M1BVR Battery Voltage Alarm Relay Relais d ' alarme du voltage de la batterie Batteriespannung / Alarmrelais TIMING DIAGRAM DIAGRAMME DES TEMPS ZEITDIAGRAMM CONNECTION DIAGRAM DIAGRAMME DE CONNECTION SCHALTBILDANSCHLUSS Supply/Monitoring Input MOUNTING DETAILS INSTRUCTIONS DE MONTAGE MONTAGEAUFUHRUNGEN Supply/Monitoring -ve HYST 89 (excl. clips) +ve 45 Insert screwdriver to release clips A1 15 LEVEL 49 59 Withdraw clips fully when surface mounting 16 18 93 (+/- 1mm) A2 Width / largeur / Breite. 17.5 mm (DIN 43880) t UNDER VOLTAGE - ADJUSTABLE TRIP LEVEL DELAY FROM FAULT - ADJUSTABLE INSTALLATION AND SETTING MONTAGE ET MISE AU POINT Troubleshooting - Check wiring and voltage present. - Check polarity. - AVANT MONTAGE, ISOLER L ' ALIMENTATION - Branchement comme indique dans le diagramme cidessus. - Regler le niveau de deplacement et le delai. - Appliquer la puissance (LED verte allumee, LED rouge allumee, contacts 15 et 18 fermee). Intervention (pour regler un probleme) - Verifier les fils et le voltage present. - Verifier la polarisation. UNTERSPANNUNG NIVEAUVERSCHIEBUNG EINSTELLBAR VERZOGERUNG DURCH FEHLER EINSTELLBAR EINBAU UND EINSTELLUNG Installation Arbeit mu von qualifiziertem Personal durchgefuhrt werden. Des travaux d'installation doivent etre menes a bien par le personnel qualifie. Installation work must be carried out by qualified personnel. - BEFORE INSTALLATION, ISOLATE THE SUPPLY - Connect the unit as shown in the diagram above. - Set trip level and delay. - Apply power (green LED on, red LED on, contacts 15 and 18 closed). SOUS-VOLTAGE - NIVEAU DE DEPLACEMENT ADJUSTABLE DELAI DE DEFAILLANCE - VOR EINBAU DIE STROMVERSORGUNG ISOLIEREN - Stromversorgung anschliessen wie im Schaltbild unten angezeig. - Standverschiebung und Verzogerung eingeben. - Energie anbringen (LED grun an, LED rot an, Kontakte 15 und 18 geschlossen). Storungsbehebung - Uberprufung von Leitungen und gegenwartiger Spannung. - Uberprufung von Polung (nur fur Gleichstromversorgung). TECHNICAL SPECIFICATION FICHES TECHNIQUES TECHNISCHE DATEN Supply/monitored voltage U: Supply variation: Power consumption: Trip level: Hysteresis: Time delay (t): Accuracy Trip level: Time delay: Ambient temperature: Relative humidity: Contact rating: Voltage d ' alimentation controlee U: Variation d ' alimentation: Puissance consommee: Niveau de deplacement: Hysterese: Delai de temps (t): Precision Niveau de deplacement: Delai de temps: Temperature ambiante: Humidite relative: Evaluation du contact: Stromversorgung / Spannungskontrolle U: Wechselversorgung: Energieverbrauch: Standverschiebung: Hysterese: Zeitsteuerung (t): Genauigkeit Standverschiebung: Zeitsteuerung: Umgebungstemperatur: Allgemeiner Feuchtigkeitsgehalt: Kontakt Belastung: Electrical life: Housing: Weight: Mounting option: Terminal conductor size: Approvals: 12 - 24V DC 0.75 - 1.25 x Un < 1.8W 9 - 28V 5% 1 - 30S (from fault) 10% 20% -20 to +60C +95% 1 x C.O. AC1 250V AC 8A (2000VA) AC15 250V AC 5A (no), 3A (nc) DC1 25V DC 8A (200W) 150,000 (AC1) to UL94 VO 60g to BS5584:1978 (EN50 002, DIN 46277-3) 2 x 2.5mm2 solid / stranded Conforms to: UL, CUL, CSA, IEC. CE and Compliant The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user's own risk Duree de vie electrique: Boitier: Poids: Option de montage: Taille du conducteur terminal: Homologations: 12 - 24V DC 0.75 - 1.25 x Un < 1.8W 9 - 28V 5% 1 - 30S (defaillance) 10% 20% -20 a +60C +95% 1 x Inverseur AC1 250V AC 8A (2000VA) AC15 250V AC 5A (travail), 3A (repos) DC1 25V DC 8A (200W) 150,000 (AC1) a UL94 VO 60g a BS5584:1978 (EN50 002, DIN 46277-3) 2 x 2.5mm2 toron / multifilaire Se conformer a: UL, CUL, CSA, IEC. CE et Deference Les indications contenues dans ce document sont exactes (sous reserve de changement sans avis prealable) toutefois aux risques et perils de l ' utilisateur 12 - 24V DC 0.75 - 1.25 x Un < 1.8W 9 - 28V 5% 1 - 30S (Fehlsteuerung) 10% 20% -20 bis +60C +95% 1 x Wechsler AC1 250V AC 8A (2000VA) AC15 250V AC 5A (Schlieer), 3A (Offner) DC1 25V DC 8A (200W) Elektrische Lebensdauer: 150,000 (AC1) Gehause: bis UL94 VO Gewicht: 60g Befestigungswahl: bis BS5584:1978 (EN50 002, DIN 46277-3) Anschlussklemme / Kabelgrosse: 2 x 2.5mm2 Festdraht / Litze Genehmigungen: Anmerkung: UL, CUL, CSA, IEC. CE und Ubereinstimmung Es handelt sich in diesen Unterlagen um uns genau bekannte Angaben, (Anderungen vorbehalten) jedoch diese Anderungen laufen auf eigene Gefahr des Benutzers. M1BVR-1-B Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England H+44 (0) 1902 773746 G+44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com