YOKO GAWA
POWER
TRANSDUCER
CATALOG
Yokogawa’s JUXTA “AC POWER SERIES” transducers (2469 & 2489) are rugged metal
case designs for utility and industrial applications. Most models are UL recognized under
File E60579 and exceed IEEE472/ANSI C37.90.1 Surge Withstand Capability test. The
“SWC” test assures maximum protection from damaging line transients caused by
switchgear operation or lightning strikes upstream on the system.
Typically, power transducers provide a reliable and accurate analog DC output propor-
tional to the AC input from the secondary of potential and / or current transformers in
switchgear or control enclosures. The output is usually linked to remote monitoring
equipment such as meters, recorders, PLC’s, SCADA systems, Energy Management
Systems, etc. Usually, 0.5% accuracy is adequate for most industrial monitoring needs.
Our 2469 meets this requirement. Most power utility applications, however, require a
higher level of accuracy. Our 2489 series, with 0.2% accuracy, is recommended for such
applications.
The plastic case power transducers (2370 & 2460 series) offer versatility and compact-
ness when panel space is tight. The 2460 series can be mounted on a DIN rail, along with
relays and terminal blocks, to maximize space and provide the ultimate in flexibility to
the panel designer. The 2370 series has the same height and width as the DIN rail mount,
but has two mounting feet which only require two drill holes and half the space of most
metal case transducers. Both of these models offer 0.5% accuracy and come in one uni-
form case size from AC Amps to 3P4W Watts or Vars.
Both of these products evolved from Yokogawa’s original 2280 series Power Line
Transducer design which is broadly accepted throughout the world. For information on
the 2281 through 2289 models, please request bulletin 2280-E from Yokogawa on our
reply card inserted in the catalog.
Yokogawa offers a complete line of transducers for expansion, retrofit or upgrade of
your power system. We hope the specification data and associated information in this
catalog will provide all that is needed to make our transducers your choice for reliable
power monitoring in your plant or equipment design.
JUXTA METAL CASE TRANSDUCERS - 0.2% AND 0.5% ACCURACY
AC CURRENT TRANSDUCERS (true RMS and Average sensing) . . . . . . . . . . . . . . . .PAGE 2
AC VOLTAGE TRANSDUCERS (true RMS and Average sensing) . . . . . . . . . . . . . . . .PAGE 4
DC TO DC ISOLATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 6
AC WATT TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 8
AC VAR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 10
COMBINATION WATT / VAR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 12
POWER FACTOR TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 14
PHASE ANGLE TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 16
FREQUENCY TRANSDUCERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 18
JUXTA 2489 SERIES ACCURACY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 20
SELECTING A WATT OR VAR TRANSDUCER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 21
TRANSDUCER TERMINOLOGY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE 22
PLASTIC CASE MINIATURE TRANSDUCERS - 0.5% ACCURACY
2371-2378 FOOT MOUNT / 2461-2468 DIN RAIL MOUNT . . . . . . . . . . . . . . . . . . .PAGE 24
TABLE OF CONTENTS
YOKOGAWA POWER TRANSDUCERS
PRODUCT OVERVIEW
2469 2489
0-1 Amp AC or 0-5 Amp AC
200% of rated input continuous
1000% of rated input for 5 seconds
<0.2VA per element
0-1mADC into 10 kmax. load; 10VDC output compliance
4-20 mADC into 750max. load; 15VDC output compliance
0-1mADC=±0.5% of full scale 0-1mADC=±0.2% of full scale
4-20mADC=±0.5% of span 4-20mADC=±0.2% of span
Zero: ±1% minimum(AHD only) Zero: ±5% minimum(AHD only)
Span: ± 2% minimum Span: ± 10% minimum
<400 milliseconds(0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case (AHD and TRMS)
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV, 1.2 x 50 microseconds)
>10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
± 250 PPM / °C of span ± 140 PPM / °C of span
< 0.2% at 400 AT/m
50 - 500 Hz < 0.2% effect on accuracy
< 0.2%, 45-65 Hz, fundamental through 9th harmonic (TRMS models only)
TRMS = 900g, 0-1mA = 358g, 4-20mA = 897g, 3 in 1 = 1100g
< 0.2% after 50G, 3 Axis and 6 repetitions
< 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
246921-380-AFA-0 248921-380-AFA-0
246931-380-AFA-1 248931-380-AFA-1
246921-380-AHD-1 248921-380-AHD-1
246931-380-AHD-1 248931-380-AHD-1
246923-380-AFA-0 248923-380-AFA-0
0-5 Amp AC, 60 HZ input
AVG./0-1 mA output / self powered
TRMS / 0-1mA output / 120V aux. power
AVG./4-20mA output / 120V aux. power
TRMS / 4-20mA / 120V aux. power
3 in 1 / 0-1mA output / self-powered
2
1) GENERAL
The 2469 and 2489 AC Average Current transducers produce an analog DC signal output corresponding to
the average value of the AC input. The true RMS versions always require external power and produce an
analog DC output corresponding to the true RMS value of the input signal.
2) SPECIFICATIONS
Model #
Input Current
Input over range capability
Input Burden
Rated outputs
Accuracy 10-100% of rated input
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Input frequency range
Influence of frequency
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
JUXTA AC CURRENT TRANSDUCERS
185-135 VAC
2170-264 VAC
21 Average current
23 3 in 1 Avg. current
31 True RMS current
3
4) ORDER FORMAT 2469 / 89 -- -
(3) Input
Model# (1) Transducer function (2) Input frequency (4) Output (5) Aux. power
2469
2489
37 0-1 Amp AC
38 0-5 Amp AC
0Input
powered
060 Hz
150 Hz
250/60 Hz
4400 Hz
5Other
AFA 0-1 mADC
(21 & 23 only)
AFA 0-1 mADC
(TRMS only)
AHD 4-20 mADC
(21 & 31 only)
5) CONNECTION DIAGRAMS FOR CT INPUT
6) MOUNTING AND OUTLINE DIMENSIONS:
SELF POWERED 3 IN 1 CURRENTAUXILIARY POWERED
SELF POWERED 3 IN 1 CURRENT
AUXILIARY POWERED
-
LOAD
L1 L2
LINE
14
DC
OUTPUT
+
23
246921
248921
246921
248921
246921
248921
246931
248931
LOAD
L1 L2
LINE
123456
DC
OUTPUT
AUX
POWER
-+-
+
246923
248923
-
LOAD
L1L2 L3
LINE
1 2 3 4
1 2 3 4
1 2 3 4
DC OUTPUT
DC OUTPUT
DC OUTPUT
+
+
+
-
-
246923
248923
246921
248921
246931
248931
JUXTA AC CURRENT TRANSDUCERS
(1) (2) (3) (4) (5)
(mm)
inches
➤➤
(77.15)
3.037
(88.9)
3.500
(10.1)
3.976
(51.11)
2.012
(50)
1.969
(38.1)
1.500
(14.7)
.579
(104.03)
4.096
(89.33)
3.517
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
(95.72)
3.769
(78)
3.071
(38.1)
1.5
(133)
5.236
(120.65)
4.750
(111.6)
4.394
+
(119.8)
4.717
(105.1)
4.138
(14.7)
.579
+
+
+
+
+
+
+
+
(95.72)
3.769
(78)
3.071
(38.1)
1.5
(111.6)
4.394
(120.65)
4.750
(133)
5.236
(119.8)
4.717
(105.1)
4.138
(14.7)
.579
2469 2489
0-150 VAC or 0-300 VAC
120% of rated input continuous
150 VAC: <1.8VA / element; 300 VAC: <3.6VA / element
150 VAC: <0.8VA; 300 VAC: <1.6VA
0-1mADC into 10 kmax. load; 10VDC output compliance
4-20 mADC into 750max. load; 15VDC output compliance
0-1mADC=±0.5% of full scale 0-1mADC=±0.2% of full scale
4-20mADC=±0.5% of span 4-20mADC=±0.2% of span
Zero: ±1% minimum(AHD only) Zero: ±5% minimum(AHD only)
Span: ±2% minimum Span: ±10% minimum
<400 milliseconds(0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case(AHD + TRMS)
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV 1.2 x 50 microseconds)
>10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
± 250 PPM / °C of span ± 140 PPM / °C of span
< 0.2% at 400 AT/m
50 - 500 Hz < 0.2% effect on accuracy
< 0.2%, 45-65 Hz, fundamental through 9th harmonic (TRMS models only)
TRMS = 900g, 0-1mA = 358g, 4-20mA = 897g, 3 in 1 = 1100g
< 0.2% after 50G, 3 Axis and 6 repetitions
< 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3Axis
File # E60579
0-150 VAC, 60 HZ input
AVG./0-1 mA / self powered
TRMS / 0-1mA / 120V aux. power
AVG./4-20mA / 120V aux. power
TRMS / 4-20mA / 120V aux. power
3 in 1 / 0-1mA output / self-powered
4
2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
246922-330-AFA-0 248922-330-AFA-0
246932-330-AFA-1 248932-330-AFA-1
246922-330-AHD-1 248922-330-AHD-1
246932-330-AHD-1 248932-330-AHD-1
246924-330-AFA-0 248924-330-AFA-0
1) GENERAL
The 2469 and 2489 AC Average Voltage transducers produce an analog DC signal output corresponding to
the average value of the AC input. The true RMS versions always require external power and produce an
analog DC output corresponding to the true RMS value of the input signal.
2) SPECIFICATIONS
Model #
Input Voltage
Input over range capability
Input Burden (Averaging models)
Input Burden (true RMS models)
Rated outputs
Accuracy 10-100% of rated input
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature drift
External magnetic field
Input frequency range
Influence of frequency
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
JUXTA AC VOLTAGE TRANSDUCERS
2469 (0.5% accuracy)
0-50mVDC and 0-1mADC are standard
Varies with input current or voltage
< 1 mADC
10 VDC
± 0.5% of full scale
± 5% minimum
± 5% minimum
< 500 milliseconds (0-99% of output)
2600 VAC input to output, power and case
1000 VAC aux. power to output and case
1000 VAC output to case
IEEE472/ANSI C37.90.1-1989 SWC TEST
C to +40° C
20 - 90% relative humidity (non-condensing)
908g (2 lbs.)
115V AC ±10%, 5.0 VA Burden
6
Input / Output Relationship
0-50mVDC / 0-1mADC
0-50mVDC / 4-20mADC
0-50mVDC / 0-10VDC
0-1mADC / 0-1mADC
0-1mADC / 4-20mADC
0-1mADC / 0-10VDC
Model # Description
246911-001-AFA-1 / DC Voltage input
246911-001-AHD-1 / DC Voltage input
246911-001-VMT-1 / DC Voltage input
246912-101-AFA-1 / DC Current input
246912-101-AHD-1 / DC Current input
246912-101-VMT-1 / DC Current input
1) GENERAL
The 2469 series DC to DC isolator provides an isolated analog output proportional to the DC voltage or
current input. Standard inputs are 50mVDC and 1 mADC. Auxiliary power is required to power the DC to
DC isolator. Other DC inputs and power options are available on special order from Yokogawa.
2) SPECIFICATIONS
Model #
Input signal ranges
Input impedance
Input burden
Output compliance
Accuracy 10-100% rated input
Span adjustment
Zero adjustment
Response time
Isolation
Surge withstand capability
Operating temperature
Operating humidity
Weight
Auxiliary Power Supply
3) STANDARD MODELS
JUXTA DC TO DC ISOLATORS
120 VAC, 5AAC, 60 Hz, input powered
Watt 1P2W, 0-1mA output (1 Element)
Watt 1P2W, 4-20mA output (1 Element)
Watt 3P3W, 0-1mA output (2 Element)
Watt 3P3W, 4-20mA output (2 Element)
Watt 3P4W, 0-1mA output (212Element)
Watt 3P4W, 4-20mA output (212Element)
Watt 3P4W, 0-1mA output (3 Element)
Watt 3P4W, 4-20mA output (3 Element)
2469 2489
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input 0-200% of rated input
200% of rated input continuous
1000% of rated input for 5 seconds
< 0.2VA per element
120V 240V 120V 240V
100-135VAC 200-264VAC 85-135VAC 170-264VAC
0-120% rated input 0-120% of rated input
< 0.5VA < 1.0VA < 0.3VA < 0.6VA
150% of rated input without damage (Auxiliary powered only)
0 to ±1mADC into 10kmax. load; 10VDC output compliance
4-20 mADC into 750max. load; 15VDC output compliance
0 ± 1mADC = 0.5% of full scale 0±1mADC = ±0.1% rdg. ± 0.05%FS
4-20mADC = 0.5% of span 4-20mADC = ±0.2% of span
120VAC: 1 Amp = 0-100 Watts; 5 Amp = 0-500 Watts
240VAC: 1 Amp = 0-200 Watts; 5 Amp = 0-1000 Watts
Zero: ± 1% minimum Zero: ± 5% minimum
Span: ± 2% minimum Span: ± 10% minimum
< 400 milliseconds (0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
> 10 megohm / 500VDC input/output/power/case
-20°C to +60°C 1mA (-20°to+70°C), 4-20mA(-20°to+60°C)
0 - 90% relative humidity (non-condensing)
±250 PPM / °C of span 1mA ±50FS, 4-20mA ±75span (PPM/°C)
< 0.2% at 400 AT/m
<0.5% <0.2%
<0.25%, 45-65 Hz, fundamental through 9th harmonic
1200g (2.65 lbs.)
<0.2% after 50G, 3 Axis and 6 repetitions
<0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy
Output calibration / element
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence : unbalanced currents /
phase interaction / Power Factor
Influence of frequency
Weight
Shock
Vibration
UL Recognition
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
8
2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
246951-540-AFA-0 248951-540-AFA-0
246951-540-AHD-0 248951-540-AHD-0
246953-540-AFA-0 248953-540-AFA-0
246953-540-AHD-0 248953-540-AHD-0
246954-540-AFA-0 248954-540-AFA-0
246954-540-AHD-0 248954-540-AHD-0
246955-540-AFA-0 248955-540-AFA-0
246955-540-AHD-0 248955-540-AHD-0
1) GENERAL
The 2469 and 2489 AC Watt transducers produce an analog output equal to the Watts measured by the
input. The typical calibration is 500 Watts / element for 120V and 5A AC transformer secondary inputs.
2) SPECIFICATIONS
3) STANDARD MODELS
JUXTA AC WATT TRANSDUCERS
120 VAC, 5AAC, 60 Hz, input powered
VAR 1P2W,
±
1mA output (1 Element)
VAR 1P2W,
12±8
mA output (1 Element)
VAR 3P3W,
±
1mA output (2 Element)
VAR 3P3W,
12±8
mA output (2 Element)
VAR 3P4W,
±
1mA output (212Element)
VAR 3P4W,
12±8
mA output (212Element)
VAR 3P4W,
±
1mA output (3 Element)
VAR 3P4W,
12±8
mA output (3 Element)
2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
246961-540-AFB-0-M 248961-540-AFB-0-M
246961-540-AHF-0-M 248961-540-AHF-0-M
246963-540-AFB-0-M 248963-540-AFB-0-M
246963-540-AHF-0-M 248963-540-AHF-0-M
246964-540-AFB-0-M 248964-540-AFB-0-M
246964-540-AHF-0-M 248964-540-AHF-0-M
246965-540-AFB-0-M 248965-540-AFB-0-M
246965-540-AHF-0-M 248965-540-AHF-0-M
2469 2489
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input 0-200% of rated input
200% of rated input continuous
1000% of rated input for 5 seconds
< 0.2VA per element
120V 240V 120V 240V
100-135VAC 200-264VAC 85-135VAC 170-264VAC
0-120% rated input 0-120% of rated input
< 0.5VA < 1.0VA < 0.3VA < 0.6VA
150% of rated input without damage (Auxiliary powered only)
0 to ±1mADC into a 10kmax. load; 10VDC output compliance
12±8mADC into a 750max. load; 15VDC output compliance
0 ± 1mADC = ±0.5% of full scale 0±1mADC = ±0.1% rdg. ± 0.1%FS
12±8mADC = ±0.5% of span 12±8mADC = ±0.2% of span
120VAC: 1 Amp = 0-100 VARS; 5 Amp = 0-500 VARS
240VAC: 1 Amp = 0-200 VARS; 5 Amp = 0-1000 VARS
Zero: ± 1% minimum Zero: ± 5% minimum
Span: ± 2% minimum Span: ± 10% minimum
< 400 milliseconds (0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
> 10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
±250 PPM / °C of span 1mA ±50FS, 4-20mA ±80span (PPM/°C)
< 0.2% at 400 AT/m
<0.5% <0.2%
1200g (2.65 lbs.)
<0.2% after 50G, 3 Axis and 6 repetitions
<0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
10
1) GENERAL
The 2469 and 2489 AC VAR transducers produce an analog output equal to the VARS measured by the
input. The typical calibration is 500 VARS / element for 120V and 5A AC transformer secondary inputs.
2) SPECIFICATIONS
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy
Output calibration / element
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence : unbalanced currents /
phase interaction / Power Factor
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS
JUXTA AC VAR TRANSDUCERS
2469 2489
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input 0-200% of rated input
200% of rated input continuous
1000% of rated input for 5 seconds
< 0.2VA per element
120V 240V 120V 240V
100-135VAC 200-264VAC 85-135VAC 170-264VAC
0-120% rated input 0-120% of rated input
< 0.5VA < 1.0VA < 0.3VA < 0.6VA
150% of rated input without damage (Auxiliary powered only)
0 to ±1mADC into a 10kmax. load; 10VDC output compliance
4-20 mADC into 750max. load; 15VDC output compliance
±0.5% of full scale ± 0.1% of reading. ± 0.05% full scale
±0.5% of full scale
± 0.1% of reading. ± 0.1% full scale
±0.5% of span ± 0.2% of span
Zero: ± 1% minimum Zero: ± 5% minimum
Span: ± 2% minimum Span: ± 10% minimum
< 400 milliseconds (0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
> 10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
±250 PPM / °C of span 1mA = W ± 50FS, V ±75span (PPM/°C)
< 0.2% at 400 AT/m
<0.5% <0.2%
<0.25%, 45-65 Hz, fundamental through 9th harmonic (Watt only)
1200g (2.65 lbs.)
<0.2% after 50G, 3 Axis and 6 repetitions
<0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
120 VAC, 5AAC, 60 Hz, input powered
W/V 1P2W, 0±1mA output (1 Element)
W/V 1P2W, 4-20mA output (1 Element)*
W/V 3P3W, 0±1mA output (2 Element)
W/V 3P3W, 4-20mA output (2 Element)*
W/V 3P4W, 0±1mA output (212Element)
W/V 3P4W, 4-20mA output (212Element)*
W/V 3P4W, 0±1mA output (3 Element)
W/V 3P4W, 4-20mA output (3 Element)*
2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
246941-540-AFB-0-M 248941-540-AFB-0-M
246941-540-AHD-0-M 248941-540-AHD-0-M
246943-540-AFB-0-M 248943-540-AFB-0-M
246943-540-AHD-0-M 248943-540-AHD-0-M
246944-540-AFB-0-M 248944-540-AFB-0-M
246944-540-AHD-0-M 248944-540-AHD-0-M
246945-540-AFB-0-M 248945-540-AFB-0-M
246945-540-AHD-0-M 248945-540-AHD-0-M
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
*VAR outputs for “AHD” are 12±8 mADC (see output options on next page).
Auxiliary power supply options <5.0 burden.
12
1) GENERAL
The 2469 and 2489 combined WATT/VAR transducers produce an analog output equal to the WATTS and
VARS measured by the input.
2) SPECIFICATIONS
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy: 0 ± 1mA output Watts
0 ± 1mA output VARS
4-20mA output
External calibration adjustment
Response time
Output ripple
Isolation
(Watt & VAR outputs are not isolated
from each other)
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence : unbalanced currents /
phase interaction / Power Factor
Influence of frequency
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS
JUXTA COMBINATION WATT/VAR TRANSDUCERS
2469 2489
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input
200% of rated input continuous
1000% of rated input for 5 seconds
< 0.2VA per element
120V 240V 120V 240V
100-135VAC 200-264VAC 85-135VAC 170-264VAC
0-120% rated input 0-120% of rated input
< 0.5VA < 1.0VA < 0.5VA < 1.0VA
150% of rated input without damage (Auxiliary powered only)
±1mADC into a 10kmax. load; 10VDC output compliance
4-12-20 mADC into a 750max. load; 15VDC output compliance
±0.01 Power Factor
0-1-0 Power Factor or 0.5-1-0.5 Power Factor
Zero: ± 1% minimum Zero: ± 5% minimum
Span: ± 2% minimum Span: ± 10% minimum
< 400 milliseconds (0-99% of output)
0.3% of FS peak-to-peak max. 0.5% of FS peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
> 10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
±500 PPM / °C of span ±150 PPM / °C of span
< 0.2% at 400 AT/m
<1% of span
Aux. Pwr.±0.01 max.±20% rated V.
Self pwr.±0.01 max. in range of Aux. Pwr
<2% of span <0.02 PF for 20-200% rated input current
<4% of rated current 4% of rated input
1000g (2.2 lbs.)
<0.2% after 50G, 3 Axis and 6 repetitions
<0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
14
2469 2489
246971-540-AFB-0-P 248971-540-AFB-0-P
246971-540-AHF-0-P 248971-540-AHF-0-P
246973-540-AFB-0-P 248973-540-AFB-0-P
246973-540-AHF-0-P 248973-540-AHF-0-P
246974-540-AFB-0-P 248974-540-AFB-0-P
246974-540-AHF-0-P 248974-540-AHF-0-P
120 VAC, 5AAC, 60 Hz, input powered
PF- Single phase / ±1mA output
PF- Single phase / 12±8mA output
PF- 3P3W balanced / ±1mA output
PF- 3P3W balanced / 12±8mA output
PF- 3P4W balanced / ±1mA output
PF- 3P4W balanced / 12±8mA output
1) GENERAL
The 2469 and 2489 Power Factor transducers have an analog output corresponding to 1- Cosine of the
phase angle of the input current relative to the input voltage signal. The analog output will indicate lead-
ing or lagging Power Factor by its direction from center which would be either 0 mA or 12mA based on
output selection.
2) SPECIFICATIONS
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy
Output calibration
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence of input Voltage
Influence of input Current
Low current detection
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS (0-1-0 PF)
JUXTA POWER FACTOR TRANSDUCERS
2469 (±2° Accuracy) 2489 (±1° Accuracy)
246976-540-AFB-0-P 248976-540-AFB-0-P
246976-540-AHF-0-P 248976-540-AHF-0-P
246977-540-AFB-0-P 248977-540-AFB-0-P
246977-540-AHF-0-P 248977-540-AHF-0-P
246978-540-AFB-0-P 248978-540-AFB-0-P
246978-540-AHF-0-P 248978-540-AHF-0-P
2469 2489
0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input
200% of rated input continuous
1000% of rated input for 5 seconds
< 0.2VA per element
120V 240V 120V 240V
100-135VAC 200-264VAC 85-135VAC 170-264VAC
0-120% rated input 0-120% of rated input
< 0.5VA < 1.0VA < 0.5VA < 1.0VA
150% of rated input without damage (Auxiliary powered only)
±1mADC into a 10kmax. load; 10VDC output compliance
4-12-20 mADC into a 750max. load; 15VDC output compliance
±2° Phase Angle ±1° Phase Angle
60°- 0°- 60° Phase Angle or 90°- 0°- 90° Phase Angle
Zero: ± 1% minimum Zero: ± 5% minimum
Span: ± 2% minimum Span: ± 10% minimum
< 400 milliseconds (0-99% of output)
0.3% of FS peak-to-peak max. 0.5% of FS peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
> 10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
±500 PPM / °C of span ±80 PPM / °C of span
< 0.2% at 400 AT/m
<0.2%, 45 - 65 Hz, fundamental through 9th harmonic
<0.5° <0.5° ±20% rated Voltage input (aux.pwr.)
<0.5° in range af aux. pwr. (int. pwr. model)
<1.0°
<1° for 20-200% rated input current
N/A 4% of rated input
1000g (2.2 lbs.)
<1° after 50G, 3 Axis and 6 repetitions
<1° after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
File # E60579
Model #
Current input / range
Current input over range capability
Current input burden
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden per element
Sustained Voltage input overange
Rated outputs
Accuracy
Output calibration
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temperature effect
External magnetic field
Influence of frequency
Influence of input Voltage
Influence of input Current
Low current detection
Weight
Shock
Vibration
UL Recognition
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
120V, 5A, 60 Hz, ±90°, input powered
PA- Single phase / ±1mA output
PA- Single phase / 12±8mA output
PA- 3P3W balanced / ±1mA output
PA- 3P3W balanced / 12±8mA output
PA- 3P4W balanced / ±1mA output
PA- 3P4W balanced / 12±8mA output
1) GENERAL
The 2469 and 2489 Phase Angle transducers have an analog output corresponding to the phase angle of
the input current relative to the input voltage signal. The analog output will indicate leading or lagging
Phase Angle by its direction from center which would be either 0 mA or 12mA based on output selection.
2) SPECIFICATIONS
3) STANDARD MODELS (±90° PA)
JUXTA PHASE ANGLE TRANSDUCERS
16
2469 2489
120V: 100 - 135 VAC, 240V: 200 - 264 VAC
±20% of rated voltage
120VAC <0.1 VA; 240VAC <0.2 VA
±1mADC into a 10kmax. load; 10VDC output compliance
4-12-20 mADC into 750max. load; 15VDC output compliance
±1% of input span 0-1mADC=±0.1% of input span
±2% of input span 0-1mADC=±0.2% of input span
4-20mADC=add±0.1% to accuracy
Zero: ±1% minimum Zero: ±5% minimum
Span: ±2% minimum Span: ±10% minimum
<400 milliseconds (0-99% of output)
0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
2500 VAC input to output, power and case
2000 VAC aux. power to output and case
500 VAC output to case
IEEE472/ANSI C37.90.1 - 1989, JIS C1111(5KV 1.2 x 50 microseconds)
>10 megohm / 500VDC input/output/power/case
-20°C to +60°C
0 - 90% relative humidity (non-condensing)
± 250 PPM / °C of span
±25ppm of center frequency(60Hz±5Hz)
± 500 PPM / °C of span
±5ppm of center frequency(60Hz±0.5Hz)
For 4-20mADC multiply ppm x 1.4
< 0.2% at 400 AT/m
Fundamental through 9th harmonic
1000g (2.2 lbs.)
< 0.2% after 50G, 3 Axis and 6 repetitions
< 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3Axis
File # E60579
18
2469 2489
246982-320-AFA-0 248982-320-AFA-0
246982-320-AHD-0 248982-320-AHD-0
246983-320-AFA-0 248983-320-AFA-0
246983-320-AHD-0 248983-320-AHD-0
246984-320-AFA-0 248984-320-AFA-0
246984-320-AHD-0 248984-320-AHD-0
1) GENERAL
The 2469 and 2489 Frequency transducers have an analog output corresponding to the frequency of the
AC input voltage. These transducers are capable of high accuracy measurement over various frequency
ranges.
2) SPECIFICATIONS
Model #
Voltage inputs and range:
Input powered range
Auxiliary powered range
Voltage input burden
Rated outputs
Accuracy: ±2, 5, 10, 25 Hz deviation
±0.5, 1 Hz deviation
External calibration adjustment
Response time
Output ripple
Isolation
Surge Withstand Capability
Insulation resistance
Operating temperature
Operating humidity
Temp. effect: ±2, 5, 10, 25 Hz deviation
±0.5, 1 Hz deviation
External magnetic field
Harmonics
Weight
Shock
Vibration
UL Recognition
3) STANDARD MODELS
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.
JUXTA FREQUENCY TRANSDUCERS
120VAC, 60 Hz, input powered
Freq. ± 1.0 Hz deviation, 0-1mA output
Freq. ± 1.0 Hz deviation, 4-20mA output
Freq. ± 2.0 Hz deviation, 0-1mA output
Freq. ± 2.0 Hz deviation, 4-20mA output
Freq. ± 5.0 Hz deviation, 0-1mA output
Freq. ± 5.0 Hz deviation, 4-20mA output
AFA 0-1 mADC
AFB 0 to ±1mADC
AHD 4-20 mADC
81 ± 0.5 Hz deviation
82 ± 1 Hz deviation
83 ± 2 Hz deviation
84 ± 5 Hz deviation
84 ± 5 Hz deviation
85 ± 10 Hz deviation
86 ± 25 Hz deviation
19
4) ORDER FORMAT 2469 / 89 ---
Model# (1) Transducer function
2469
2489 32 120 VAC
35 240 VAC
32 120 VAC
35 240 VAC
0Input pwr’d
1120 VAC
2240 VAC
060 Hz
150 Hz
32 120 VAC
35 240 VAC
355 Hz
32 120 VAC
35 240 VAC
4400 Hz
5) CONNECTION DIAGRAMS
6) MOUNTING AND OUTLINE DIMENSIONS:
(2) Input (3) Input frequency (4) Output (5) Aux. power
-
LOAD
L1 L2
LINE
1
DC
OUTPUT
+
23
456
AUX
POWER (OPTIONAL)
-
+
+
+
+
+
+
+
+
+
(95.72)
3.769
(78)
3.071
(38.1)
1.5
(111.6)
4.394
(120.65)
4.750
(133)
5.236
(119.8)
4.717
(105.1)
4.138
(14.7)
.579
JUXTA FREQUENCY TRANSDUCERS
(1) (2) (3) (4) (5)
(mm)
inches
Transducer function Rated inputs
*Rated outputs/external
Accuracy Output Response Frequency Power Auxiliary
Model# code load resistance @23±3ºC ripple time range consump. power
DC / DC Isolator 2371 00 0 - 50 mVDC 0 - 1mADC / 10k
(Photocoupler or 0 - 5 VDC 0 - 5mADC / 2k~1mA +
isolation) 2461 0 - 10VDC 4 - 20mADC / 500±0.5%of N / A 0.5 sec. DC aux. pwr. 120VAC
0 - 25VDC 0 - 10mVDC / 10kspan 1.9VA ±10%
0 - 65VDC 0 - 5VDC / 1k
0 - 1mADC 0 - 10VDC / 2k
AC Voltage/Current 2372 00 0 - 1mADC / 10k
(Mean value rect.) 2462 1 AAC 0 - 5mADC / 2k1 second 45-65 Hz 1 VA not req’d
AC Voltage/Current 2373 00 5 AAC 0 - 5VDC / 5k±0.5% of 1% p-p
(RMS value rect.) 2463 150 VAC 0 - 1mADC / 2kspan max.
AC Voltage/Current 2374 00 300 VAC 0 - 10VDC / 2k0.5 VA+ 120VAC
(True RMS rect.) or 0 - 1mADC / 10k0.5 sec. 45-10kHz Aux. pwr. ±10%
2464 4 - 20mADC / 5002 VA
1P2W 10 120V / 1 AAC 0 - 10VDC / 2k
Power 1P3W 2375 20 120V / 5 AAC 0 - 1mADC / 10k
(Watts) 3P3W 2465 30 240V / 1 AAC 0 - 5mADC / 2k
3P4W 40 240V / 5 AAC 4 - 20mADC / 500±0.5% of 0.7 sec. V = 3VA
Reactive 1P2W 10 120V / 1 AAC ± 10 VDC / 2kspan A = 1VA
Power 1P3W 2376 20 120V / 5AAC ± 1mADC / 10k1% p-p 45-65 Hz not req’d
(VARS) 3P3W 2466 30 240V / 1AAC ± 5mADC / 2kmax.
3P4W 40 240V / 5AAC 4 - 20mADC / 500
1P2W 10 120V / 1AAC ± 10 VDC / 2k
Phase 1P3W 2377 20 120V / 5AAC ± 1mADC / 10k±2° 0.5 sec. V = 2.5VA
Angle 3P3W 2467 30 240V / 1AAC ± 5mADC / 2kA = 0.1VA
3P4W 40 240V / 5AAC 4 - 20mADC / 500
01
120V/45-55Hz
45-55 Hz
240V/45-55Hz
0 - 10VDC / 2k±0.1 Hz
Frequency 2378 02
120V/55-65Hz
0 - 1mADC / 10k.1%p-p 2 seconds 55-65 Hz 1.5VA not req’d
2468
240V/55-65Hz
0 - 5mADC / 2kmax.
03
120V/45-65Hz
4 - 20mADC / 500±0.2Hz 45-65 Hz
240V/45-65Hz
24
1) GENERAL
The 2371-2378 and 2461-2468 series of power transducers combine high performance with compact size.
Most of these transducers are self powered except DC to DC isolators and True RMS Amps and Volts which
require auxiliary power. Accuracy of 0.5% is standard in both the foot mount and DIN rail models. They
are constructed of flame resistant molded black ABS resin material; and operating temperature is 0-40°C
(20-80% RH, non-condensing). Storage temperature is -10 to +50°C. Weight <.5Kg (1.1lbs.)
2) SPECIFICATIONS
2461-2468 DIN rail mount 2371-2378 foot mount
YOKOGAWA TRANSDUCERS
*See next page for additional outputs.
5) ORDER FORMAT: 237
OR: 246
-- -
(1) Transducer function
(2) Rated inputs (3) **Rated outputs (4) Auxiliary power
2120 VAC 50/60 Hz
4240 VAC 50/60 Hz
Only required for function
100 DC/DC & 400 TRMS
Polarity (Watt/VAR/PA only)
NNo polarity (Watt only)
P-Lag to +Lead
M-Lead to +Lag
AFA 0-1mADC
AFX 0-5mADC
AFB ± 1mADC
AFZ ± 5mADC
AHE 4 - 20mADC
VGZ 0 - 10mVDC
VLS 0 - 5VDC
VMT 0 - 10VDC
VHB ± 10mVDC
VLU ± 5VDC
VLY ± 6VDC
VMS ± 10VDC
VME 4.5-6.5VDC
237 = Foot mount
246 = DIN rail
100 DC / DC isolator
200 AC Amp or Volt (Mean value)
300 AC Amp or Volt (RMS value)
400 AC Amp or Volt (True RMS)
xx*(select one)
5XX* Watt 10 1P2W
6XX* VAR 20 1P3W
7XX* Phase Angle 30 3P3W
40 3P4W
xx*(select one)
8XX* Frequency 01 45-55 Hz
02 55-65 Hz
03 45-65 Hz
01 DC 50mV
02 DC 1V
03 DC 5V
04 DC 10V
05 DC 25V
06 DC 65V
21 DC 1mA
32 AC 150V
34 AC 300V
35 AC 1A
36 AC 5A
45 AC 120V / 1A
46 AC 120V / 5A
47 AC 240V / 1A
48 AC 240V / 5A
37 AC 120V
38 AC 240V
CODE# AFA AFX AFB AFZ AHE VGZ VLS VMT VHB VLU VLY VMS VME
FUNCTION OUTPUT 1mA 5mA ±1mA ±5mA 4-20mA 10mV 5V 10V ±10mV ±5V ±6V ±10V 4.5-6.5V
100 DC / DC isolator XX - - X XXX - -- - -
200 AC Amp / Volt XX - - - - -- - -- - -
300 AC Amp / Volt X- - - - XX- - -- - -
400 AC Amp / Volt XX - - X XXX - -- - -
5XX Watt XX - - X XXX - -- - -
6XX VAR --X X X --- XX-X -
7XX Phase Angle --X X X --- X -X- -
801 / 802 Frequency XX - - X X -X X -- - -
803 Frequency XX - - X XXX - -- - X
** Outputs available by transducer function:
PLASTIC CASE MINIATURE TRANSDUCERS
3) GENERAL SPECIFICATIONS
Overrange capability Dielectric strength between: Insulation resistance between:
Current input: 1) Input terminals & case - 2600VAC for 1 minute 1) All terminals and ground terminal
1000% of rated input for 5 sec. 2) Input & output terminals - 2600VAC for 1 minute 2) Input/output/ground term./auxiliary pwr.
Voltage input: 3) Aux. pwr. term. & input term./case-2600VAC for 1 min. -----------------------------------------------
150% of rated input for 5 sec. 4) Output terminals and case - 1000VAC for 1 minute Is greater than 100 Megohm at 500VDC
(1) (2) (3) (4)
4) STANDARD MODELS (AC AMPS, VOLTS, WATTS, VARS, PHASE ANGLE)
Input Output DIN Rail Foot Mount Input Output DIN Rail Foot Mount
5A AC (AVG) 1mA 246300-36-AFA 237300-36-AFA Watt 3P4W 1mA 246540-46-AFA-N 237540-46-AFA-N
5A AC (TRMS) 1mA 246400-36-AFA-2 237400-36-AFA-2 (120V, 5A) 4-20mA 246540-46-AHE-N 237540-46-AHE-N
4-20mA 246400-36-AHE-2 237400-36-AHE-2 VAR 3P3W ±1mA 246630-46-AFB-M 237630-46-AFB-M
150V AC (AVG) 1mA 246300-32-AFA 237300-32-AFA (120V, 5A) 4-20mA 246630-46-AHE-M 237630-46-AHE-M
150V AC (TRMS) 1mA 246400-32-AFA-2 237400-32-AFA-2 VAR 3P4W ±1mA 246640-46-AFB-M 237640-46-AFB-M
4-20mA 246400-32-AHE-2 237400-32-AHE-2 (120V, 5A) 4-20mA 246640-46-AHE-M 237640-46-AHE-M
Watt 3P3W 1mA 246530-46-AFA-N 237530-46-AFA-N PA 3P3W ±1mA 246730-46-AFB-P 237730-46-AFB-P
(120V, 5A) 4-20mA 246530-46-AHE-N 237530-46-AHE-N (120V, 5A) 4-20mA 246730-46-AHE-P 237730-46-AHE-P
25