MICRO SWITCH™ Hazardous Location Limit Switches
Table 3. Circuitry and Electrical Ratings
Rating
code Circuitry Electrical rating
A SPDT
UL/CSA Rating:
15 A, 125, 250, or 480 Vac
1/8 HP, 125 Vac; 1/4 HP, 250 Vac
0.5 A, 125 Vdc; 0.25 A 250 Vdc
B SPDT
UL/CSA Rating:
20 A, 125, 250, or 480 Vac
10 A, 125 Vac “L”
1 HP, 125 Vac; 2 HP, 250 Vac
0.5 A, 125 Vdc; 0.25 A, 250 Vdc
C DPDT
UL/CSA Rating:
10 A, 125 or 250 Vac
0.3 A, 125 Vac; 0.15 A 250 Vdc
D SPDT
UL/CSA Rating:
10 A, 125, 250, or 480 Vac
0.5 A, 125 Vdc; 0.25 A 250 Vdc
E SPDT UL Rating: 1 A, 125 Vac
F SPDT
UL/CSA Rating:
3 A, 125 or 250 Vac
1/10 HP, 125 Vac; 1/6 HP, 250 Vac
G SPDT
UL/CSA Rating:
5 A, 125, 250, or 480 Vac;
0.50 A, 125 Vdc; 0.25 A, 250 Vac
Table 4. Hazardous Location Classifications
Rating
code Classification
1
Explosion Proof-UL listed for Hazardous Locations
NEMA 7, Class I, Groups B, C, and D
NEMA 9, Class II, Groups E, F, and G
2
Explosion Proof-UL listed for Hazardous Locations
NEMA 7, Class I, Groups C and D
NEMA 9, Class II, Groups E, F, and G
3European Hazardous Locations Designation:
Ex dIIB + H2 T6 Category II 2 G
4European Hazardous Locations Designation:
Ex dIIB + H2 T2 Category II 2 G
Series Code ATEX Temperature Rating
EX T6 -40 °C to 70 °C [-40 °F to 158 °F]
EXHT T2 -40 °C to 204 °C [-40 °F to 400 °F]