https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page1/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR voltage measuring transducer, for alternating current voltages from 0..20 V AC to 0..440 V AC, output signal
0..10 V/0(4)..20 mA
Your advantages
Replacement device MACX MCR-VAC-(PT) 2906239 with 8 measurement ranges from 0V...20VAC to 0V...660VAC, output signals:
0V...10V / 0 (4)mA...20mA
Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20%
Tool-free parameterization of measured values
Teach-in configuration of the measured value range
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4017918125400
Weight per Piece (excluding packing) 200.000 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page2/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Technical data
Dimensions
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C (non-condensing)
Maximum altitude < 2000 m
Degree of protection IP20
Noise immunity EN 61000-6-2
Input data
Input voltage range 0 V ... 370 VAC
Input resistance 370 kΩ
Input voltage range 0 V ... 250 VAC
Input resistance 250 kΩ
Input voltage range 0 V ... 170 VAC
Input resistance 170 kΩ
Input voltage range 0 V ... 120 VAC
Input resistance 120 kΩ
Input voltage range 0 V ... 80 VAC
Input resistance 80 kΩ
Input voltage range 0 V ... 54 VAC
Input resistance 54 kΩ
Input voltage range 0 V ... 36 VAC
Input resistance 36 kΩ
Input voltage range 0 V ... 24 VAC
Input resistance 24 kΩ
Nom. voltage 440 V (ungrounded)
250 V (to earth)
Output data
Output name Voltage output
Voltage output signal 0 V ... 10 V
Max. output voltage 15 V
Load/output load voltage output > 10 kΩ
Ripple < 50 mVPP
Output name Current output
Current output signal 0 mA ... 20 mA
https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page3/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Technical data
Output data
4 mA ... 20 mA
Max. output current 30 mA
Load/output load current output < 500 Ω
Ripple < 50 mVPP
Power supply
Supply voltage range 18.5 VDC ... 30.2 VDC
Max. current consumption < 45 mA
Connection data
Connection method Pluggable screw connection
Connection technology Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
General
Maximum transmission error < 1.5 % (of final value)
Temperature coefficient, typical 0.02 %/K (50/60Hz)
Frequency measuring range 45 Hz ... 400 Hz
Alignment zero ± 20 %
Alignment span ± 20 %
Step response (10-90%) 250 ms
Overvoltage category III
Degree of pollution 2
Rated insulation voltage 300 VDC
Test voltage input/output 3.3 kV (50 Hz, 1 min.)
Test voltage input/power supply 3.3 kV (50 Hz, 1 min.)
Test voltage output/power supply 1 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Color green
Housing material Polyamide PA non-reinforced
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page4/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Technical data
Standards and Regulations
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Connection in acc. with standard CUL
Conformance CE-compliant
UL, USA/Canada cULus
Conformance/approvals
Designation CE
Identification CE-compliant
Designation UL, USA/Canada
Identification cULus
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Application drawing
4...20mA
24V
MCR-VAC-UI-O-DC
13
14
15
+24V
POWER
GND3
1
2
3
9
10
11
I
U
GND2
ZERO
Power
OUT
IN
5
6
7
16
GND3
412
GND2
8
GND1
SPAN
U4
U7 U3
U6 U2
U5 U1
+24V
L1
L2
L3
N
Controlsystem
Mainsvoltage
Voltage measurement in case of grounded circuits
Dimensional drawing
99 22,5
114,5
https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page5/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Circuit diagram
+24VDC
+24VDC
OUT
IN
GND2
GND3
GND2
GND3
OUTU
OUTI
9
1
5
13
11
3
7
15
10
2
6
14
12
4
8
16
GND1
0-24V
0-120V
0-170V
0-36V
0-250V
0-54V
0-370V
0-80V
J
J
Classifications
eCl@ss
eCl@ss 10.0.1 27210125
eCl@ss 11.0 27210125
eCl@ss 4.0 27271100
eCl@ss 4.1 27200300
eCl@ss 5.0 27200300
eCl@ss 5.1 27200300
eCl@ss 6.0 27210100
eCl@ss 7.0 27210125
eCl@ss 8.0 27210125
eCl@ss 9.0 27210125
ETIM
ETIM 4.0 EC002477
ETIM 5.0 EC002477
ETIM 6.0 EC002477
ETIM 7.0 EC002477
UNSPSC
UNSPSC 6.01 30211504
UNSPSC 7.0901 39121006
UNSPSC 11 39121006
UNSPSC 12.01 39121006
UNSPSC 13.2 39121006
UNSPSC 18.0 39121008
UNSPSC 19.0 39121008
UNSPSC 20.0 39121008
UNSPSC 21.0 39121008
https://www.phoenixcontact.com/us/products/2811103
01/16/2021Page6/6
Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / cULus Recognized
Ex Approvals
Approval details
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
EAC RU*DE.*08.B.01852-19
cULus Recognized
Phoenix Contact 2021 © - all rights reserved