Sensing and Control
!
WARNING
MISUSE OF DOCUMENTATION
• The information presented in this product
sheet (or catalogue) is for reference only.
DO NOT USE this document as product
installation information.
• Complete installation, operation and
maintenance information is provided in the
instructions supplied with each product.
Failure to comply with these instructions
could result in death or serious injury.
943 Series
Ultrasonic Distance Sensors
Analogue voltage output
0-10 V and 4-20 mA
Beam angle: 8°
Supply voltage: 15 to 30 V
Sealing: IP67
M30
Housing: M30 x 1,5 mm plastic (PBTB)
Max. sensing distance: 3500 mm
Min. sensing distance: 300 mm
Response time: 400 ms
Repeatability: 0,2 % or ±2 mm
OUTPUT TERMINATION REFERENCE
0-10 V Connector 943-T4V-2D-1C0-130E
0-10 V Cable 943-T4Y-2D-1C0-130E
4-10 mA Connector 943-T4V-2D-1D0-130E
4-20 mA Cable 943-T4Y-2D-1D0-130E
M18
Housing: M18 x 1,0 mm plastic (PBTB)
Max. sensing distance: 2000 mm
Min. sensing distance: 200 mm
Switching frequency: 250 ms
Repeatability: 0,2 % or ±2 mm
OUTPUT TERMINATION REFERENCE
0-10 V Connector 943-F4V-2D-1C0-180E
0-10 V Cable 943-F4Y-2D-1C0-180E
4-10 mA Connector 943-F4V-2D-1D0-180E
4-20 mA Cable 943-F4Y-2D-1D0-180E
Max. sensing distance: 800 mm
Min. sensing distance: 100 mm
Switching frequency: 100 ms
Repeatability: 0,2 % or ±1 mm
OUTPUT TERMINATION REFERENCE
0-10 V Connector 943-F4V-2D-1C0-300E
0-10 V Cable 943-F4Y-2D-1C0-300E
4-10 mA Connector 943-F4V-2D-1D0-300E
4-20 mA Cable 943-F4Y-2D-1D0-300E
Max. sensing distance: 500 mm
Min. sensing distance: 60 mm
Switching frequency: 100 ms
Repeatability: 0,2 % or ±1 mm
OUTPUT TERMINATION REFERENCE
0-10 V Connector 943-F4V-2D-1C0-330E
0-10 V Cable 943-F4Y-2D-1C0-330E
4-10 mA Connector 943-F4V-2D-1D0-330E
4-20 mA Cable 943-F4Y-2D-1D0-330E
!
WARNING
PERSONAL INJURY
DO NOT USE these products as safety or emergency stop devices, or in any other application
where failure of the product could result in personal injury.
Failure to comply with these instructions could result in death or serious injury.
OPTIONS AND ORDER GUIDE
2 switching outputs
PNP NO and NPN NO
Beam angle: 8°
Supply voltage: 12 to 30 V
Sealing: IP67
M30
Housing: M30 x 1,5 mm plastic (PBTB)
Max. sensing distance: 3500 mm
Min. sensing distance: 300 mm
Switching frequency: 1.0 Hz
Repeatability: 0,2 % or 2 mm
OUTPUT TERMINATION REFERENCE
PNP, 2 NO/NC Connector 943-T4V-2D-001-130E
PNP, 2 NO/NC Cable 943-T4Y-2D-001-130E
NPN, 2 NO/NC Connector 943-T4V-2D-002-130E
NPN, 2 NO/NC Cable 943-T4Y-2D-002-130E
M18
Housing: M18 x 1,0 mm plastic (PBTB)
Max. sensing distance: 2000 mm
Min. sensing distance: 200 mm
Switching frequency: 1.2 Hz
Repeatability: 0,2 % or 2 mm
OUTPUT TERMINATION REFERENCE
PNP, 2 NO/NC Connector 943-F4V-2D-001-180E
PNP, 2 NO/NC Cable 943-F4Y-2D-001-180E
NPN, 2 NO/NC Connector 943-F4V-2D-002-180E
NPN, 2 NO/NC Cable 943-F4Y-2D-002-180E
Max. sensing distance: 800 mm
Min. sensing distance: 100 mm
Switching frequency: 4.7 Hz
Repeatability: 0,2 % or 1 mm
OUTPUT TERMINATION REFERENCE
PNP, 2 NO/NC Connector 943-F4V-2D-001-300E
PNP, 2 NO/NC Cable 943-F4Y-2D-001-300E
NPN, 2 NO/NC Connector 943-F4V-2D-002-300E
NPN, 2 NO/NC Cable 943-F4Y-2D-002-300E
Max. sensing distance: 500 mm
Min. sensing distance: 60 mm
Switching frequency: 4.7 Hz
Repeatability: 0,2 % or 1 mm
OUTPUT TERMINATION REFERENCE
PNP, 2 NO/NC Connector 943-F4V-2D-001-330E
PNP, 2 NO/NC Cable 943-F4Y-2D-001-330E
NPN, 2 NO/NC Connector 943-F4V-2D-002-330E
NPN, 2 NO/NC Cable 943-F4Y-2D-002-330E
The new 943 series industrial
sensors are the latest addition to
our product range. They have
improved scanning ranges, remote
teach in of the switching or
analog outputs, as well as new
advanced features, such as window
and hysteresis modes.
M18
CONNECTOR
3,5
CABLE
M30
CONNECTOR
M30 x 1,5
5,0 11,2
CABLE
5,0
M30 x 1,5
123,5 ±0,5
90 ±0,5 2000 ± 100
M18/M30
Termination: Connector M12 x 1
Cable Preleaded 2 m