QL Series
These circuit breakers are specifically intended to
provide service entrance, feeder, and branch circuit
protection.
Features
lUL 489 File E192487
lConvenient DIN Rail Mounting
lCompact Housing Design Only 13 mm
lOne or Two Pole
lShock-Proof Connections
lEasy To Wire, Clamp Connections
lOther Configurations Available Upon Request
l10 Year Warranty
Technical Data
Number of Poles 1, 2
Max. Voltage 120/240V, 50/60 Hz
Min. Amp Rating .5 Amp
Max Amp Rating 25 Amp
Interrupting Capacity 10,000A
Dielectric Strength 1500V, 50/60 Hz
Insulation Resistance 100 Megaohm
Operating Temp. Range -40 C to +60 C
Miniature Circuit Breakers - QL SeriesMiniature Circuit Breakers - QL Series
ASI
ASI
Automation Systems Interconnect, Inc.Automation Systems Interconnect, Inc.
Innovative Interconnect and Interface Solutions
Buy Direct On-Line
Make It EZ - Save 20 - 50%
www.asi-ez.com
Automation Systems Interconnect, Inc. lP.O. Box 1230 lCarlisle, PA 17013-1230 lPhone (717) 249-5581 or (877) 650-5160 lFax (717) 249-5542
To locate additional product specifications and technical drawings go to www.asi-ez.com
QL Series Dimensions
Ordering Information
Curve Limits
125 150 200 400 600 800 1000
KM Min. (sec) 15 8 4 0.7 0.09 0.007 0.005
KM Max.(sec) 300 90 28 41.5 0.5 0.4
Percentage of Rated Current
Rated
Current Catalog Number Pcs/Pkg Catalog Number Pcs/Pkg
.5 A QL113D M K M 0.5 12 - -
1A QL113D M K M 01 12 - -
2A QL113D M K M 02 12 - -
3A QL113D M K M 03 12 - -
5A QL113D M K M 05 12 QL213D M K M 05 6
10A QL113D M K M 10 12 QL213D M K M 10 6
15A QL113D M K M 15 12 QL213D M K M 15 6
20A QL113D M K M 20 12 QL213D M K M 20 6
25A QL113D M K M 25 12 QL213D M K M 25 6
Single Pole Two Pole
QL Time Delay
Trip time listed in seconds.
Note: Other current ratings and trip curves available upon request.