Lightning/surge arrester type 1/2-VAL-MS-T1/T2 48/12.5/1+0-2801241
Technical data
Protective circuit
IEC test classification I / II
T1 / T2
EN type T1 / T2
Nominal voltage UN60 V AC/DC
- 48 V DC (RRH)
Maximum continuous operating voltage UC75 V AC
100 V DC
UT (TOV-proof) 100 V AC (5 s)
130 V DC (5 s)
Nominal frequency fN50 Hz (60 Hz)
Residual current IPE ≤ 0.6 mA
Standby power consumption PC≤ 90 mVA
Max. discharge current Imax (8/20) µs 30 kA
Nominal discharge current In (8/20) µs 12.5 kA
Impulse discharge current (10/350)µs charge 6.25 As
Impulse discharge current (10/350)˽µs, specific energy 39 kJ/Ω
Impulse discharge current (10/350)˽µs, peak value limp 12.5 kA
Voltage protection level Up≤ 0.4 kV
Voltage protection level Up (L+) - (L-) ≤ 0.4 kV
Voltage protection level Up (L+/L-) - PE ≤ 0.4 kV
Residual voltage ≤ 0.4 kV
≤ 0.35 kV (at 10 kA)
≤ 0.3 kV (at 5 kA)
≤ 0.25 kV (at 3 kA)
Residual voltage (L+) - (L-) ≤ 0.4 kV
Residual voltage (L+/L-) - PE ≤ 0.4 kV
Response time ≤ 25 ns
Max. backup fuse with branch wiring 160 A (gL/gG)
Max. backup fuse with V-type through wiring 80 A (gL / gG)
Short-circuit resistance IP with max. backup fuse (effective) 25 kA
Connection, protective circuit
Connection method Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M5