A600
Q600
Pilot Duty of Contact Elements acc. UL508
Technical UL/CSA
—
snap action contacts Action Type of the Contact Element (acc. to IEC 60947-
5-1)
Ø22 mm stainless steel roller lever Actuator Type
acc. to IEC 60947-5-1 Max. 1.50 MTS
acc. to IEC 60947-5-1 Min. 0.00 MTS
Actuation Speed
acc. to IEC 60947-5-1 Min. 0.15 N·m Actuation Torque
adjustable head every 90° Angular Head Adjustment
9° in 9° Angular Lever Adjustment
according to IEC 68-2-3 and salty mist according to IEC 68-2-11 Climatic Withstand
acc. to IEC 60947-5-1, q = 40 °C 10 A Conventional Free-air Thermal Current (Ith)
Bar AWG 20 ... AWG 14
Bar 0.5 ... 2.5
Connecting Capacity
0.05 mm Consistency (Measured over 1 Million Operations)
Zb Contact Element Form (acc. to IEC 60947-5-1)
M3.5 (+,-) pozidriv 2 screw with cable clamp Connecting Terminals (delivered in open position)
acc. to IEC 60529 IP66 Degree of Protection
Class I Electrical Shock Protection acc. to IEC 536
3600 cycles per hour
AC-15 3600 cycles per hour
DC-13 3600 cycles per hour
Maximum Electrical Switching Frequency
25 million Mechanical Durability
2 or 4 x M5 screws Mounting by Screws (not supplied)
all positions are authorised Mounting Position
30° Cam Translation Movement Movement to be Detected
1 Number of Auxiliary Contacts NC
1 Number of Auxiliary Contacts NO
1/2 NPT cable gland Number and Type of Bottom Cable Glands
A shape acc. EN 50041 Operating Head Shape
1 piece Order Multiple
Minimum Torque acc. to IEC 60947-5-1 0.32 N·m Positive Opening Operation Torque (Direct Opening
Action)
Yes Positive Opening Operation of NC Contact(s)
LS40 Product Main Type
Limit Switch Product Name
Supply Circuit 50 60 Hz Rated Frequency (f)
6 kV Rated Impulse Withstand Voltage (Uimp)
acc. to UL/CSA 600 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 500 V
Rated Insulation Voltage (Ui)
(230 V AC) 3.1 A
(240 V) 3 A
(400 V) NC 4 A
(130 V) 5.5 A
(24 V) 10 A
Rated Operational Current AC-15 (Ie)
(125 V) 0.55 A
(24 V) 6 A
(250 V) 0.4 A
Rated Operational Current DC-13 (Ie)
Additional Information
—
2LS45M42B11