https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) MCR voltage measuring transducer, for alternating current voltages from 0..20 V AC to 0..440 V AC, output signal 0..10 V/0(4)..20 mA Your advantages Replacement device MACX MCR-VAC-(PT) 2906239 with 8 measurement ranges from 0V...20VAC to 0V...660VAC, output signals: 0V...10V / 0 (4)mA...20mA Adjustable voltage ranges Bidirectional output signals 3-way isolation ZERO/SPAN adjustment 20% Tool-free parameterization of measured values Teach-in configuration of the measured value range Key Commercial Data Packing unit 1 pc GTIN GTIN 4017918125400 Weight per Piece (excluding packing) 200.000 g Custom tariff number 85437090 Country of origin Germany Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area 01/16/2021Page1/6 https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Technical data Dimensions Width 22.5 mm Height 99 mm Depth 114.5 mm Ambient conditions Ambient temperature (operation) -25 C ... 60 C Ambient temperature (storage/transport) -40 C ... 85 C (non-condensing) Maximum altitude < 2000 m Degree of protection IP20 Noise immunity EN 61000-6-2 Input data Input voltage range 0 V ... 370 VAC Input resistance 370 k Input voltage range 0 V ... 250 VAC Input resistance 250 k Input voltage range 0 V ... 170 VAC Input resistance 170 k Input voltage range 0 V ... 120 VAC Input resistance 120 k Input voltage range 0 V ... 80 VAC Input resistance 80 k Input voltage range 0 V ... 54 VAC Input resistance 54 k Input voltage range 0 V ... 36 VAC Input resistance 36 k Input voltage range 0 V ... 24 VAC Input resistance 24 k Nom. voltage 440 V (ungrounded) 250 V (to earth) Output data Output name Voltage output Voltage output signal 0 V ... 10 V Max. output voltage 15 V Load/output load voltage output > 10 k Ripple < 50 mVPP Output name Current output Current output signal 0 mA ... 20 mA 01/16/2021Page2/6 https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Technical data Output data 4 mA ... 20 mA Max. output current 30 mA Load/output load current output < 500 Ripple < 50 mVPP Power supply Supply voltage range 18.5 VDC ... 30.2 VDC Max. current consumption < 45 mA Connection data Connection method Pluggable screw connection Connection technology Screw connection Stripping length 8 mm Screw thread M3 Conductor cross section solid 0.2 mm ... 2.5 mm Conductor cross section flexible 0.2 mm ... 2.5 mm Conductor cross section AWG 24 ... 14 General Maximum transmission error < 1.5 % (of final value) Temperature coefficient, typical 0.02 %/K (50/60Hz) Frequency measuring range 45 Hz ... 400 Hz Alignment zero 20 % Alignment span 20 % Step response (10-90%) 250 ms Overvoltage category III Degree of pollution 2 Rated insulation voltage 300 VDC Test voltage input/output 3.3 kV (50 Hz, 1 min.) Test voltage input/power supply 3.3 kV (50 Hz, 1 min.) Test voltage output/power supply 1 kV (50 Hz, 1 min.) Electromagnetic compatibility Conformance with EMC directive Noise emission EN 61000-6-4 Noise immunity EN 61000-6-2 Color green Housing material Polyamide PA non-reinforced Standards and Regulations Electromagnetic compatibility Conformance with EMC directive 01/16/2021Page3/6 https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Technical data Standards and Regulations Noise emission EN 61000-6-4 Noise immunity EN 61000-6-2 Connection in acc. with standard CUL Conformance CE-compliant UL, USA/Canada cULus Conformance/approvals Designation CE Identification CE-compliant Designation UL, USA/Canada Identification cULus Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 50 years For details about hazardous substances go to tab "Downloads", Category "Manufacturer's declaration" Drawings Application drawing Dimensional drawing Control system 99 22,5 4...20mA 1 U1 6 U6 2 U2 7 U7 OUT MCR-VAC-UI-O-DC POWER 13 + 24V 14 3 U3 GND 2 11 GND 3 8 GND 1 4 U4 GND 2 ZERO + 24V SPAN 9 10 Power I U 12 L1 L2 L3 N 114,5 IN 5 U5 15 16 GND 3 24V Mains voltage Voltage measurement in case of grounded circuits 01/16/2021Page4/6 https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Circuit diagram IN 0-370V 0-250V 0-170V 0-120V 0-80V 0-54V 0-36V 0-24V GND 1 OUT 9 OUT I 10 OUT U 11 GND2 12 GND2 1 2 3 4 13 + 24VDC 14 + 24VDC 15 GND3 16 GND3 5 6 J 7 J 8 Classifications eCl@ss eCl@ss 10.0.1 27210125 eCl@ss 11.0 27210125 eCl@ss 4.0 27271100 eCl@ss 4.1 27200300 eCl@ss 5.0 27200300 eCl@ss 5.1 27200300 eCl@ss 6.0 27210100 eCl@ss 7.0 27210125 eCl@ss 8.0 27210125 eCl@ss 9.0 27210125 ETIM ETIM 4.0 EC002477 ETIM 5.0 EC002477 ETIM 6.0 EC002477 ETIM 7.0 EC002477 UNSPSC UNSPSC 6.01 30211504 UNSPSC 7.0901 39121006 UNSPSC 11 39121006 UNSPSC 12.01 39121006 UNSPSC 13.2 39121006 UNSPSC 18.0 39121008 UNSPSC 19.0 39121008 UNSPSC 20.0 39121008 UNSPSC 21.0 39121008 01/16/2021Page5/6 https://www.phoenixcontact.com/us/products/2811103 Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103 Approvals Approvals Approvals UL Recognized / cUL Recognized / EAC / cULus Recognized Ex Approvals Approval details UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 EAC RU*DE.*08.B.01852-19 cULus Recognized Phoenix Contact 2021 (c) - all rights reserved http://www.phoenixcontact.com 01/16/2021Page6/6