Millenium II + Standard Intuitive programming via function block (FBD) or grafcet (SFC) Function : timing, counting, etc Application-specific functions : rotation, cam timers, 1 calculation, etc Discrete, analogue or potentiometer inputs Relay, solid state or PWM outputs Backlit LCD display Program password protection Integral calender and clock User-definable from the front panel Non-expandable Specifications Type SA 12 Input 8 PNP 8 8 8 PNP 8 PNP 8 PNP 8 NPN 12 PNP 12 12 12 PNP 12 PNP 12 PNP 12 NPN SA 20 Output 4 relays 4 relays 4 relays 4 solid state 4 relays 4 solid state 4 relays 8 relays 8 relays 8 relays 8 solid state 8 relays 8 solid state 8 relays Supply 24 VDC 100 - 240 VAC 24 VAC 24 VDC 12 V DC 12 V DC 24 VDC 24 VDC 100 - 240 VAC 24 VAC 24 VDC 12 V DC 12 V DC 24 VDC Code 88 950 041 88 950 043 88 950 044 88 950 042 88 950 045 88 950 046 88 950 049 88 950 051 88 950 053 88 950 054 88 950 052 88 950 055 88 950 056 88 950 059 Dimensions SA 12 SA 20 125 mm A B Esc OK 82 mm I1 I2 I3 I4 I5 I6 I7 I8 90 mm 90 mm 82 mm 72 mm L1 N L1 N I1 I2 I3 I4 I5 I6 I7 I8 A B Esc I9 I10 I11 I12 OK O1 O 2 O3 O4 59,2 mm 60 mm 112,6 mm 60 mm General characteristics see page 23 To order, see page 6 16 For more information www.crouzet.com Millenium II + Expandable Expandable : communication, inputs/outputs, etc Intuitive programming via function block (FBD) or grafcet (SFC) Function : timing, counting, etc Application-specific functions : rotation, cam timers, calculation, etc Discrete, analogue or potentiometer inputs Relay, solid state or PWM outputs Backlit LCD display Program password protection Integral calender and clock User-definable from the front panel Can take an XC adjacent extension and an XL local extension 1 Specifications Type XT 20 Input 12 PNP 12 PNP 12 PNP 12 PNP 12 PNP 12 PNP 12 NPN 12 PNP 12 12 12 PNP 12 NPN EX 20 Output 8 relays 8 relays 8 relays 8 solid state 8 relays 8 solid state 8 relays 8 relays 8 relays 8 relays 8 solid state 8 relays Supply 24 VDC 100 - 240 VAC 24 VAC 24 VDC 12 V DC 12 V DC 24 VDC 24 V DC 100 - 240 V AC 24 V AC 24 V DC 24 V DC Code 88 950 061 88 950 063 88 950 064 88 950 062 88 950 065 88 950 066 88 950 069 88 950 831 88 950 833 88 950 834 88 950 832 88 950 839 Dimensions XT 20 EX 20 A B Esc 125 mm I9 I10 I11 I12 L1 N OK 112,6 mm 60 mm I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 82 mm I1 I2 I3 I4 I5 I6 I7 I8 90 mm 82 mm 90 mm 125 mm L1 N 112,6 mm 60 mm General characteristics see page 23 To order, see page 6 For more information www.crouzet.com 17 Millenium II + Blind No display or parameter-setting buttons Intuitive programming via function block (FBD) or grafcet (SFC) Function : timing, counting, etc Application-specific functions : rotation, cam timers, 1 calculation, etc Discrete, analogue or potentiometer inputs Relay, solid state or PWM outputs Program protected by a password Integral calendar and clock Specifications Type EC12 Input 8 PNP 8 8 8 PNP 8 PNP 8 PNP 8 NPN 12 PNP 12 12 12 PNP 12 PNP 12 PNP 12 NPN EC 20 Output 4 relays 4 relays 4 relays 4 solid state 4 relays 4 solid state 4 relays 8 relays 8 relays 8 relays 8 solid state 8 relays 8 solid state 8 relays Supply 24 VDC 100 - 240 VAC 24 VAC 24 VDC 12 V DC 12 V DC 24 VDC 24 VDC 100 - 240 VAC 24 VAC 24 VDC 12 V DC 12 V DC 24 VDC Code 88 950 021 88 950 023 88 950 024 88 950 022 88 950 025 88 950 026 88 950 029 88 950 031 88 950 033 88 950 034 88 950 032 88 950 035 88 950 036 88 950 039 Dimensions EC 12 EC 20 125 mm 72 mm I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 82 mm 90 mm 90 mm L1 N I1 I2 I3 I4 I5 I6 I7 I8 82 mm L1 N O1 O 2 O3 O4 59,2 mm 60 mm 112,6 mm 60 mm General characteristics see page 23 To order, see page 6 18 For more information www.crouzet.com Chronos 2 timers 17.5 mm DIN rail mounting Relay or solid state output Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Option of connecting an external power supply to the control input 3-wire sensor control option Specifications Type MUR1 MAR1 MBR1 MCR1 MHR1 MLR1 MUR4 MUR3 MURc3 MXR1 MUS2 MAS5 MHS2 MLS2 2 Functions A - At - B - C- H - Ht - Di - D - Ac - Bw A - At B C H - Ht Li-L A - At - B - C - H - Ht - Di - D - Ac - Bw A - At - B - C - H - Ht-Di - D - Ac - Bw A - At - B - C - H - Ht - Di - D - Ac - Bw Ad - Ah - N - O - P - Pt - Tl - Tt - W A - At - B - C - H - Ht - Di - D - Ac - Bw A H Li - L Output 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay 1 changeover relay Solid state Solid state Solid state Solid state Nominal rating 8A 8A 8A 8A 8A 8A 8A 8A 8A 8A 0.7 A 0.7 A 0.7 A 0.7 A Connections Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals Spring terminals Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals Supply voltage 24 V DC / 24 240 V AC 24 V DC / 24 240 VAC 24V DC / 24 240 V AC 24 V DC / 24 240 V AC 24 V DC / 24 240 V AC 24 V DC / 24 240 V AC 12 V DC / AC 12 240V AC / DC 12 240 V AC/DC 24 V DC / 24 240 V AC 24 240 V AC 24 240V AC / DC 24 240 V AC 24 240 V AC Code 88 826 105 88 826 115 88 826 125 88 826 135 88 826 145 88 826 155 88 826 100 88 826 103 88 826 503 88 826 185 88 826 004 88 826 014 88 826 044 88 826 054 Connections 1 changeover relay output 1 changeover relay output Solid state output U U U + + Y1 A1 15 R A1 Y1 A1 A2 18 R Solid state output Y1 16 15 A1 A-At / H-Ht / B / C / Di-D / Ac / BW - Ad - Ah - N - O - P - Pt - Tl - Tt - W MULTI A2 16 18 Y1 A2 15 R Y1 Li - L A-At / H-Ht / B / C / Di-D / Ac / BW - Ad - Ah - N - O - P - Pt - Tl - Tt - W Solid state output U U A1 A1 Y1 A2 A2 18 R R A2 A/H Y1 L / Li General characteristics see page 45 To order, see page 6 36 For more information www.crouzet.com GRD single or double phase DIN rail mounting GRD range 22.5 mm single phase Single phase Complete, compact units Tailor-made solution to current sinks DIN rail and panel mounting Rating : 12 and 25 A (Triac) -25 A (SCR) Protection by RC filter Optional protection by removable varistor LED display of input status UL-Cul approval and CE marking Specifications Type Current Output voltage Input voltage Zero voltage switching (Triac) 12 A 24 - 280 V AC 20 A 24 - 280 V AC Zero voltage switching (SCR) 25 A 48 - 660 V AC Instantaneous switching (SCR) 25 A 48 - 660 V AC 90 - 140 V AC 4 - 32 V DC 180 - 280 V AC/ DC 90 - 140 V AC 4 - 32 V DC 180 - 280 V AC/ DC 180 - 280 V AC DC 4 - 32 V DC 90 - 140 V AC 4 - 32 V DC Code 84 130 150 84 130 101 84 130 100 84 130 152 84 130 103 84 130 102 84 130 118 84 130 116 84 130 158 84 130 117 Connections 5 GRD range - single-phase with triac 4 GRD range - single-phase with SCR Zero voltage switching 1 3 1 U 2 2 4 2 4 3 1 3 U 4 + 3 GRD range - single-phase with SCR Instantaneous switching 1 + 2 Curves GRD range 22.5 mm - 12 A (Triac) I (A) I(A) 12 10 8 6 4 I (A) 25 25 20 20 15 15 10 10 5 2 0 25 A (SCR) GRD range 22.5 mm - 25 A (Triac) 0 0 10 20 30 40 50 60 70 t ( C) 5 0 10 25 40 50 60 70 t ( C) 0 0 10 25 40 50 60 70 t ( C) To order, see page 6 162 For more information www.crouzet.com GRD single or double phase DIN rail mounting GRD Range 45 mm single phase Single phase Complete, compact units Tailor-made solution to current sinks DIN rail and panel mounting Rating : 35 and 45 A Back-to-back SCRs Protection by RC filter Optional protection by removable varistor LED display of input status UL-Cul approval and CE marking Specifications Type Zero voltage switching SCR output Instantaneous switching Thyristor output Current 35 A Output voltage 48 - 660 V AC 45 A 48 - 660 V AC 35 A 45 A 48 - 660 V AC Input voltage 90 - 280 V AC / DC 4 - 32 V DC 90 - 280 V AC / DC 4 - 32 V DC 4 - 32 V DC Code 84 130 110 84 130 111 84 130 115 84 130 113 84 130 112 84 130 114 General characteristics Output characteristics Voltage range (Vrms max) Peak voltage - t = min (V) Maximum off-state leakage at Vmax and T = 25 C (mAeff per phase) Minimum current mA(rms) Max. 1-cycle surge A(peak) Max. 1-second surge A(peak) On-state voltage drop at Imax and T = 25 oC V(peak) I t (t = 10 ms) (A2s) 5 Static (off-state) dv/dt (V/s) Supply frequency range Cos (Zero voltage) Rth junction / ambient air (oC/W) Inputs specifications Input voltage Turn-off voltage (V) Maximum current at Vmax Nominal input resistance (k) Response time (close) (ms) Response time (open) (ms) General characteristics Operating temperature Temperature stored Input to output insulation voltage V(rms) Dielectric strength V(rms) Input/output capacitance (pF) Material housing Material baseplate Weight (g) Input terminal capacity Output terminal capacity 48-660 1000 (1) 4 100 750 145 1.6 35A : 1260 45A : 5000 500 47 80 > 0.5 35A : 3.78 C 45A : 1.65 C/W 35A : 80-280 AC/DC 45A : 4-32 DC 35A : 10 Veff 45A : 1 V DC 35A : 10 mAeff 45A : 12 mA 35A : 45 45A : 3 35A : 20 ms 45A : 0.5 cycle max. 35A : 30 ms 45A : 0.5 cycle max. -20 +80 C -40 +100 C 4000 2500 8 Self-extinguishing (UL 94 V0) aluminium 490 O 2 mm max. O 5.6 mm max. To order, see page 6 164 For more information www.crouzet.com GRD three-phase DIN rail mounting GRD Range 90 mm 3 phase Three-phase Complete, compact units Tailor-made solution to current sinks DIN rail and panel mounting Rating : 3 x 25 A Back-to-back SCRs Protection by RC filter Optional protection by removable varistor LED display of input status UL-Cul approval and CE marking Specifications Type SCR zero voltage switching Current 3 x 20 A Output voltage 48 - 660 V AC SCR Instantaneous switching 3 x 20 A 48 - 660 V AC Input voltage 90 - 280 V AC / DC 4 - 32 V DC 4 - 32 V DC Code 84 130 311 84 130 310 84 130 312 General characteristics Output characteristics Voltage range (Vrms max) Peak voltage (1 min) V(peak) Maximum current Maximum off-state leakage at Vmax and T = 25 C (mAeff per phase) Minimum current (mArms per phase) Max 1 cycle surge T = 25 oC A(rms) Max 1 second surge T = 25 oC A(rms) On-state voltage drop at Imax and T = 25 oC V(peak) I t (t = 10 ms) (A2s) Static (off-state) dv/dt (V/s) Supply frequency range Cos (Zero voltage) Rth junction / ambient air (oC/W) Inputs specifications Input voltage 5 Turn-off voltage (V) Maximum current at Vmax Nominal input resistance (k) Response time (close) (ms) Response time (open) (ms) General characteristics Operating temperature (oC) Storage temperature (0C) Input to output insulation voltage V(rms) Dielectric strength V(rms) Material housing Material baseplate Input/output capacitance (pF) Weight (g) 48-660 1200 3x35 (A) 20 100 500 145 1.6 1260 500 47 80 Hz > 0.5 1 C/W 90-280 AC/DC 4-32 DC 10 Veff 1 V DC 10 mAeff 10 mA 45 3 20 ms 0.5 cycle max. 30 ms 0.5 cycle max. -20 +80 -40 +100 4000 2500 Self-extinguishing (UL 94 V0) aluminium 8 940 To order, see page 6 166 For more information www.crouzet.com GRD double phase DIN rail mounting GRD Range 90 mm double phase Double phase Complete, compact units Tailor-made solution to current sinks DIN rail and panel mounting Rating : 2 x 25 A Back-to-back SCRs Protection by RC filter Optional protection by removable varistor LED display of input status UL-Cul approval and CE marking Specifications Type SCR zero voltage switching Current 2 x 25 A Output voltage 48 - 660 V AC SCR Instantaneous switching 2 x 25 A 48 - 660 V AC Input voltage 90 - 280 V AC / DC 4 - 32 V DC 4 - 32 V DC Code 84 130 222 84 130 220 84 130 221 General characteristics Output specifications Voltage range (Vrms max) Peak voltage (1 min) V(peak) Maximum current Maximum off-state leakage at Vmax and T = 25 C (mAeff per phase) Minimum current (mArms per phase) Max 1 cycle surge T = 25 oC A(rms) Max 1 second surge T = 25 oC A(rms) On-state voltage drop at Imax and T = 25 oC V(peak) I t (t = 10 ms) (A2s) Supply frequency range Cos (Zero voltage) Rth junction / ambient air (oC/W) Inputs specifications Input voltage 5 Turn-off voltage (V) Maximum current at Vmax Nominal input resistance (k) Response time (close) (ms) Response time (open) (ms) General characteristics Operating temperature (oC) Storage temperature (0C) Input to output insulation voltage V(rms) Dielectric strength V(rms) Input/output capacitance (pF) Material housing Material baseplate Weight (g) 48-660 1200 2500 2x25A 100 500 135 1.6 1260 47 80 Hz > 0.5 0.95 90-280 AC/DC 4-32 DC 10 Veff 1 V DC 10 mAeff 10 mA 45 3 20 ms 0.5 cycle max. 30 ms 0.5 cycle max. -20 +80 -40 +100 4000 2500 8 Self-extinguishing (UL 94 V0) aluminium 940 To order, see page 6 168 For more information www.crouzet.com