Box Cover Units
For Plug Fuses
Plug fuse box cover units provide a simple, inexpensive way
to protect small motors with Edison-type “T”, “TL”, “TC”, “P”
and “W” plug fuses. Box cover units are easily installed in
standard electrical boxes. By using fuses sized at the amp
rating of a motor or slightly larger, optimum overload and
short-circuit protection is provided. Box cover units are UL
Listed.
Fuse Holder
On/Off Switch
Receptacle
Switch Light
SSY-RL
Selection Data — Plug Fuse Box Cover Units
Receptacle Motor Agency†
Box Cover Fuseholder Outlet to Load Switch Switch Size Listing/
Cat. No. Type Box Single Double 125Vac 250Vac Control+ Light++ (Max.) General Data Certification
SOU X3⁄4Hp 125V, 15A UL, CSA
SRU 2 1⁄4" Handy X X 1⁄2Hp 125V, 15A UL
SSU XX
1⁄2Hp 125Vac (do not use on DC), 15A UL, CSA
SOW X3⁄4Hp 125V, 15A UL, CSA
SRW 2 3⁄4" Switch X X 1⁄2Hp 125V, 15A UL
SSW XX
1⁄2Hp 125Vac (do not use on DC), 15A UL, CSA
SOX X3⁄4Hp 125V, 15A UL, CSA
SRX 4" Octagon X X 1⁄2Hp 125V, 15A UL
SSX XX
1⁄2Hp 125Vac (do not use on DC), 15A UL, CSA
SOY X3⁄4Hp 125V, 15A UL, CSA
SRY XX 1⁄2Hp 125V, 15A UL
SSY XX
1⁄2Hp 125Vac (do not use on DC), 15A UL, CSA
SSY-RL 4" Square X X X X 1⁄2Hp 125Vac (do not use on DC), 15A —
STY* XX*
1⁄2Hp* 125Vac (do not use on DC)*, 15A UL
SCY** X X(2)** 1⁄2Hp(2)** 125Vac (do not use on DC); UL
can protect two motors**, 15A
SOY-B X3⁄4Hp 125V, protects two motors, 15A UL
SKA 4 11⁄16" Square X X(15A) 2 Hp 250V, 15A single-phase UL
SSN Single Gang X X 1⁄2Hp 125V, 15A Weatherproof UL
+ Switch turns power to fused load OFF or ON.
++ Switch light indicates power to load (dark when switch OFF or fuse open).
* Double-pole switch opens both sides of circuit. STY can be used for two separate 125V motors not larger than 1⁄2Hp with the common switch, or a single motor not
larger than 2 Hp at 250V (Maximum of 150V to ground).
** The SCY unit can be used for protection of a single motor not larger than 2Hp at 250V (Maximum of 150V to ground).
† UL Guide JAMZ, File E6491; CSA Class 6225-01, File 47235.
Box Cover Units
for Plug Fuses