Industrial Control Transformers
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© January 2017
192
SBE - Open Style, Copper Wound - SBE performance in larger VA (1500 - 5000) sizes
The open style SBE Series provides voltage regulation
in excess of NEMA recommendations without
exceeding 55oC rise. These higher power capacity
transformers are the best choice when 80% or more
of the load components are electromagnetic devices.
Features
Interleaved copper windings reduce I2R losses
and maximize efciency.
Ratings 60 Hz unless noted 50/60 Hz
Meets or exceeds electrical requirements of
NEMA, ANSI, NMTBA and JIC
55°C rise, 105°C insulation system
High quality silicon steel core
Certifications and Compliances
Listed: E77014 - Type SZO
- UL 5085-1, UL 5085-2
Certied LR14328-4
- CSA C22.2 No. 66.1, No. 66.2
RoHS Compliant
Related Products
Linear Power Supplies
DIN Rail DC Power Supplies
Constant Voltage Transformers
Selection Table
Group 1 – 240 X 480 Volt Primary, 120 Volt Secondary 60 Hz
230 X 460 Volt Primary, 115 Volt Secondary 50/60 Hz
220 X 440 Volt Primary, 110 Volt Secondary 50/60 Hz
VA Catalog
Number
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Mtg
Width
in (mm)
Mtg
Depth
in (mm)
Slot Size
in (mm)
Approx.
Ship Weight
lbs (kg)
1500 Y1500 6.25
(158.8)
6.75
(171.5)
8.75
(222.3)
5.75
(146.1)
6.38
(162.1)
.44 x .69
(11.2 x 17.5) 43.0 (19.55)
2000 Y2000 6.25
(158.8)
6.75
(171.5)
10.00
(254.0)
5.75
(146.1)
7.75
(196.9)
.44 x .69
(11.2 x 17.5) 55.0 (25.00)
3000 Y3000 8.00
(203.2)
9.00
(228.6)
9.63
(244.6)
8.00
(203.2)
6.00
(152.4)
.44 x .69
(11.2 x 17.5) 74.0 (33.64)
5000 Y5000 8.00
(203.2)
9.00
(228.6)
12.00
(304.8)
8.00
(203.2)
8.75
(222.3)
.44 x .69
(11.2 x 17.5) 120.0 (54.55)
Note: Fuse holders are not available for this voltage conguration.
Design Style
E77014 LR14328-4
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Sola/Hevi-Duty:
Y1500 Y2000 Y3000 Y5000