136
1 NO 2 NO
20/30 20/30
250/400 250/400
5,000 5,000
1,000 1,000
——
20/0.3/0.12 20/0.3/0.12
1,000 (10/10) 1,000 (10/10)
AgNi AgNi
8 - 12 - 24 - 48 - 110 - 120 - 230 - 240
12 - 24 - 48 - 110 12 - 24 - 48 - 110
2.3/1.25 2.3/1.25
(0.85…1.1)UN (0.85…1.1)UN
(0.9…1.1)UN(0.9…1.1)UN
500 · 103500 · 103
50 · 10350 · 103
continuous continuous
4,000 4,000
–40…+40 –40…+40
IP 20 IP 20
22.21 22.22
Contact specifications
Contact configuration
Rated current/Max. peak current A
Rated voltage/Max. switching voltage V AC
Rated load in AC1 VA
Rated load in AC15 (230 VAC) VA
Single phase motor rating (230 VAC) kW/HP
Breaking capacity: 30/110/220 V A
Minimum switching load mW(V/mA)
Standard contact material
Coil specifications
Nominal voltage V AC (50/60Hz)
V DC
Rated power AC/DC VA (50Hz)/W
Operating range AC (50Hz)/W
DC
Technical data
Mechanical life cycles
Electrical life at rated load in AC1 cycles
Maximum impulse duration
Surge test (1.2/50µs) between coil and contacts
V
Ambient temperature range °C
Protection category
Approvals:
(according to type)
22 Series - Modular Monostable Relays 20 A
- Single phase switch 1 NO
- 35 mm rail (EN 50022)
- Double phase switch 2 NO
- 35 mm rail (EN 50022)
A1
A2
1
2
45
58.4
43.5
26.5
84
84
17.5
A1
A2
1
2
3
4
45
58.4
43.5
26.5
84
17.5
84
- One module (17.5mm) wide
- Test button
- Identification label
- AC and DC coils
- 35 mm rail (EN 50022) mount
1 NO + 1 NC 2 NC
20/30 20/30
250/400 250/400
5,000 5,000
1,000 1,000
— —
20/0.3/0.12 20/0.3/0.12
1,000 (10/10) 1,000 (10/10)
AgNi AgNi
8 - 12 - 24 - 48 - 110 - 120 - 230 - 240
12 - 24 - 48 - 110 12 - 24 - 48 - 110
2.3/1.25 2.3/1.25
(0.85…1.1)UN (0.85…1.1)UN
(0.9…1.1)UN(0.9…1.1)UN
500 · 103500 · 103
50 · 10350 · 103
continuous continuous
4,000 4,000
–40…+40 –40…+40
IP 20 IP 20
22.23 22.24
137
22 Series - Modular Monostable Relays 20 A
- Double phase switch
1 NO + 1 NC
- 35 mm rail (EN 50022)
- Double phase switch 2 NC
- 35 mm rail (EN 50022)
A1
A2
1
2
3
4
45
58.4
43.5
26.5
84
84
17.5
A1
A2
1
2
3
4
45
58.4
43.5
26.5
84
17.5
84
Contact specifications
Contact configuration
Rated current/Max. peak current A
Rated voltage/Max. switching voltage V AC
Rated load in AC1 VA
Rated load in AC15 (230 VAC) VA
Single phase motor rating (230 VAC) kW/HP
Breaking capacity: 30/110/220 V A
Minimum switching load mW(V/mA)
Standard contact material
Coil specifications
Nominal voltage V AC (50/60Hz)
V DC
Rated power AC/DC VA (50Hz)/W
Operating range AC (50Hz)/W
DC
Technical data
Mechanical life cycles
Electrical life at rated load in AC1 cycles
Maximum impulse duration
Surge test (1.2/50µs) between coil and contacts
V
Ambient temperature range °C
Protection category
Approvals:
(according to type)
- One module (17.5mm) wide
- Test button
- Identification label
- AC and DC coils
- 35 mm rail (EN 50022) mount
22 Series - Modular Monostable Relays 20 A
ORDERING INFORMATION
COIL SPECIFICATIONS
Nominal Coil Operating range Resistance Absorption
voltage code
Iat UN (50Hz)
UNUmin Umax R
VVVmA
88.008 6.8 8.8 6.5 275
12 8.012 10.2 13.2 13.5 185
24 8.024 20.4 26.4 42 95
48 8.048 40.8 52.8 185 48
110 8.110 93.5 121 980 21
120 8.120 102 132 1,400 18
230 8.230 195.5 253 4,250 10
240 8.240 204 264 4,400 9.5
AC VERSION DATA
Nominal Coil Operating range Resistance
Absorption
voltage code Iat UN
UNUmin Umax R
VVVmA
12 9.012 10.8 13.2 115 104.3
24 9.024 21.6 26.4 460 52.2
48 9.048 43.2 52.8 1,850 25.9
110 9.110 99 121 9,700 11.3
DC VERSION DATA
TECHNICAL DATA
INSULATION
DIELECTRIC STRENGTH
- between supply and contacts V AC
3,500
- between open contacts V AC
2,000
- between adjacent contacts V AC
2,000
SURGE TEST (1.2/50µs)
- between supply and contacts V
4,000
OTHER DATA 22.21 22.22, 22.23, 22.24
POWER LOST IN THE ENVIRONMENT
- without contact current W 1.2 1.2
- with rated current W 3.2 5.2
COIL CLAMPS CONTACT CLAMPS
MAX WIRE SIZE solid cable flexible cable solid cable flexible cable
mm21x4 / 2x2.5 1x2.5 / 2x2.5 1x6 / 2x6 1x6 / 2x4
AWG 1x12 / 2x14 1x14 / 2x14 1x10 / 2x10 1x10 / 2x12
TORQUE Nm 0.8 0.8
138
If the coil is operated for a prolonged period of time, adaquate ventilation of the relays must be provided, for example leaving a gap of about 9mm
between pairs of relays.
Example: a 22 series 35 mm rail (EN 50022) mount relay with 1 NO (SPST-NO) - 20 A contacts, with coil rated at 24 V DC, contact material AgSnO2.
Contact material
0 = AgNi standard
4 = AgSnO2
Coil voltage
see coil specifications
Coil version
8 = AC (50/60 Hz)
9 = DC
Series
Type
2 = 35 mm rail (EN 50022) mount
No. of poles
1 = 1 NO (SPST-NO)
2 = 2 NO (DPST-NO)
3 = 1 NO (SPST-NO) +1 NC (SPST-NC)
4 = 2 NC (DPST-NC)
2 1 09 0 0
... .
02422
NOMINAL RATE LAMPS
-
incandescence (230V) W
1,000
- compensated fluorescent (230V) W
360
CONTACT SPECIFICATIONS