MAG-GARD(R) Motor Circuit Protectors, Molded Case Switches and POWERPACT(R) Electronic Trip Circuit Breakers Class 612 MAG-GARD(R)--Motor Circuit Protector k o t y t d i l e i nc b a u l i a no v A An be Motor Circuit Protector 600-1200 A 600 Vac 50/60 Hz Ampere Rating 600 800 1000 1200 3-Pole only Adjustable Trip Range Amperes Catalog Number Price Terminal Wire Range 2500-5000 4000-8000 PJL36060M67 PJL36080M68 $4800. 6303. 3-3/0 thru 500 kcmil Al/Cu 4500-9000 4000-8000 PJL36100M69 PJL36120M70 8067. 10487. 4-3/0 thru 500 kcmil Al/Cu Catalog Number Price Catalog Number Price 240 Vac 480 Vac 600 Vac ACc 600 800 PJL26000S60 PJL26000S80 $ 3390. 3804. PJL36000S60 PJL36000S80 $ 4180. 4594. 100 100 65 65 25 25 7200 9600 3-3/0 thru 500 kcmil Al/Cu 1000 1200 PJL26000S10 PLL26000S12 4742. 6912. PJL36000S10 PLL36000S12 5896. 7981. 100 125 65 100 25 50 12000 14400 4-3/0 thru 500 kcmil Al/Cu 2000 2500 RLF26000S20 RLF26000S25 10055. 15990. RLF36000S20 RLF36000S25 12418. 19765. 125 125 100 100 50 50 24000 30000 Order RLTB See Page 6-40 2-Pole 3-Pole Withstand Ratinga a The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit breaker with an equal continuous current rating. c UL magnetic trip setting tolerances are -20% and +30% from the nominal values shown. k Additional MAG-GARD motor circuit protectors are listed on Page 6-27. e Additional automatic switches are listed on Page 6-27. MICROLOGIC(R) Electronic Trip Units for Field Upgrade MICROLOGIC Electronic Trip Units may be purchased as separate components for field installation and upgradeability of POWERPACT(R) Unit Mount circuit breakers. Please specify the following catalog numbers to purchase these MICROLOGIC trip units as field installable components. Catalog Number Price Long-time and Instantaneous (MICROLOGIC 3.0) S131A $ 1667. Long-time, Short-time, and Instantaneous (MICROLOGIC 5.0) S133A 2386. Long-time and Instantaneous (MICROLOGIC 3.0A) S141A 2602. Long-time, Short-time, and Instantaneous (MICROLOGIC 5.0A) S143A 3320. Long-time, Short-time, Instantaneous, and Ground-fault Trip (MICROLOGIC 6.0A) S144A 4237. Long-time, Short-time, and Instantaneous (MICROLOGIC 5.0P) S163A 6391. Long-time, Short-time, Instantaneous, and Ground Fault Trip (MICROLOGIC 6.0P) S164A 7307. Description Standard Trip Unit Ammeter Trip Unit Power Trip Unit Harmonic Trip Unit o t y t d i l e i nc b a u l i o a n Av An be Long-time, Short-time, and Instantaneous (MICROLOGIC 5.0H) S173A 9847. Long-time, Short-time, Instantaneous, and Ground Fault Trip (MICROLOGIC 6.0H) S174A 10763. The standard rating plug supplied with a trip unit will be the "A" rating plug. To specify an alternative adjustable rating plug, please replace the letter designation at the end of the catalog number. Please refer to Page 6-18 for a complete listing of adjustable settings available with each plug. (Example: S143B would specify a "B" rating plug, instead of the standard "A" plug.) Trip Unit Options for MICROLOGIC To order, include the following suffix at the end of the trip unit catalog number. Description Calibration Calibrated Trip System (Trip Unit and Current Sensors) Catalog Suffix Price S $2519. Communications MODBUS(R) Protocol for MICROLOGIC Power and Harmonic Trip Unit MODBUS Protocol for MICROLOGIC Ammeter Trip Unit standard N/C E1 1129. MAG-GARD, MICROLOGIC, MODBUS and POWERPACT are Registered Trademarks of Square D Company or related companies. 3/00 DE2 Discount Schedule (c) 2000 Square D All Rights Reserved 6-17 6 Trip Point Amperes Terminal Wire Range Ampere Rating CIRCUIT BREAKERS POWERPACT(R) Automatic Molded Case Switches e --600 Vac 50/60 Hz