Data sheet
Creation date February 16, 2021 5:28:40 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 1
PRO ECO 240W 48V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
You are looking for a reliable power supply with basic
functions.
With PROeco we can offer you low-cost switch-mode
power supply units with
high efficiency and system capability. Let’s connect.
In the series production of machines, in particular, switch-
mode power supply units with
above-average performance values can deliver genuine
competitive advantages.
The low-cost PROeco series offers all the basic functions
and delivers impressively
high performance and flexibility.
Our PROeco switch-mode power supply units feature a
compact design, high
efficiency and are extremely easy to maintain. Thanks to
temperature protection,
short-circuit and overload resistance they can be
universally used in all
applications.
Wide-ranging safety functions and compatibility with our
diode and capacitance modules, together with UPS
components for setting up a
redundant power supply, characterise solutions with
PROeco.
General ordering data
Version Power supply, switch-mode power supply unit, 48
V
Order No. 1469590000
Type PRO ECO 240W 48V 5A
GTIN (EAN) 4050118275773
Qty. 1 pc(s).
Data sheet
PRO ECO 240W 48V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date February 16, 2021 5:28:40 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 2
Dimensions and weights
Depth 100 mm Depth (inches) 3.937 inch
Height 125 mm Height (inches) 4.921 inch
Net weight 1.014 g Width 60 mm
Width (inches) 2.362 inch
Temperatures
Storage temperature -40 °C...85 °C Operating temperature -25 °C...70 °C
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Rated data UL
Operating altitude ≤ 3000 m
Input
AC current consumption 1.2 A @ 230 V AC / 2.4 A
@ 115 V AC
AC input voltage range 85...264 V AC (derating at
100 V AC)
Connection system
Screw connection
DC current consumption 1.2 A @ 370 V DC / 2.4 A
@ 120 V DC
DC input voltage range 80...370 V DC (Derating @
120 V DC)
Frequency range AC
47...63 Hz
Input frequency 47...63 Hz Input fuse (internal) Yes
Inrush current
Max. 10 A
Rated input voltage 100...240 V AC (wide-
range input)
Recommended back-up fuse 4 A / DI, safety fuse
10 A, Char. B, circuit
breaker
3...4 A, Char. C, circuit
breaker
Surge protection
Varistor
Output
Capacitive load unrestricted Connection system Screw connection
Nominal output current for Unom 5 A at 55 °C Output power 240 W
Output voltage
48 V
Output voltage 42...56 V (adjustable via
potentiometer)
Output voltage, max. 56 V Output voltage, min. 42 V
Output voltage, note (adjustable via
potentiometer)
Overload protection
Yes
Parallel connection option yes, max. 5 Protection against inverse voltage Yes
Ramp-up time ≤ 100 ms Rated output voltage 48 V DC ± 1 %
Residual ripple, breaking spikes < 100 mV ss @ 48 V DC, I
Nenn
Data sheet
PRO ECO 240W 48V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date February 16, 2021 5:28:40 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 3
General data
AC failure bridging time @ Inom > 20 ms @ 230 V AC / >
20 ms @ 115 V AC
Degree of efficiency
92 %
Earth leakage current, max. 3.5 mA Housing version Metal, corrosion resistant
Indication Green LED (Uoutput >
21.6VDC), Yellow LED
(loutput > 90% IRated
typ. ), red LED (overload,
overtemperature,
short-circuit, Uoutput <
20.4VDC)
MTBF
> 500,000 h in
accordance with IEC
61709 (SN29500)
Max. perm. air humidity (operational) 5 %…95 % RH Mounting position, installation notice on terminal rail TS 35
Operating temperature
-25 °C...70 °C
Power factor (approx.) > 0.94 @ 230 V AC / >
0.99 @ 115 V AC
Protection against over-heating
Yes
Protection against reverse voltages from
the load 58…65 V DC
Short-circuit protection Yes
EMC / shock / vibration
Interference immunity test acc. to EN 61000-4-2 (ESD),
EN 61000-4-3 (RS), EN
61000-4-4 (burst), EN
61000-4-5 (surge), EN
61000-4-6 (conducted),
EN61000-4-8 (Fields),
EN61000-4-11 (Dips)
Limiting of mains voltage harmonic
currents
According to EN
61000-3-2
Noise emission in accordance with
EN55032 Class B
Shock resistance IEC 60068-2-27
15 g In all directions
Vibration resistance IEC 60068-2-6 1 g according to EN
50178
Insulation coordination
Insulation voltage, input/output 3 kV Pollution severity 2
Protection class I, with PE connection
Electrical safety (applied standards)
Electrical machine equipment
Acc. to EN60204
For use with electronic equipment Acc. to EN50178 /
VDE0160
Protection against dangerous shock
currents Acc. to VDE0106-101
Protective separation / protection
against electrical shock
VDE0100-410 / acc. to
DIN57100-410
Safety transformers for switch-mode
power supplies
According to EN
61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , min. 0.5 mm² Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm² Connection system Screw connection
Wire connection cross section, flexible
(input), max. 2.5 mm²
Data sheet
PRO ECO 240W 48V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date February 16, 2021 5:28:40 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 4
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , max. 2.5 mm² Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm² Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection Number of terminals 6 (++,--,13,14)
Signalling
Contact load (NO contact) max. 30 V DC / 1 A Floating contact Yes
Relay on/off Output voltage
>21.6VDC/ <20.4VDC,
overload
Approvals
Certificate no. (cULus) E258476 Institute (cULus) CULUS
Classifications
ETIM 6.0 EC002540 ETIM 7.0 EC002540
ECLASS 9.0 27-04-07-01 ECLASS 9.1 27-04-07-01
ECLASS 10.0 27-04-07-01 ECLASS 11.0 27-04-07-01
Approvals
Approvals
ROHS Conform
UL File Number Search E258476
Downloads
Approval/Certificate/Document of
Conformity Declaration of Conformity
Engineering Data STEP
Engineering Data EPLAN, WSCAD
User Documentation Operating instructions
Data sheet
PRO ECO 240W 48V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Drawings
Creation date February 16, 2021 5:28:40 PM CET
Catalogue status 12.02.2021 / We reserve the right to make technical changes. 5
Electric symbol Derating curve
Derating curve Derating curve