19
19
19.10 Low Voltage Products & Systems
1SXU 000 020 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Interface
relays
M 4/9.R111...
M 4/9.R111 M 4/9.R111L
12 V 24 V 12 V 24 V
0.3 W 0.3 W 0.6 W 0.8 W
24 mA 14 mA 52 mA 33 mA
1.2 V DC 2.4 V DC 1.2 V 2.4 V
12 V / 150 V DC - 250 V AC
10 mA / 5 A
0.6 VA / 1250 VA
0.6 W / 150 W
1 x 106
2 x 107
5 ms
6 ms 7 ms
4 ms
UL 94 V0
0.2-4 mm² / 22-12 AWG
0.22-2.5 mm² / 22-12 AWG
2.5 mm² / 12 AWG
9 mm .354"
3.5 mm .137"
IP 20 NEMA 1
0.4-0.6 Nm 3.5-5.3 lb.in
11
A2
A1
14
M 4/9.R111...
1
2
5
7
4
6
3
M 4/9.R111
M 4/9.R111L
8
9
R910 Relay modules
DIN 1-3
M 4/9.R111... - 2.5 mm² blocks - 9 mm .354" spacing
center of rail
Relay characteristics
COIL
Rated voltage +20%, -20% on DC
Power
Rated current
Drop-out voltage at 20°C
Status device
CONTACT
Type
Voltage switching range min./max.
Current switching range
Load switching range
AC1 min. / max.
DC1 min. / max.
Number of on-load operations
Number of off-load operations
Pull-in time (delay time)
Drop-out time (delay time)
Bounce time
Insulation coil / contacts
Breakdown voltage with 1.2/50µ wave
Insulation contacts/contacts
Storage ambient temperature
Operating ambient temperature
Other characteristics
Body material grey
Wire Solid wire
size Stranded wire
Rated wire size
Wire stripping length
Recommended screwdriver
Protection
Recommended torque
Approvals
Reference standards
lamp
1 NO
3000 V RMS
4000 V RMS
750 V RMS
-40°C to +80°C
See derating curve hereunder
-
CEI 947-7-1 / CEI 947-1 / CEI 1131-2 (in relevant parts) / CEI 60664-1 / CEM : IRC 1000-4-2, 3, 4, 5, 6.
Characteristics
Description Type Order P/N
Packaging Weight
kg
Relay module 12 V DC M 4/9.R111-12VDC 1SNA 607 029 R0100 10 0.02
Relay module 24 V DC M 4/9.R111-24VDC 1SNA 607 030 R0600 10 0.02
Relay module with lamp 12 V DC M 4/9.R111L-12VDC 1SNA 607 001 R0600 10 0.02
Relay module with lamp 24 V DC M 4/9.R111L-24VDC 1SNA 607 002 R0700 10 0.02
Accessories
Derating curve
1 High end stop (all rails) BAMH 9,1 mm 1SNA 114 836 R0000 50
2 Test socket DIA. 2 mm AL2 1 1SNA 163 070 R0000 50
DIA. 3 mm AL3 1 1SNA 163 261 R0000 50
3 Test device grey DCG 1SNA 163 218 R0500 10
4 Test plug FC2 1SNA 007 865 R2600 10
5 Jumper bar 8 poles BJS9 12 1SNA 177 583 R1200
not assembled 16 poles BJS9 12 1SNA 177 584 R1300
6 Sub-assembly for jumper bar EV6D 12 1SNA 168 400 R1600 20
(screw + jumper + post)
7 IDC jumper AD2,5 1SNA 114 205 R2000 50
8 Comb type jumper bar PC9 1SNA 210 160 R1200 10
9 Marking method RC65 and RC610 see marking
1 These accessories can be used on the lower connection only.
2 Use of these accessories requires the user to cut out the precut partition.
Order Codes