http://www.tracopower.com Page 2 of 5
Metal Case Power Supplies
TXH Series 120–480 Watt
Input Specifications
Input voltage – nominal 100 – 240 VAC
– AC range (universal input) 90 – 264 VAC
– DC range 120 – 370 VDC
Input frequency 47 – 63 Hz
Earth leakage current (240 VAC / 63 Hz) 360 W models: 300 µA max.
other models: 500 µA max.
Input current at full load – at 115 VAC / 230 VAC 120 W models: 1.2 A typ. / 0.6 A typ.
240 W models: 2.3 A typ. / 1.1 A typ.
360 W models: 3.6 A typ. / 1.8 A typ.
480 W models: 5.1 A typ. / 2.5 A typ.
Recommended circuit breaker 120 W models: 3.15 A
(characteristic C) or slow blow fuse 240 W models: 5 A
360 W models: 6.3 A
480 W models: 10 A
Output Specifications
Voltage set accuracy ±2 % max.
Output voltage adjustment range details see table page 1
Regulation – Input variation 1 % max.
– Load variation (0–100%) 1 % max.
Minimum load not required
Ripple and noise (20 MHz bandwidth) [mVp-p] max. Models: 12 VDC 24 VDC 48 VDC
120 W 120 240 480
240 W 120 200 200
360 W 150 200 200
480 W 100 200 300
Hold-up time 10 ms min.
Current limitation 130 - 150 % foldback, auto recovery
Short circuit protection indefinite,
360 & 480 W models: auto recovery
120 & 240 W models: no auto recovery (power disconnect required)
Overvoltage protection by Zener diode 120 % of Vout typ.
360 & 480 W models: auto recovery
120 & 240 W models: no auto recovery (power disconnect required)
Overtemperature protection for 360 & 480 W models only, auto recovery
Capacitive load, [µF] max. Models: 12 VDC 24 VDC 48 VDC
120 W 23‘000 10‘000 470
240 W 23‘000 10‘000 470
360 W 85‘000 48‘000 13‘000
480 W 180‘000 75‘000 25‘000
General Specifications
Temperature ranges – Operating 480/360/120 W models: –25°C to +70°C
other models: –10°C to +70°C
– Storage (non operating) –25°C to +85°C
Derating – Ambient temperature all models: 2.5 %/K above +50°C
TXH 480 -122: 2.0 %/K below 5°C
– Low input voltage TXH 480 -122: 0.35 %/V below 180 VAC
other models 1.0 %/V below 100 VAC
Temperature coefficient 0.03 %/K
Humidity (non condensing) 95 % rel max.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.