/230VAC COLD START 25A/115VAC 45A/230VAC 500ms, 50ms/115VAC at full load 12ms/115VAC at full load 120 ~ 370VDC (390VDC operational ) 89% 88% 105 ~ 160% rated output power OVERLOAD Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed PROTECTION OVER VOLTAGE 5.75 ~ 7.5V 15 ~ 18V 18.8 ~ 22.5V 57.6~ 67.2V 30 ~ 36V Protection type : Shut down o/p voltage, re-power on to recover -30 ~ +70 (Refer to "Derating Curve") WORKING TEMP. 20 ~ 90% RH non-condensing WORKING HUMIDITY STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH non-condensing ENVIRONMENT TEMP. COEFFICIENT VIBRATION 0.03%/ (0 ~ 50) RH non-condensing 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 OPERATING ALTITUDE 2000 meters OVER VOLTAGE CATEGORY ; According to E N 61558, EN50178,EN60664-1, EN62477-1 ; altitude up to 2000 meters UL62368-1, UL508, TUV EN61558-2-16, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to TUV EN62368-1 SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P:4KVAC I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH Parameter Conducted EMC EMISSION SAFETY & EMC (Note 4) Radiated Harmonic Current NOTE EN55032(CISPR32), CNS13438 EN55032(CISPR32), CNS13438 Class B EN61000-3-2 Class A Class B ------Test Level /Note ESD Level 3, 8KV air; Level 2, 4KV contact, criteria A EFT/Burest Surge EN61000-4-2 EN61000-4-3 EN61000-4-4 Conducted Magnetic Field EN61000-4-5 EN61000-4-6 EN61000-4-8 Voltage Dips and interruptions EN61000-4-11 DIMENSION 968.1K hrs min. MIL-HDBK-217F (25) 35*90*54.5mm (W*H*D) PACKING 0.12Kg;96pcs/12.5Kg/1.04CUFT MTBF OTHERS Test Level / Note Voltage Flicker EN61000-3-3 EN55024, EN55035, EN61000-6-2, EN61204-3 Parameter Standard Radiated Susceptibility EMC IMMUNITY Standard Level 3, criteria A Level 3, criteria A Level 4,2KV/L-N, criteria A Level 3, criteria A Level 4, criteria A 95% dip 0. 5 periods, 30% dip 25 periods, 95% interruptions 250 periods 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1f & 47f parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com) 5. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft). File Name:HDR-30-SPEC 2019-11-25 HDR-30 30W Ultra Slim Step Shape DIN Rail series Block Diagram RECTIFIERS & FILTER EMI FILTER I/P RECTIFIERS & FILTER POWER SWITCHING +V -V DETECTION CIRCUIT O.L.P. CONTROL O.V.P. Derating Curve Output Derating VS Input Voltage 100 100 90 80 80 70 50 LOAD (%) LOAD (%) 60 40 20 -30 0 10 20 30 40 50 AMBIENT TEMPERATURE () 60 70 (VERTICAL) 60 50 40 85 95 100 115 120 140 160 180 200 220 240 264 277 (operational) INPUT VOLTAGE (VAC) 60Hz File Name:HDR-30-SPEC 2019-11-25 HDR-30 30W Ultra Slim Step Shape DIN Rail series Mechanical Specification ( Unit: mm , tolerance 0.5mm) 58.4 35 54.5 4 45.15 63.65 90 2 1 3 35 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Terminal Pin No. Assignment Pin No. Assignment 1 +V 2 -V Pin No. Assignment AC/L 3 4 AC/N Installation Manual Please refer to : http://www.meanwell.com/manual.html File Name:HDR-30-SPEC 2019-11-25