SPECIFICATIONS
FUNCTIONAL SPECIFICATIONS
SERVICE: Liquid, gas or vapor.
RANGE LIMITS:
0/3 to 0/6 psi (0/.2 to 0/.4 bar)
0/6 to 0/15 psi (0/.4 to 0/1 bar)
0/3 to 0/15 psi (0/.2 to 0/1 bar)
0/6 to 0/30 psi (0/.4 to 0/2.1 bar)
0/20 to 0/100 psi (0/1.4 to 0/6.9 bar)
0/60 to 0/300 psi (0/4 to 0/20.7 bar)
0/200 to 0/1000 psi (0/14 to 0/69.0 bar)
0/600 to 0/3000 psi (0/40 to 0/206.9 bar)
0/1000 to 0/5000 psi (0/70 to 0/344.8 bar)
OUTPUT: 4-20 mADC, limited to 30 mADC.
POWER SUPPLY: 12 to 40 VDC with
reverse polarity protection.
LOOP RESISTANCE: 1400 ohms max at 40
volts.
TURNDOWN: 5:1.
ZERO ADJUST: +10%.
SPAN ADJUST: +10%.
TEMPERATURE LIMITS:
Electronics (Ambient): -40o F to 140o F
(-40o C to 60o C)
Process Interface: -40o F to 212o F (-40o C
to 100o C)
Storage: -40o F to 212o F (-40o C to 100o C)
OVERRANGE: 300% upper range limit.
HUMIDITY LIMITS: 0-100% RH.
PERFORMANCE SPECIFICATIONS
ACCURACY: +0.25% of calibrated span
including linearity, hysteresis and
repeatability. (BFSL)
RESPONSE TIME: Time constant of 20
milliseconds.
STABILITY: +0.5% of upper range limit for
six months.
TEMPERATURE EFFECT:
(includes zero and span)
Compensated: -20o F to 180o F (-29o C
to 82o C)
Between 30o F and 130o F (-1o C and
54o C): +1% of URL per 50o F (28o C)
Between -20o F and 180o F (-29o C and
82o C): +1.6% of URL per 50o F (28o C)
POWER SUPPLY EFFECT: +0.005% Full
Scale per volt.
SURGE PROTECTION: Standard.
VIBRATION EFFECT: +0.1% of upper
range limit for 3 g to 200 Hz.
POSITION EFFECT: Zero shifts up to
0.01 psi.
OVERRANGE EFFECTS: +0.15% Full
Scale per 200% of maximum range.
PHYSICAL SPECIFICATIONS
MATERIALS OF CONSTRUCTION:
Process Wetted Parts: 316 Stainless
Steel
Diaphragm (Models 851F): Hastelloy “C”
Non Wetted Parts: 316 Stainless Steel;
VITON “O” Ring
Fill Fluid: DC 200 Silicone (Standard)
Process Connection: Reference Model
Code
Electrical Connection: Reference Model
Code
Weight: 1 lb. (450 grams)
Cable Length: 24 inches (61 cm), 22 AWG
CLASSIFICATIONS
FACTORY MUTUAL:
Intrinsically safe for Class I, II, III Division
I, Groups A, B, C, D, E, F, G for
hazardous locations per AMETEK Dwg.
BK750407.
Entity Requirement: Imax = 225mA, Vmax
= 36V, Ci = 0.126 µf., Li = 0 mH
Explosion Proof for Class I, II, III Division
1, Groups C, D,E, G, for hazardous
locations. NEMA 4 Enclosure. Conduit
seal must be within 18” of transmitter.
CANADIAN STANDARDS ASSOCIATION:
Exia-Intrinsically safe for Class I, Division
1 & 2, Groups A, B, C, D; Class II,
Groups E, F, G when connected per
AMETEK Dwg. BK750483.
Explosion Proof for Class I, Division 1,
Groups B, C, D; Class II, Groups E, F, G;
Class III for Hazardous locations.
Enclosure 4, Temperature Code T3C
(160o C)
CALIBRATION
MODCAL II CALIBRATION SYSTEM*
NEGATIVE
TURNDOWN
(COURSE)
ADJUSTMENT
SPAN
ADJUSTMENT
GROUND
POSITIVE
ZERO (FINE)
ADJUSTMENT
*Contact factory for information on calibration system.