YOKOGAWA POWER TRANSDUCER CATALOG YOKOGAWA POWER TRANSDUCERS PRODUCT OVERVIEW Yokogawa's JUXTA "AC POWER SERIES" transducers (2469 & 2489) are rugged metal case designs for utility and industrial applications. Most models are UL recognized under File E60579 and exceed IEEE472/ANSI C37.90.1 Surge Withstand Capability test. The "SWC" test assures maximum protection from damaging line transients caused by switchgear operation or lightning strikes upstream on the system. Typically, power transducers provide a reliable and accurate analog DC output proportional to the AC input from the secondary of potential and / or current transformers in switchgear or control enclosures. The output is usually linked to remote monitoring equipment such as meters, recorders, PLC's, SCADA systems, Energy Management Systems, etc. Usually, 0.5% accuracy is adequate for most industrial monitoring needs. Our 2469 meets this requirement. Most power utility applications, however, require a higher level of accuracy. Our 2489 series, with 0.2% accuracy, is recommended for such applications. The plastic case power transducers (2370 & 2460 series) offer versatility and compactness when panel space is tight. The 2460 series can be mounted on a DIN rail, along with relays and terminal blocks, to maximize space and provide the ultimate in flexibility to the panel designer. The 2370 series has the same height and width as the DIN rail mount, but has two mounting feet which only require two drill holes and half the space of most metal case transducers. Both of these models offer 0.5% accuracy and come in one uniform case size from AC Amps to 3P4W Watts or Vars. Both of these products evolved from Yokogawa's original 2280 series Power Line Transducer design which is broadly accepted throughout the world. For information on the 2281 through 2289 models, please request bulletin 2280-E from Yokogawa on our reply card inserted in the catalog. Yokogawa offers a complete line of transducers for expansion, retrofit or upgrade of your power system. We hope the specification data and associated information in this catalog will provide all that is needed to make our transducers your choice for reliable power monitoring in your plant or equipment design. TABLE OF CONTENTS JUXTA METAL CASE TRANSDUCERS - 0.2% AND 0.5% ACCURACY AC CURRENT TRANSDUCERS (true RMS and Average sensing) . . . . . . . . . . . . . . . .PAGE 2 AC VOLTAGE TRANSDUCERS (true RMS and Average sensing) . . . . . . . . . . . . . . . .PAGE 4 DC TO DC ISOLATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 6 AC WATT TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 8 AC VAR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 10 COMBINATION WATT / VAR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 12 POWER FACTOR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 14 PHASE ANGLE TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 16 FREQUENCY TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 18 JUXTA 2489 SERIES ACCURACY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 20 SELECTING A WATT OR VAR TRANSDUCER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 21 TRANSDUCER TERMINOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 22 PLASTIC CASE MINIATURE TRANSDUCERS - 0.5% ACCURACY 2371-2378 FOOT MOUNT / 2461-2468 DIN RAIL MOUNT . . . . . . . . . . . . . . . . . . .PAGE 24 JUXTA AC CURRENT TRANSDUCERS 1) GENERAL The 2469 and 2489 AC Average Current transducers produce an analog DC signal output corresponding to the average value of the AC input. The true RMS versions always require external power and produce an analog DC output corresponding to the true RMS value of the input signal. 2) SPECIFICATIONS Model # Input Current Input over range capability Input Burden Rated outputs Accuracy 10-100% of rated input External calibration adjustment Response time Output ripple Isolation Surge Withstand Capability Insulation resistance Operating temperature Operating humidity Temperature effect External magnetic field Input frequency range Influence of frequency Weight Shock Vibration UL Recognition 3) STANDARD MODELS 0-5 Amp AC, 60 HZ input AVG./0-1 mA output / self powered TRMS / 0-1mA output / 120V aux. power AVG./4-20mA output / 120V aux. power TRMS / 4-20mA / 120V aux. power 3 in 1 / 0-1mA output / self-powered 2469 2489 0-1 Amp AC or 0-5 Amp AC 200% of rated input continuous 1000% of rated input for 5 seconds <0.2VA per element 0-1mADC into 10 k max. load; 10VDC output compliance 4-20 mADC into 750 max. load; 15VDC output compliance 0-1mADC=0.5% of full scale 0-1mADC=0.2% of full scale 4-20mADC=0.5% of span 4-20mADC=0.2% of span Zero: 1% minimum(AHD only) Zero: 5% minimum(AHD only) Span: 2% minimum Span: 10% minimum <400 milliseconds(0-99% of output) 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. 2500 VAC input to output, power and case 2000 VAC aux. power to output and case (AHD and TRMS) 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV, 1.2 x 50 microseconds) >10 megohm / 500VDC input/output/power/case -20C to +60C 0 - 90% relative humidity (non-condensing) 250 PPM / C of span 140 PPM / C of span < 0.2% at 400 AT/m 50 - 500 Hz < 0.2% effect on accuracy < 0.2%, 45-65 Hz, fundamental through 9th harmonic (TRMS models only) TRMS = 900g, 0-1mA = 358g, 4-20mA = 897g, 3 in 1 = 1100g < 0.2% after 50G, 3 Axis and 6 repetitions < 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis File # E60579 2469 (0.5% Accuracy) 2489 (0.2% Accuracy) 246921-380-AFA-0 246931-380-AFA-1 246921-380-AHD-1 246931-380-AHD-1 246923-380-AFA-0 248921-380-AFA-0 248931-380-AFA-1 248921-380-AHD-1 248931-380-AHD-1 248923-380-AFA-0 NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 2 JUXTA AC CURRENT (1) (2) (3) (4) (5) 4) ORDER FORMAT 2469 / 89 Model# 2469 2489 - (1) Transducer function 21 Average current 23 3 in 1 Avg. current 31 True RMS current - TRANSDUCERS (3) Input frequency 0 60 Hz 1 50 Hz 2 50/60 Hz 4 400 Hz 5 Other (2) Input 37 0-1 Amp AC 38 0-5 Amp AC (4) Output (5) Aux. power 0 Input AFA 0-1 mADC powered (21 & 23 only) AFA 0-1 mADC (TRMS only) AHD 4-20 mADC (21 & 31 only) 1 85-135 VAC 2 170-264 VAC 5) CONNECTION DIAGRAMS FOR CT INPUT LINE L1 L2 DC OUTPUT + DC OUTPUT + - LINE L1 L2 - - + LINE L1L2 L3 AUX POWER + - DC OUTPUT + 1 2 3 4 - 1 2 3 4 5 6 + LOAD 2 3 4 1 2 3 4 1 2 3 4 DC OUTPUT LOAD LOAD 246921 248921 246921 248921 246931 248931 246923 248923 AUXILIARY POWERED (mm) inches 6) MOUNTING AND OUTLINE DIMENSIONS: 3 IN 1 CURRENT (111.6) 4.394 SELF POWERED (77.15) 3.037 1 DC OUTPUT 4.394 (120.65) 4.750 (133) 5.236 (111.6) (38.1) 1.5 (78) 3.071 (95.72) 3.769 (38.1) 1.500 + (50) + + + + + 1.969 + + + + + 2.012 + + + + + + + (51.11) + + + + + + + + (95.72) 3.769 (78) 3.071 (38.1) 1.5 (120.65) 4.750 (133) 5.236 (10.1) 3.976 + (88.9) 3.500 (14.7) .579 (105.1) 4.138 3.517 (89.33) (104.03) 4.096 (119.8) 4.717 246921 248921 246931 248931 AUXILIARY POWERED 3 .579 (105.1) 4.138 SELF POWERED (14.7) (14.7) .579 (119.8) 4.717 246921 248921 246923 248923 3 IN 1 CURRENT JUXTA AC V O LTA G E TRANSDUCERS 1) GENERAL The 2469 and 2489 AC Average Voltage transducers produce an analog DC signal output corresponding to the average value of the AC input. The true RMS versions always require external power and produce an analog DC output corresponding to the true RMS value of the input signal. 2) SPECIFICATIONS Model # Input Voltage Input over range capability Input Burden (Averaging models) Input Burden (true RMS models) Rated outputs Accuracy 10-100% of rated input External calibration adjustment Response time Output ripple Isolation Surge Withstand Capability Insulation resistance Operating temperature Operating humidity Temperature drift External magnetic field Input frequency range Influence of frequency Weight Shock Vibration UL Recognition 3) STANDARD MODELS 0-150 VAC, 60 HZ input AVG./0-1 mA / self powered TRMS / 0-1mA / 120V aux. power AVG./4-20mA / 120V aux. power TRMS / 4-20mA / 120V aux. power 3 in 1 / 0-1mA output / self-powered 2469 2489 0-150 VAC or 0-300 VAC 120% of rated input continuous 150 VAC: <1.8VA / element; 300 VAC: <3.6VA / element 150 VAC: <0.8VA; 300 VAC: <1.6VA 0-1mADC into 10 kmax. load; 10VDC output compliance 4-20 mADC into 750 max. load; 15VDC output compliance 0-1mADC=0.5% of full scale 0-1mADC=0.2% of full scale 4-20mADC=0.5% of span 4-20mADC=0.2% of span Zero: 1% minimum(AHD only) Zero: 5% minimum(AHD only) Span: 2% minimum Span: 10% minimum <400 milliseconds(0-99% of output) 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. 2500 VAC input to output, power and case 2000 VAC aux. power to output and case(AHD + TRMS) 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV 1.2 x 50 microseconds) >10 megohm / 500VDC input/output/power/case -20C to +60C 0 - 90% relative humidity (non-condensing) 250 PPM / C of span 140 PPM / C of span < 0.2% at 400 AT/m 50 - 500 Hz < 0.2% effect on accuracy < 0.2%, 45-65 Hz, fundamental through 9th harmonic (TRMS models only) TRMS = 900g, 0-1mA = 358g, 4-20mA = 897g, 3 in 1 = 1100g < 0.2% after 50G, 3 Axis and 6 repetitions < 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3Axis File # E60579 2469 (0.5% Accuracy) 2489 (0.2% Accuracy) 246922-330-AFA-0 246932-330-AFA-1 246922-330-AHD-1 246932-330-AHD-1 246924-330-AFA-0 248922-330-AFA-0 248932-330-AFA-1 248922-330-AHD-1 248932-330-AHD-1 248924-330-AFA-0 NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 4 JUXTA DC TO DC ISOLATORS 1) GENERAL The 2469 series DC to DC isolator provides an isolated analog output proportional to the DC voltage or current input. Standard inputs are 50mVDC and 1 mADC. Auxiliary power is required to power the DC to DC isolator. Other DC inputs and power options are available on special order from Yokogawa. 2) SPECIFICATIONS Model # 2469 (0.5% accuracy) 0-50mVDC and 0-1mADC are standard Input signal ranges Varies with input current or voltage Input impedance < 1 mADC Input burden 10 VDC Output compliance 0.5% of full scale Accuracy 10-100% rated input Span adjustment 5% minimum Zero adjustment 5% minimum < 500 milliseconds (0-99% of output) Response time 2600 VAC input to output, power and case Isolation 1000 VAC aux. power to output and case 1000 VAC output to case IEEE472/ANSI C37.90.1-1989 SWC TEST Surge withstand capability 0 C to +40 C Operating temperature Operating humidity 20 - 90% relative humidity (non-condensing) 908g (2 lbs.) Weight 115V AC 10%, 5.0 VA Burden Auxiliary Power Supply 3) STANDARD MODELS Model # Description 246911-001-AFA-1 / DC Voltage input 246911-001-AHD-1 / DC Voltage input 246911-001-VMT-1 / DC Voltage input Input / Output Relationship 0-50mVDC / 0-1mADC 0-50mVDC / 4-20mADC 0-50mVDC / 0-10VDC 0-1mADC / 0-1mADC 0-1mADC / 4-20mADC 0-1mADC / 0-10VDC 246912-101-AFA-1 / DC Current input 246912-101-AHD-1 / DC Current input 246912-101-VMT-1 / DC Current input 6 JUXTA AC WATT TRANSDUCERS 1) GENERAL The 2469 and 2489 AC Watt transducers produce an analog output equal to the Watts measured by the input. The typical calibration is 500 Watts / element for 120V and 5A AC transformer secondary inputs. 2) SPECIFICATIONS 2469 2489 Model # 0-1 Amp AC or 0-5 Amp AC Current input / range 10 to 200% of rated input 0-200% of rated input 200% of rated input continuous Current input over range capability 1000% of rated input for 5 seconds < 0.2VA per element Current input burden 120V 240V 120V 240V Voltage inputs and range: 100-135VAC 200-264VAC 85-135VAC 170-264VAC Input powered range 0-120% rated input 0-120% of rated input Auxiliary powered range < 0.5VA < 1.0VA < 0.3VA < 0.6VA Voltage input burden per element 150% of rated input without damage (Auxiliary powered only) Sustained Voltage input overange 0 to 1mADC into 10k max. load; 10VDC output compliance Rated outputs 4-20 mADC into 750 max. load; 15VDC output compliance 0 1mADC = 0.5% of full scale 01mADC = 0.1% rdg. 0.05%FS Accuracy 4-20mADC = 0.5% of span 4-20mADC = 0.2% of span 120VAC: 1 Amp = 0-100 Watts; 5 Amp = 0-500 Watts Output calibration / element 240VAC: 1 Amp = 0-200 Watts; 5 Amp = 0-1000 Watts Zero: 1% minimum Zero: 5% minimum External calibration adjustment Span: 2% minimum Span: 10% minimum < 400 milliseconds (0-99% of output) Response time 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. Output ripple 2500 VAC input to output, power and case Isolation 2000 VAC aux. power to output and case 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) Surge Withstand Capability > 10 megohm / 500VDC input/output/power/case Insulation resistance -20C to +60C 1mA (-20to+70C), 4-20mA(-20to+60C) Operating temperature 0 - 90% relative humidity (non-condensing) Operating humidity 250 PPM / C of span 1mA 50FS, 4-20mA 75span (PPM/C) Temperature effect < 0.2% at 400 AT/m External magnetic field <0.5% <0.2% Influence : unbalanced currents / phase interaction / Power Factor <0.25%, 45-65 Hz, fundamental through 9th harmonic Influence of frequency 1200g (2.65 lbs.) Weight <0.2% after 50G, 3 Axis and 6 repetitions Shock <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis Vibration File # E60579 UL Recognition 3) STANDARD MODELS 120 VAC, 5AAC, 60 Hz, input powered Watt 1P2W, 0-1mA output (1 Element) Watt 1P2W, 4-20mA output (1 Element) Watt 3P3W, 0-1mA output (2 Element) Watt 3P3W, 4-20mA output (2 Element) Watt 3P4W, 0-1mA output (212 Element) Watt 3P4W, 4-20mA output (212 Element) Watt 3P4W, 0-1mA output (3 Element) Watt 3P4W, 4-20mA output (3 Element) 2469 (0.5% Accuracy) 246951-540-AFA-0 246951-540-AHD-0 246953-540-AFA-0 246953-540-AHD-0 246954-540-AFA-0 246954-540-AHD-0 246955-540-AFA-0 246955-540-AHD-0 2489 (0.2% Accuracy) 248951-540-AFA-0 248951-540-AHD-0 248953-540-AFA-0 248953-540-AHD-0 248954-540-AFA-0 248954-540-AHD-0 248955-540-AFA-0 248955-540-AHD-0 NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 8 JUXTA AC VAR TRANSDUCERS 1) GENERAL The 2469 and 2489 AC VAR transducers produce an analog output equal to the VARS measured by the input. The typical calibration is 500 VARS / element for 120V and 5A AC transformer secondary inputs. 2) SPECIFICATIONS Model # 2469 2489 Current input / range 0-1 Amp AC or 0-5 Amp AC 10 to 200% of rated input 0-200% of rated input Current input over range capability 200% of rated input continuous 1000% of rated input for 5 seconds Current input burden < 0.2VA per element Voltage inputs and range: 120V 240V 120V 240V Input powered range 100-135VAC 200-264VAC 85-135VAC 170-264VAC Auxiliary powered range 0-120% rated input 0-120% of rated input Voltage input burden per element < 0.5VA < 1.0VA < 0.3VA < 0.6VA Sustained Voltage input overange 150% of rated input without damage (Auxiliary powered only) Rated outputs 0 to 1mADC into a 10k max. load; 10VDC output compliance 128mADC into a 750 max. load; 15VDC output compliance Accuracy 0 1mADC = 0.5% of full scale 01mADC = 0.1% rdg. 0.1%FS 128mADC = 0.5% of span 128mADC = 0.2% of span Output calibration / element 120VAC: 1 Amp = 0-100 VARS; 5 Amp = 0-500 VARS 240VAC: 1 Amp = 0-200 VARS; 5 Amp = 0-1000 VARS External calibration adjustment Zero: 1% minimum Zero: 5% minimum Span: 2% minimum Span: 10% minimum Response time < 400 milliseconds (0-99% of output) Output ripple 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. Isolation 2500 VAC input to output, power and case 2000 VAC aux. power to output and case 500 VAC output to case Surge Withstand Capability IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) Insulation resistance > 10 megohm / 500VDC input/output/power/case Operating temperature -20C to +60C Operating humidity 0 - 90% relative humidity (non-condensing) Temperature effect 250 PPM / C of span 1mA 50FS, 4-20mA 80span (PPM/C) External magnetic field < 0.2% at 400 AT/m Influence : unbalanced currents / <0.5% <0.2% phase interaction / Power Factor Weight 1200g (2.65 lbs.) Shock <0.2% after 50G, 3 Axis and 6 repetitions Vibration <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis UL Recognition File # E60579 3) STANDARD MODELS 120 VAC, 5AAC, 60 Hz, input powered VAR 1P2W, 1mA output (1 Element) VAR 1P2W, 128mA output (1 Element) VAR 3P3W, 1mA output (2 Element) VAR 3P3W, 128mA output (2 Element) VAR 3P4W, 1mA output (212 Element) VAR 3P4W, 128mA output (212 Element) VAR 3P4W, 1mA output (3 Element) VAR 3P4W, 128mA output (3 Element) 2469 (0.5% Accuracy) 246961-540-AFB-0-M 246961-540-AHF-0-M 246963-540-AFB-0-M 246963-540-AHF-0-M 246964-540-AFB-0-M 246964-540-AHF-0-M 246965-540-AFB-0-M 246965-540-AHF-0-M 2489 (0.2% Accuracy) 248961-540-AFB-0-M 248961-540-AHF-0-M 248963-540-AFB-0-M 248963-540-AHF-0-M 248964-540-AFB-0-M 248964-540-AHF-0-M 248965-540-AFB-0-M 248965-540-AHF-0-M NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 10 JUXTA COMBINATION WATT/VAR TRANSDUCERS 1) GENERAL The 2469 and 2489 combined WATT/VAR transducers produce an analog output equal to the WATTS and VARS measured by the input. 2) SPECIFICATIONS Model # 2469 2489 Current input / range 0-1 Amp AC or 0-5 Amp AC 10 to 200% of rated input 0-200% of rated input Current input over range capability 200% of rated input continuous 1000% of rated input for 5 seconds Current input burden < 0.2VA per element Voltage inputs and range: 120V 240V 120V 240V Input powered range 100-135VAC 200-264VAC 85-135VAC 170-264VAC Auxiliary powered range 0-120% rated input 0-120% of rated input Voltage input burden per element < 0.5VA < 1.0VA < 0.3VA < 0.6VA Sustained Voltage input overange 150% of rated input without damage (Auxiliary powered only) Rated outputs 0 to 1mADC into a 10k max. load; 10VDC output compliance 4-20 mADC into 750 max. load; 15VDC output compliance Accuracy: 0 1mA output Watts 0.5% of full scale 0.1% of reading. 0.05% full scale 0 1mA output VARS 0.5% of full scale 0.1% of reading. 0.1% full scale 4-20mA output 0.5% of span 0.2% of span External calibration adjustment Zero: 1% minimum Zero: 5% minimum Span: 2% minimum Span: 10% minimum Response time < 400 milliseconds (0-99% of output) Output ripple 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. Isolation 2500 VAC input to output, power and case (Watt & VAR outputs are not isolated 2000 VAC aux. power to output and case from each other) 500 VAC output to case Surge Withstand Capability IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) Insulation resistance > 10 megohm / 500VDC input/output/power/case Operating temperature -20C to +60C Operating humidity 0 - 90% relative humidity (non-condensing) Temperature effect 250 PPM / C of span 1mA = W 50FS, V 75span (PPM/C) External magnetic field < 0.2% at 400 AT/m Influence : unbalanced currents / <0.5% <0.2% phase interaction / Power Factor Influence of frequency <0.25%, 45-65 Hz, fundamental through 9th harmonic (Watt only) Weight 1200g (2.65 lbs.) Shock <0.2% after 50G, 3 Axis and 6 repetitions Vibration <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis UL Recognition File # E60579 3) STANDARD MODELS 120 VAC, 5AAC, 60 Hz, input powered W/V 1P2W, 01mA output (1 Element) W/V 1P2W, 4-20mA output (1 Element)* W/V 3P3W, 01mA output (2 Element) W/V 3P3W, 4-20mA output (2 Element)* W/V 3P4W, 01mA output (212 Element) W/V 3P4W, 4-20mA output (212 Element)* W/V 3P4W, 01mA output (3 Element) W/V 3P4W, 4-20mA output (3 Element)* 2469 (0.5% Accuracy) 246941-540-AFB-0-M 246941-540-AHD-0-M 246943-540-AFB-0-M 246943-540-AHD-0-M 246944-540-AFB-0-M 246944-540-AHD-0-M 246945-540-AFB-0-M 246945-540-AHD-0-M 2489 (0.2% Accuracy) 248941-540-AFB-0-M 248941-540-AHD-0-M 248943-540-AFB-0-M 248943-540-AHD-0-M 248944-540-AFB-0-M 248944-540-AHD-0-M 248945-540-AFB-0-M 248945-540-AHD-0-M NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. *VAR outputs for "AHD" are 128 mADC (see output options on next page). Auxiliary power supply options <5.0 burden. 12 JUXTA POWER FACTOR TRANSDUCERS 1) GENERAL The 2469 and 2489 Power Factor transducers have an analog output corresponding to 1- Cosine of the phase angle of the input current relative to the input voltage signal. The analog output will indicate leading or lagging Power Factor by its direction from center which would be either 0 mA or 12mA based on output selection. 2) SPECIFICATIONS Model # Current input / range Current input over range capability Current input burden Voltage inputs and range: Input powered range Auxiliary powered range Voltage input burden per element Sustained Voltage input overange Rated outputs Accuracy Output calibration External calibration adjustment Response time Output ripple Isolation Surge Withstand Capability Insulation resistance Operating temperature Operating humidity Temperature effect External magnetic field Influence of input Voltage Influence of input Current Low current detection Weight Shock Vibration UL Recognition 3) STANDARD MODELS (0-1-0 PF) 120 VAC, 5AAC, 60 Hz, input powered PF- Single phase / 1mA output PF- Single phase / 128mA output PF- 3P3W balanced / 1mA output PF- 3P3W balanced / 128mA output PF- 3P4W balanced / 1mA output PF- 3P4W balanced / 128mA output 2469 2489 0-1 Amp AC or 0-5 Amp AC 10 to 200% of rated input 200% of rated input continuous 1000% of rated input for 5 seconds < 0.2VA per element 120V 240V 120V 240V 100-135VAC 200-264VAC 85-135VAC 170-264VAC 0-120% rated input 0-120% of rated input < 0.5VA < 1.0VA < 0.5VA < 1.0VA 150% of rated input without damage (Auxiliary powered only) 1mADC into a 10k max. load; 10VDC output compliance 4-12-20 mADC into a 750 max. load; 15VDC output compliance 0.01 Power Factor 0-1-0 Power Factor or 0.5-1-0.5 Power Factor Zero: 1% minimum Zero: 5% minimum Span: 2% minimum Span: 10% minimum < 400 milliseconds (0-99% of output) 0.3% of FS peak-to-peak max. 0.5% of FS peak-to-peak max. 2500 VAC input to output, power and case 2000 VAC aux. power to output and case 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) > 10 megohm / 500VDC input/output/power/case -20C to +60C 0 - 90% relative humidity (non-condensing) 500 PPM / C of span 150 PPM / C of span < 0.2% at 400 AT/m <1% of span Aux. Pwr.0.01 max.20% rated V. Self pwr.0.01 max. in range of Aux. Pwr <2% of span <0.02 PF for 20-200% rated input current <4% of rated current 4% of rated input 1000g (2.2 lbs.) <0.2% after 50G, 3 Axis and 6 repetitions <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis File # E60579 2469 246971-540-AFB-0-P 246971-540-AHF-0-P 246973-540-AFB-0-P 246973-540-AHF-0-P 246974-540-AFB-0-P 246974-540-AHF-0-P 2489 248971-540-AFB-0-P 248971-540-AHF-0-P 248973-540-AFB-0-P 248973-540-AHF-0-P 248974-540-AFB-0-P 248974-540-AHF-0-P NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 14 JUXTA PHASE ANGLE TRANSDUCERS 1) GENERAL The 2469 and 2489 Phase Angle transducers have an analog output corresponding to the phase angle of the input current relative to the input voltage signal. The analog output will indicate leading or lagging Phase Angle by its direction from center which would be either 0 mA or 12mA based on output selection. 2) SPECIFICATIONS Model # Current input / range Current input over range capability Current input burden Voltage inputs and range: Input powered range Auxiliary powered range Voltage input burden per element Sustained Voltage input overange Rated outputs Accuracy Output calibration External calibration adjustment Response time Output ripple Isolation Surge Withstand Capability Insulation resistance Operating temperature Operating humidity Temperature effect External magnetic field Influence of frequency Influence of input Voltage Influence of input Current Low current detection Weight Shock Vibration UL Recognition 3) STANDARD MODELS (90 PA) 120V, 5A, 60 Hz, 90, input powered PA- Single phase / 1mA output PA- Single phase / 128mA output PA- 3P3W balanced / 1mA output PA- 3P3W balanced / 128mA output PA- 3P4W balanced / 1mA output PA- 3P4W balanced / 128mA output 2469 2489 0-1 Amp AC or 0-5 Amp AC 10 to 200% of rated input 200% of rated input continuous 1000% of rated input for 5 seconds < 0.2VA per element 120V 240V 120V 240V 100-135VAC 200-264VAC 85-135VAC 170-264VAC 0-120% rated input 0-120% of rated input < 0.5VA < 1.0VA < 0.5VA < 1.0VA 150% of rated input without damage (Auxiliary powered only) 1mADC into a 10k max. load; 10VDC output compliance 4-12-20 mADC into a 750 max. load; 15VDC output compliance 2 Phase Angle 1 Phase Angle 60- 0- 60 Phase Angle or 90- 0- 90 Phase Angle Zero: 1% minimum Zero: 5% minimum Span: 2% minimum Span: 10% minimum < 400 milliseconds (0-99% of output) 0.3% of FS peak-to-peak max. 0.5% of FS peak-to-peak max. 2500 VAC input to output, power and case 2000 VAC aux. power to output and case 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) > 10 megohm / 500VDC input/output/power/case -20C to +60C 0 - 90% relative humidity (non-condensing) 500 PPM / C of span 80 PPM / C of span < 0.2% at 400 AT/m <0.2%, 45 - 65 Hz, fundamental through 9th harmonic <0.5 <0.5 20% rated Voltage input (aux.pwr.) <0.5 in range af aux. pwr. (int. pwr. model) <1.0 <1 for 20-200% rated input current N/A 4% of rated input 1000g (2.2 lbs.) <1 after 50G, 3 Axis and 6 repetitions <1 after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis File # E60579 2469 (2 Accuracy) 246976-540-AFB-0-P 246976-540-AHF-0-P 246977-540-AFB-0-P 246977-540-AHF-0-P 246978-540-AFB-0-P 246978-540-AHF-0-P 2489 (1 Accuracy) 248976-540-AFB-0-P 248976-540-AHF-0-P 248977-540-AFB-0-P 248977-540-AHF-0-P 248978-540-AFB-0-P 248978-540-AHF-0-P NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 16 JUXTA FREQUENCY TRANSDUCERS 1) GENERAL The 2469 and 2489 Frequency transducers have an analog output corresponding to the frequency of the AC input voltage. These transducers are capable of high accuracy measurement over various frequency ranges. 2) SPECIFICATIONS Model # Voltage inputs and range: Input powered range Auxiliary powered range Voltage input burden Rated outputs Accuracy: 2, 5, 10, 25 Hz deviation 0.5, 1 Hz deviation External calibration adjustment Response time Output ripple Isolation Surge Withstand Capability Insulation resistance Operating temperature Operating humidity Temp. effect: 2, 5, 10, 25 Hz deviation 0.5, 1 Hz deviation External magnetic field Harmonics Weight Shock Vibration UL Recognition 3) STANDARD MODELS 120VAC, 60 Hz, input powered Freq. 1.0 Hz deviation, 0-1mA output Freq. 1.0 Hz deviation, 4-20mA output Freq. 2.0 Hz deviation, 0-1mA output Freq. 2.0 Hz deviation, 4-20mA output Freq. 5.0 Hz deviation, 0-1mA output Freq. 5.0 Hz deviation, 4-20mA output 2469 2489 120V: 100 - 135 VAC, 240V: 200 - 264 VAC 20% of rated voltage 120VAC <0.1 VA; 240VAC <0.2 VA 1mADC into a 10kmax. load; 10VDC output compliance 4-12-20 mADC into 750 max. load; 15VDC output compliance 1% of input span 0-1mADC=0.1% of input span 2% of input span 0-1mADC=0.2% of input span 4-20mADC=add0.1% to accuracy Zero: 1% minimum Zero: 5% minimum Span: 2% minimum Span: 10% minimum <400 milliseconds (0-99% of output) 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max. 2500 VAC input to output, power and case 2000 VAC aux. power to output and case 500 VAC output to case IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV 1.2 x 50 microseconds) >10 megohm / 500VDC input/output/power/case -20C to +60C 0 - 90% relative humidity (non-condensing) 250 PPM / C of span 25ppm of center frequency(60Hz5Hz) 500 PPM / C of span 5ppm of center frequency(60Hz0.5Hz) For 4-20mADC multiply ppm x 1.4 < 0.2% at 400 AT/m Fundamental through 9th harmonic 1000g (2.2 lbs.) < 0.2% after 50G, 3 Axis and 6 repetitions < 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3Axis File # E60579 2469 246982-320-AFA-0 246982-320-AHD-0 246983-320-AFA-0 246983-320-AHD-0 246984-320-AFA-0 246984-320-AHD-0 2489 248982-320-AFA-0 248982-320-AHD-0 248983-320-AFA-0 248983-320-AHD-0 248984-320-AFA-0 248984-320-AHD-0 NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options. Auxiliary power supply options <5.0 VA burden. 18 JUXTA (1) 4) ORDER FORMAT 2469 / 89 Model# 2469 2489 FREQUENCY (2) (3) - (4) - TRANSDUCERS (5) - (1) Transducer function 81 0.5 Hz deviation 82 1 Hz deviation 83 2 Hz deviation 84 5 Hz deviation (2) Input 32 120 VAC 35 240 VAC 84 5 Hz deviation 32 120 VAC 35 240 VAC 1 50 Hz 85 10 Hz deviation 32 120 VAC 35 240 VAC 3 55 Hz 86 25 Hz deviation 32 120 VAC 35 240 VAC 4 400 Hz (3) Input frequency (4) Output 0 60 Hz AFA 0-1 mADC AFB 0 to 1mADC AHD 4-20 mADC 5) CONNECTION DIAGRAMS DC OUTPUT - LINE L1 L2 - + + AUX (OPTIONAL) POWER 1 2 3 4 5 6 LOAD 6) MOUNTING AND OUTLINE DIMENSIONS: (111.6) 4.394 (mm) inches (14.7) .579 (105.1) 4.138 (119.8) 4.717 (38.1) 1.5 (78) 3.071 (95.72) 3.769 + + + + + + + + (120.65) 4.750 (133) 5.236 19 (5) Aux. power 0 Input pwr'd 1 120 VAC 2 240 VAC YOKOGAWA TRANSDUCERS 1) GENERAL The 2371-2378 and 2461-2468 series of power transducers combine high performance with compact size. Most of these transducers are self powered except DC to DC isolators and True RMS Amps and Volts which require auxiliary power. Accuracy of 0.5% is standard in both the foot mount and DIN rail models. They are constructed of flame resistant molded black ABS resin material; and operating temperature is 0-40C (20-80% RH, non-condensing). Storage temperature is -10 to +50C. Weight <.5Kg (1.1lbs.) 2461-2468 DIN rail mount 2371-2378 foot mount 2) SPECIFICATIONS Transducer function Model# code DC / DC Isolator (Photocoupler isolation) 2371 00 or 2461 AC Voltage/Current (Mean value rect.) AC Voltage/Current (RMS value rect.) AC Voltage/Current (True RMS rect.) 2372 00 2462 2373 00 2463 2374 00 or 2464 10 2375 20 2465 30 40 10 2376 20 2466 30 40 10 2377 20 2467 30 40 01 1P2W 1P3W 3P3W 3P4W Reactive 1P2W Power 1P3W (VARS) 3P3W 3P4W 1P2W Phase 1P3W Angle 3P3W 3P4W Power (Watts) Frequency 2378 02 2468 03 Rated inputs *Rated outputs/external load resistance 0 - 50 mVDC 0 - 1mADC / 10k 0 - 5 VDC 0 - 5mADC / 2k 0 - 10VDC 4 - 20mADC / 500 0 - 25VDC 0 - 10mVDC / 10k 0 - 65VDC 0 - 5VDC / 1k 0 - 1mADC 0 - 10VDC / 2k 0 - 1mADC / 10k 1 AAC 0 - 5mADC / 2k 5 AAC 0 - 5VDC / 5k 150 VAC 0 - 1mADC / 2k 300 VAC 0 - 10VDC / 2k 0 - 1mADC / 10k 4 - 20mADC / 500 120V / 1 AAC 0 - 10VDC / 2k 120V / 5 AAC 0 - 1mADC / 10k 240V / 1 AAC 0 - 5mADC / 2k 240V / 5 AAC 4 - 20mADC / 500 120V / 1 AAC 10 VDC / 2k 120V / 5AAC 1mADC / 10k 240V / 1AAC 5mADC / 2k 240V / 5AAC 4 - 20mADC / 500 120V / 1AAC 10 VDC / 2k 120V / 5AAC 1mADC / 10k 240V / 1AAC 5mADC / 2k 240V / 5AAC 4 - 20mADC / 500 120V/45-55Hz 240V/45-55Hz 0 - 10VDC / 2k 120V/55-65Hz 0 - 1mADC / 10k 240V/55-65Hz 0 - 5mADC / 2k 120V/45-65Hz 4 - 20mADC / 500 240V/45-65Hz Accuracy Output Response Frequency Power Auxiliary @233C ripple time range consump. power 0.5%of span N/A 0.5 sec. DC 1 second 45-65 Hz ~1mA + aux. pwr. 120VAC 1.9VA 10% 1 VA not req'd 0.5% of 1% p-p span max. 0.5 sec. 0.5% of span 0.7 sec. 1% p-p max. 2 0.5 VA+ 120VAC 45-10kHz Aux. pwr. 10% 2 VA V = 3VA A = 1VA 45-65 Hz 0.5 sec. not req'd V = 2.5VA A = 0.1VA 45-55 Hz 0.1 Hz .1%p-p 2 seconds max. 0.2Hz 55-65 Hz 1.5VA not req'd 45-65 Hz *See next page for additional outputs. 24 PLASTIC CASE MINIATURE TRANSDUCERS 3) GENERAL SPECIFICATIONS Overrange capability Current input: 1000% of rated input for 5 sec. Voltage input: 150% of rated input for 5 sec. Dielectric strength between: Insulation resistance between: 1) Input terminals & case - 2600VAC for 1 minute 1) All terminals and ground terminal 2) Input & output terminals - 2600VAC for 1 minute 2) Input/output/ground term./auxiliary pwr. 3) Aux. pwr. term. & input term./case-2600VAC for 1 min. ----------------------------------------------4) Output terminals and case - 1000VAC for 1 minute Is greater than 100 Megohm at 500VDC 4) STANDARD MODELS (AC AMPS, VOLTS, WATTS, VARS, PHASE ANGLE) Input Output 5A AC (AVG) 5A AC (TRMS) 1mA 1mA 4-20mA 150V AC (AVG) 1mA 150V AC (TRMS) 1mA 4-20mA Watt 3P3W 1mA (120V, 5A) 4-20mA DIN Rail 246300-36-AFA 246400-36-AFA-2 246400-36-AHE-2 246300-32-AFA 246400-32-AFA-2 246400-32-AHE-2 246530-46-AFA-N 246530-46-AHE-N (1) 5) ORDER FORMAT: 237 OR: 246 Foot Mount Input Output DIN Rail Foot Mount 237300-36-AFA 237400-36-AFA-2 237400-36-AHE-2 237300-32-AFA 237400-32-AFA-2 237400-32-AHE-2 237530-46-AFA-N 237530-46-AHE-N Watt 3P4W (120V, 5A) VAR 3P3W (120V, 5A) VAR 3P4W (120V, 5A) PA 3P3W (120V, 5A) 1mA 4-20mA 1mA 4-20mA 1mA 4-20mA 1mA 4-20mA 246540-46-AFA-N 246540-46-AHE-N 246630-46-AFB-M 246630-46-AHE-M 246640-46-AFB-M 246640-46-AHE-M 246730-46-AFB-P 246730-46-AHE-P 237540-46-AFA-N 237540-46-AHE-N 237630-46-AFB-M 237630-46-AHE-M 237640-46-AFB-M 237640-46-AHE-M 237730-46-AFB-P 237730-46-AHE-P (2) - 237 = Foot mount 246 = DIN rail (1) Transducer function 100 DC / DC isolator 200 300 400 5XX* 6XX* 7XX* 8XX* AC Amp or Volt (Mean value) AC Amp or Volt (RMS value) AC Amp or Volt (True RMS) xx*(select one) Watt 10 1P2W VAR 20 1P3W Phase Angle 30 3P3W 40 3P4W xx*(select one) Frequency 01 45-55 Hz 02 55-65 Hz 03 45-65 Hz (3) - (4) - (2) Rated inputs 01 DC 50mV 02 DC 1V 03 DC 5V 04 DC 10V 05 DC 25V 06 DC 65V 21 DC 1mA 32 34 35 36 AC 150V AC 300V AC 1A AC 5A 45 46 47 48 AC 120V / 1A AC 120V / 5A AC 240V / 1A AC 240V / 5A (3) **Rated outputs (4) Auxiliary power 2 120 VAC 50/60 Hz AFA 0-1mADC 4 240 VAC 50/60 Hz AFX 0-5mADC Only required for function AFB 1mADC 100 DC/DC & 400 TRMS AFZ 5mADC AHE 4 - 20mADC VGZ 0 - 10mVDC VLS 0 - 5VDC Polarity (Watt/VAR/PA only) VMT 0 - 10VDC N No polarity (Watt only) VHB 10mVDC P -Lag to +Lead VLU 5VDC M -Lead to +Lag VLY 6VDC VMS 10VDC VME 4.5-6.5VDC 37 AC 120V 38 AC 240V ** Outputs available by transducer function: CODE# AFA AFX AFB AFZ AHE VGZ VLS VMT VHB VLU VLY VMS VME FUNCTION OUTPUT 1mA 5mA 1mA 5mA 4-20mA 10mV 5V 10V 10mV 5V 6V 10V 4.5-6.5V 100 DC / DC isolator X X X X X X 200 AC Amp / Volt X X 300 AC Amp / Volt X X X 400 AC Amp / Volt X X X X X X 5XX Watt X X X X X X 6XX VAR X X X X X X 7XX Phase Angle X X X X X 801 / 802 Frequency X X X X X X 803 Frequency X X X X X X X 25