https://www.phoenixcontact.com/us/products/2308072
09/03/2014Page2/5
Universal current transducer-MCR-SL-CUC-400-I-2308072
Technical data
Input data
Input current range 0 A ... 400 A
Overload capacity 2.5 x IIN
Frequency measuring range 20 Hz ... 6000 Hz (0 Hz)
Connection method Cable design: 32 mm diameter
Output data
Output name Current output
Current output signal 4 mA ... 20 mA
Max. output current < 25 mA
Load/output load current output < 300 Ω
Switching output
Output name No switching output
Power supply
Nominal supply voltage 24 V DC
Supply voltage range 20 V DC ... 30 V DC
Max. current consumption (30 + IOUT) mA
Power consumption 1.65 W
Connection data
Conductor cross section solid min. 0.25 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Stripping length 10 mm
General
Maximum transmission error <± 1 % (of final value)
Temperature coefficient, typical 0.02 %/K (0 ... 60°C)
0.04 %/K (-40 ... 65°C)
Linearity error <± 1 % (From the range end value)
Step response (10-90%) 150 ms
Surge voltage category III
Pollution degree 2
Rated insulation voltage 300 V AC
Test voltage input/output 3.5 kV (50 Hz, 1 min.)
Test voltage input/power supply 3.5 kV (50 Hz, 1 min.)