100W Single Output with Battery Charger (UPS Function) DRC-100 series
File Name:DRC-100-SPEC 2014-12-19



Bauar
Sicher heit
egel gema
t gepru ft
od
be
www.
ID 2000000000
tuv.com
wac g
o s








SPECIFICATION
100W Single Output with Battery Charger (UPS Function) DRC-100 series
File Name:DRC-100-SPEC 2014-12-19
MODEL
DC VOLTAGE
OUTPUT NUMBER
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME Note.4
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
FUNCTION
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING TEMP.
BATTERY LOW
AC OK
BATTERY CUT OFF
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
2400ms, 50ms/230VAC 2400ms, 50ms/115VAC at full load
50ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
47 ~ 63Hz
87%
CH1:28.98 ~ 37.26V
20±1V
Battery low voltage : < 22V
89%
1.8A/115VAC 1.1A/230VAC
COLD START 30A/115VAC 60A/230VAC
105 ~ 150% rated output power
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
-30 ~ +70 (Refer to "Derating Curve")
10±0.5V
Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A
Battery low voltage : < 11V
20 ~ 90% RH non-condensing
-40 ~ +85, 10 ~ 95% RH
±0.03%/ (0 ~ 50) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
410.1K hrs min. MIL-HDBK-217F (25)
55*90*100mm (W*H*D)
0.37Kg; 30pcs/12.1Kg/0.82CUFT
DRC-100B
27.6V13.8V 27.6V
CH1CH2 CH2
2.25A2.5A 1.25A
0 ~ 3.5A-------- --------
96.6W
240mVp-p-------- --------
-------- --------
-------- --------
-------- --------
CH1:24 ~ 30V
±1.0%
±0.5%
±0.5%
DRC-100A
13.8V
CH1
4.5A
0 ~ 7A
96.6W
120mVp-p
CH1:12 ~ 15V
±1.0%
±0.5%
±0.5%
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH
SAFETY &
EMC
(Note 5)
EMC IMMUNITY
EMC EMISSION
 








INPUT VOLTAGE (V) 60Hz
90 100 125 135 145 155 165 175 180 200 230 264
100
90
80
70
60
50
40
LOAD (%)
175
LOAD (%)
CIRCUIT
CIRCUIT
DETECTION
ALARM
RL1
RL2
O.L.P.
EMI FILTER
&
RECTIFIER
POWER
SWITCHING FILTER
&
RECTIFIERS +V
Bat. +
Battery Charger
&
Back up Control
AC OK
-V
Bat. -
Bat. Low
I/P
CONTROL
PWM
O.V.P.
AMBIENT TEMPERATURE ()
LOAD (%)
230VAC
Input only
20
40
60
80
100
(VERTICAL)
-20 0 15 300 40 45 50-30 60 70
100W Single Output with Battery Charger (UPS Function) DRC-100 series
File Name:DRC-100-SPEC 2014-12-19
Derating Curve Static Characteristics
Block Diagram
Suggested Application
V-V+Bat-Bat+
Load
A : 12V
B : 24V
Battery ++
--
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
Fig 1.1 Suggested system connection
Fig 2.2 Internal circuit of AC OK (Battery Low), via relay contact
2.Alarm signal for AC OK and battery low
(1) Alarm signal is sent out through " AC OK " & " Battery Low " pins via relay contact.
(2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. Please refer to Fig 2.2.
(3) Table2.1 explains the alarm function built in the power supply
(4) AC OK signal (RL1, referring to Block Diagram) will go into hiccup mode when the overload protection is activated.
Function Output of alarm
Low or short
Low or short
High or open (External applied voltage 30V max.)
High or open (External applied voltage 30V max.)
Description
The signal is "Low" when the power supply turns ON.
The signal is "Low" when the voltage of battery is under A:11V, B:22V.
The signal is "High" when the voltage of battery is above A:11V, B:22V.
The signal turns to be "High" when the power supply turns OFF.
AC OK
Battery Low
Table 2.1 Explanation of alarm signal
R
VExternal voltage sorece (V) and resistor (R)
(The max. Sink is 1A and 30V)
AC OK (Battery low)
100W Single Output with Battery Charger (UPS Function) DRC-100 series
File Name:DRC-100-SPEC 2014-12-19
+
DC OK
+V ADJ
Terminal Pin No. Assignment (TB1):
Pin No.
1
2
3
Assignment
AC/L or DC+
AC/N or DC-
FG
Installation Instruction
Back View
35
Case No.973A Unit:mm
Mechanical Specification
Terminal Pin No. Assignment (TB2):
Pin No. Pin No.
1,2
7,8
9,10
6
3,4
5
Assignment Assignment
-V
+V
Bat. +
AC OK
Bat. Low
Bat. -
100W Single Output with Battery Charger (UPS Function) DRC-100 series
File Name:DRC-100-SPEC 2014-12-19
90
123
TB2
TB1
7.57.5
3.81x9
55 100
DC OK
+V ADJ
12345678910
+
This series fits DIN rail TS35/7.5 or TS35/15.
(This diagram is for reference. The rail is not included with unit.)
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Mean Well:
DRC-100B DRC-100A