Engineering Specification
Crimp-type terminals shall, electrically and mechnically,
connect to a pre-stripped end of a stranded copper wire
and hav e a flat tongue portion with a central opening for
mounting around a scre w or stud.
The terminal line shall of fer tongue v ariations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.): and
barrel v ariations in wire (AWG) size (22-18, 16-14,
12-10, etc.) and construction (non-insulated brazed seam,
vinyl insulated b utted seam, nylon insulated with
insulation grip, etc.). The terminal line shall hav e
regulatory agenc y co verage (UL Listing, CSA
Certification). The terminal tongue shall be mark ed with
the wire range and manufacturer’s symbol ().
The nylon-insulated, ring tongue terminal with insulation
grip shall be tin-plated, annealed copper , with the tongue
having a specif ied stud hole (size 4 thru 1/2 in.) and a
butted seam barrel with a tin plated brass, funnel entry
insulation grip, covered by a molded n ylon slee v e, color
coded and sized for a specified (AWG) wire range
(22-18, 16-14, 12-10).
Insulated terminals shall be UL Listed and CSA Certified
for 600 Volts maximum building wire: 1000 Volts
maximum in signs, fixtures and luminaries and ha ve a
maximum operating temperature of 221°F (105°C).
Installation Information
UL Listed and CSA Certified for use on stranded copper
(AWG) wire only.
Strip away the end 3/8 inch of wire insulation.
Make the crimp in the proper station of a recommended
3M crimp tool: TH-440, TH-450 (scissor style), or
TR-482, TR-490 (ratchet style) hand tools.
Barrel Crimp (Electrical)
Insulation Support Crimp
(Mechanical)
WARNING
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electr ical codes.