0 - 0.1 ... 10 s
1 - 1 ... 100 s
2 - 10 ... 1000 s
3 - 0.1 ... 10 m
4 - 1 ... 100 m
5 - 10... 1000 m
XX X XX
Low Voltage Products & Systems5.168
Description
The HRDR Series combines an electromechanical relay and microcontroller timing circuitry. It offers 12 to
230 V operation in five ranges and factory fixed, onboard or externally adjustable time delays with a repeat
accuracy of +/-0.5%. The high switching capacity of the output contacts allow for direct control of heavy loads
like compressors, pumps, motors, heaters, and lighting. Bypass/reset switch option allows operator to
interrupt normal recycling sequence and energize output relay. An excellent choice for OEM applications.
Operation
Upon application of input voltage, the ON time T1
begins and output relay energizes. At the end of the
ON time, the output relay de-energizes and the OFF
time T2 begins. At the end of the OFF time, the output
relay energizes and the cycle repeats as long as input
voltage is applied. Some recycling timers have the
OFF time as the first delay.
Reset: Removing input voltage resets output and
time delays, and returns sequence to the first delay.
Bypass/Reset Switch: Closing the normally open
bypass/reset switch energizes the output relay and
resets the time delays. Opening the switch restarts
recycling operation with the first delay.
Mechanical View
HRDRGen 10.03.05
30 A SPDT N.O. Output
Contacts
12 ... 230 V Operation in
5 Ranges
Encapsulated Circuitry
Delays from 100 ms ...
1000 m in 6 Ranges
Independent Adjustment of
ON and OFF Delays
+/-0.5% Repeat Accuracy
+/-5% Factory Calibration
Fixed or Onboard or External
Adjustment
Approvals:
Recycling (Pulse Generator)
HRDR Power -Time
Time Delay Relay
Connection
Example P/N:
Function
V = Voltage S1 = Reset Switch
L = Load R = Reset T1 = ON Time
T2 = OFF Time
Recycling w/Reset Switch
Series
HRDR
1 - 12 V DC
2 - 24 V AC
3 - 24 V DC
4 - 120 V AC
6 - 230 V AC
1 - Both Times Fixed
2 - Both Times Onboard Adj.
3 - Both Times External Adj.
4 - ON Time External Adj.
OFF Time Fixed
5 - ON Time Fixed
OFF Time External Adj.
6 - ON Time Onboard Adj.
OFF Time, Fixed
7 - ON Time, Fixed
OFF Time Onboard Adj.
8 - ON Time Onboard Adj.
OFF Time, External Adj.
9 - ON Time, External Adj.
OFF Time Onboard Adj.
0 - 0.1 ... 10 s
1 - 1 ... 100 s
2 - 10 ... 1000 s
3 - 0.1 ... 10 m
4 - 1 ... 100 m
5 - 10 ...1000 m
A - ON Time
First
B - OFF Time
First
Blank - No Bypass/
Reset Option
R - Bypass/Reset
Option
X
Input Operation
T2 OFF Time *Operating
Sequence
T1 ON Time *External Adjust
* If Fixed Delay is selected, insert
delay [ 0.11000 ] followed by ( S )
sec. or [ 0.1 ... 1000 ] ( M ) min.
Inches (Millimeters)
HRDR431A4R
Fixed – HRDR410.2SB100S
= Undefined time
Relay contacts are non-isolated. RT is included
when external adjustment is ordered. Dashed
lines are internal connections. Terminal 6 is
included when Bypass/Reset is selected.
NO = Normally Open S1 = Reset Switch
C = Common, Transfer Contact L = Load
Ordering Table
Note: Terminals 4 & 5 and/or 7 & 8 are only
included on externally adjustable units.
Technical Data
Recycling (Pulse Generator)
HRDR Power -Time
Time Delay Relay
Low Voltage Products & Systems 5.169
HRDRGen 10.03.05
AccessoriesExternal Resistance vs Time Delay
See accessory pages for specifications.
External adjust
potentiometer
P/Ns: P1004-95 ( fig. A)
P1004-95-X (fig. B)
B
A
Versa-knob
P/N: P0700-7
Quick connect to
screw adaptor
P/N: P1015-18
Female quick
connect
P/Ns:
P1015-64
(AWG 14/16)
P1015-13
(AWG 10/12)
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
DIN rail adaptor
P/N: P1023-20
Mounting bracket
P/N: P1023-6
Time Delay
Range 100 ms ... 1000 m in 6 adjustable ranges or fixed
Repeat Accuracy +/-0.5% or 20 ms, whichever is greater
Tolerance (Factory Calibration) +/-5%
Reset Time 150 ms
Time Delay vs. Temperature & Voltage +/-2%
Input
Voltage 12 or 24 V DC; 24, 120, or 230 V AC
Tolerance 12 V DC & 24 V DC -15% ... +20%
24 ... 230 V AC -20% ... +10%
Line Frequency 50 ... 60 Hz
Power Consumption AC 4 VA; DC 2 W
Output
Type Electromechanical relay
Form SPDT, non-isolated
Ratings: SPDT- N.O. SPDT-N.C.
General Purpose 125/240 V AC 30 A 15 A
Resistive 125/240 V AC 30 A 15 A
28 V DC 20 A 10 A
Motor Load 125 V AC 1 hp* 1/4 hp**
240 V AC 2 hp** 1 hp**
Life Mechanical -- 1 x 106; Electrical -- 1 x 105, *3 x 104, **6,000
Protection
Surge IEEE C62.41-1991 Level A
Circuitry Encapsulated
Dielectric Breakdown 2000 V RMS terminals to mounting surface
Insulation Resistance 100 M
Polarity DC units are reverse polarity protected
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Package 3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1mm)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage Temperature -40°C ... +60°C/-40°C ... +85°C
Humidity 95% relative non-condensing
Weight 3.9 oz (111 g)