ASI Buy Direct On-Line Make It EZ - Save 20 - 50% www.asi-ez.com Automation Systems Interconnect, Inc. Innovative Interconnect and Interface Solutions Miniature Circuit Breakers - QL Series QL Series These circuit breakers are specifically intended to provide service entrance, feeder, and branch circuit protection. Features l l l l l l l QL Time Delay Curve l UL 489 File E192487 Convenient DIN Rail Mounting Compact Housing Design Only 13 mm One or Two Pole Shock-Proof Connections Easy To Wire, Clamp Connections Other Configurations Available Upon Request 10 Year Warranty Percentage of Rated Current Lim its 125 150 200 400 600 KM Min. (sec) 15 8 4 KM Max.(sec) 300 90 28 800 1000 Technical Data 0.7 0.09 0.007 0.005 4 1.5 0.5 Number of Poles Max. Voltage Min. Amp Rating Max Amp Rating Interrupting Capacity Dielectric Strength Insulation Resistance Operating Temp. Range 0.4 Trip time listed in seconds. QL Series Dimensions 1, 2 120/240V, 50/60 Hz .5 Amp 25 Amp 10,000A 1500V, 50/60 Hz 100 Megaohm -40 C to +60 C Ordering Information Single Pole Two Pole Rated Current Catalog Number Pcs/Pkg Catalog Number Pcs/Pkg .5 A QL113D M K M 0.5 12 - - 1A QL113D M K M 01 12 - - 2A QL113D M K M 02 12 - - 3A QL113D M K M 03 12 - - 5A QL113D M K M 05 12 QL213D M K M 05 6 10A QL113D M K M 10 12 QL213D M K M 10 6 15A QL113D M K M 15 12 QL213D M K M 15 6 20A QL113D M K M 20 12 QL213D M K M 20 6 25A QL113D M K M 25 12 QL213D M K M 25 6 Note: Other current ratings and trip curves available upon request. To locate additional product specifications and technical drawings go to www.asi-ez.com Automation Systems Interconnect, Inc. l P.O. Box 1230 l Carlisle, PA 17013-1230 l Phone (717) 249-5581 or (877) 650-5160 l Fax (717) 249-5542