2Specifications are subject to change without notice (14.03.01)
Power supply AC types Installation cat. III (IEC 664)
Rated operational voltage
through pins 2 & 10 230 230 VAC ± 15%, 45 to 65 Hz
115 115 VAC ± 15%, 45 to 65 Hz
024 24 VAC ± 15%, 45 to 65 Hz
Drop-out tolerance ≥40 ms
Rated insulation voltage ≥2.0 kVAC (rms)
(supply/elec.)
Rated transient protection volt. 4 kV (1.2/50 µs)
(line/neutral)
Power supply DC type Installation cat. III (IEC 664)
Rated operational voltage 724 24 VDC ± 15% (pin 2 pos.)
Rated insulation voltage None
Rated transient protection volt. 800 V (1.2/50 µs)
Consumption AC supply 2.5 VA
DC supply 1.5 W
Built-in battery for
time function
Nominal voltage 5 V
Capacity 40 mAh
Charging current 360 µA
Discharging current 120 µA
SB 135
Time setting
Knob-adjustable on scale in
seconds, minutes or hours.
PE = pin 7
Power supply
The relay operates immedi-
ately after power supply is
applied.
When power supply is inter-
rupted, the time period starts
and at expiration of the set
time period, the relay releases.
If power supply is reapplied
before the relay is released,
the time is reset and the re-
lay remains on.
The built-in battery is re-
charged when power supply
is applied and is discharged
during the time periods.
To maintain sufficient energy
in the battery, the relay must
be recharged for at least one
third of the total discharging
periods as the recharge/dis-
charge current ratio is 3:1.
The capacity of the built-in
battery is sufficient for more
than 300 h of continuous time
measuring without recharg-
ing it.
Please note
The SB 135 should not be
operated by short pulses. For
this purpose the relay
DMB01, operated by means
of an external contact func-
tion, should be used.
NB! It is recommended to
connect the SB 135 to the
power supply for 48 hrs be-
fore it is put into regular ser-
vice in order to compensate
for energy losses due to e.g.
a long storage period.
Between pins 6 and 7. Pin 6
positive.
Rj= 1 kΩ.
Curve I
Ideal battery voltage at unin-
terrupted power supply.
Curve II
Min. battery voltage. Battery
should be recharged before
voltage drops to min. level.
Curve III
Course of battery voltage.
The recharging periods must
always equal at least one
third of the total discharging
periods.
PowerON delay ≤200 ms
Indication for
Power supply ON LED, red
Environment
Degree of protection IP 20 B
Pollution degree 2 (IEC 664)
Operating -20°to +50°C (-4°to +122°F)
Storage -50°to +85°C (-58°to +185°F)
Weight AC types 200 g
DC types 125 g
Approvals UL, CSA
CE Marking Yes
Battery
control
Supply Specifications General Specifications
Time Setting
Mode of Operation
Battery Control
Wiring Diagram