IB IL AO 4/8/U/BP-PAC Order No.: 2878036
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878036
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 8, 2011
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Interface
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 kbps
500 kBit/s
Transmission physics Copper
Inline potential routing
Communications power UL7.5 V DC (via voltage jumper)
Current consumption from ULTyp. 80 mA
I/O supply voltage UANA 24 V DC
Current consumption from UANA Typ. 72 mA
Analog outputs
Number of outputs 8
Connection method 2-wire (shielded)
Output name Analog outputs
Type of protection Transient protection of outputs
Data formats IB IL, IB ST, IB RT, standardized representation, S7 compatible
Measured value representation 16 bits (15 bits + sign bit)
Process data update < 2 ms (depends on operating mode)
Voltage output signal 0 V ... 10 V
-10 V ... 10 V
0 V ... 5 V
-5 V ... 5 V
Load/output load voltage output > 2 kΩ 0.05 %
Precision Typ. 0.1 % (of output range final value)