General Purpose US Fuses
General Purpose US Fuses
GPUS1
American Power Fuses
AMP-TRAP 2000®
AJT (Class J TD)
12/04
SMARTSPOT®with Maximum circuit
protection
Amp-trap 2000®SmartSpot®AJT fuses now
provide a visual open fuse indicator. With advanced
material technology added to the existing product line
the AJT fuse provides IEC Type “2” (No Damage)
protection to main, feeder, and branch circuits, for all
types of loads — yet, they require only half the mounting
space needed for 600VAC Class RK fuses. AJT’s time delay
characteristics for handling typical in-rush currents,
its current limiting ability.
Features/Benefits
• Solid State SmartSpot Indicator
• Time delay for motor starting and transformer inrush
• 300kA interrupting rating - self-certified,
UL witnessed tests
• Extremely current limiting for low peak let-thru current
• Most current limiting UL class fuse
• Small footprint requires less mounting space and
allows smaller, more economical fuse blocks
• Easy 2-to-1 selectivity for prevention of nuisance
shutdowns
• Unique Class J dimensions prevent replacement errors
• High-visibility orange label gives instant recognition
• Metal-embossed date and catalog number for
traceability and lasting identification
• Fiberglass body provides dimensional stability in
harsh industrial settings
• High-grade silica filler ensures fast arc quenching
• Optional EI Indicator/Switch mount for AJT70 to
600 open fuse indication
Ratings
AC: 1 to 600A
600VAC, 200kA I.R. (self certified for 600VAC,
300kA I.R.,UL witnessed)
DC: 1 to 600A
500VDC, 100kA I.R.
Highlights
• Smart Spot Indicator
• Time Delay
• Highly Current Limiting
• DC Ratings
• Optional Mechanical Indicator
(70 to 600A fuses)
Applications
• Motor Circuits
• Mains
• Feeders
• Branch Circuits
• Lighting, Heating and General Loads
• Transformers
• Control Panels
• Circuit Breaker Back-up
• Bus Duct
• Load Centers
Approvals
AJT (1-600):
• UL Listed to Standard 248-8
• DC Listed to UL Standard 198L
• CSA Certified to Standard
C22.2 No. 248.8
• IEC 269-2-1
AJT (70-600) EI:
• UL Component Recognized
• DC Tested to UL Standard 198L
General Purpose US Fuses
General Purpose US Fuses
GPUS2
American Power Fuses
AMP-TRAP 2000®
AJT (Class J TD)
12/04
Fuse 600V OR LESS
Ampere 1 Pole 3 pole
Rating Catalog Number Reference Number Catalog Number Reference Number
Standard Fuse Ampere Ratings, Catalog Numbers and Ref Numbers
Recommended Fuse Blocks With Box Connectors for Amp-trap®Class J Fuses
A variety of pole configurations and termination provisions is available.
*For optional indicator/switch mount add EI. For Example: AJT100EI .See table below
Note: Indicator not available for rating 1A to 7A.
1 AJT1 X214748
1-1/4 AJT1-1/4 C215765
1-1/2 AJT1-1/2 B215258
1-6/10 AJT1-6/10 G216275
1-8/10 AJT1-8/10 H216782
2 AJT2 P219364
2-1/4 AJT2-1/4 A200882
2-1/2 AJT2-1/2 T223094
2-8/10 AJT2-8/10 M201422
3 AJT3 Q211683
3-2/10 AJT3-2/10 L212714
3-1/2 AJT3-1/2 W212194
4 AJT4 W214241
4-1/2 AJT4-1/2 Y214749
5 AJT5 H216276
5-6/10 AJT5-6/10 J216783
6 AJT6 D217813
6-1/4 AJT6-1/4 P218329
7 AJT7 Q219365
8 AJT8 M219891
9 AJT9 D222574
10 AJT10 Y217302
12 AJT12 C217812
15 AJT15 N218328
17-1/2 AJT17-1/2 A218845
20 AJT20 Z201939
25 AJT25 X211160
30 AJT30 W213229
35 AJT35 M213727
40 AJT40 C215259
45 AJT45 D215766
50 AJT50 Z217303
60 AJT60 B218846
70 AJT70* L201421*
80 AJT80* W211159*
90 AJT90* V212193*
100 AJT100* B215764*
110 AJT110* F216780*
125 AJT125* A217810*
150 AJT150* Y218843*
175 AJT175* K219889*
200 AJT200* Y200880*
225 AJT225* V211158*
250 AJT250* K212713*
300 AJT300* L213726*
350 AJT350* W214747*
400 AJT400* G216781*
450 AJT450* M218327*
500 AJT500* N219363*
600 AJT600* C222573*
Ampere Catalog Reference Ampere Catalog Reference
Rating Number Number Rating Number Number
0-30 US3J1I M212922 US3J3I K214967
31-60 US6J1I F222047 US6J3I M211381
61-100 61036J Z201640 61038J G212917
101-200 62001J D214455 62003J E214962
201-400 64031J X218543 64033J S219068
401-600 6631J P201125 6633J A201641
General Purpose US Fuses
General Purpose US Fuses
GPUS3
American Power Fuses
AMP-TRAP 2000®
AJT (Class J TD)
12/04
Optional Indicator/Microswitch Mount (EI) dimensions:
Note: Fuses with the EI option will
receive the AOS-S or AOS-Q
Add-On-Switch whiech is
ordered reparately.
AMPERE ABCDE FGH
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
1-30 2-1/4 57 13/16 21 - - ----------
31-60 2-3/8 60 1-1/16 27 - - ----------
61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 14 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
1-60A
70-600A
Dimensions
Catalog Reference A
Number Number
AJT70EI Y201938
AJT80EI P211682 2.80
AJT90EI V214240 (71.0)
AJT100EI F216274
AJT110EI W217300
AJT125EI L218326 3.22
AJT150EI M219362 (81.8)
AJT175EI R223092
AJT200EI K201420
AJT225EI N211681
AJT250EI V213228 3.24
AJT300EI T214239 (82.2)
AJT350EI A215257
AJT400EI X217301
AJT450EI Z218844
AJT500EI L219890 3.61
AJT600EI S223093 (91.8)
General Purpose US Fuses
General Purpose US Fuses
GPUS4
American Power Fuses
AMP-TRAP 2000®
AJT (Class J TD)
12/04
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
Peak Let-Thru Current Data
AJT 30 to 600, 600 Volts AC 230 Volt Three Phase Class J AJT Fuses
Three Phase Motor Fuse Selection
Full Recommended Fuse Ampere Rating
Motor Load Motor Acceleration Times
HP Amperes Minimum Typical Heavy Load
at 230V 2 sec. 5 sec. Over 5 sec.
1/2 2.2 3 3-1/2 4
3/4 3.2 4 5 6
1 4.2 5 6-1/4 8
1-1/2 6 8 9 10
2 6.8 8 10 12
3 9.6 12 15 17-1/2
5 15.2 20 25 30
7-1/2 22 30 35 40
10 28 35 40 50
15 42 50 60 80
20 54 70 80 100
25 68 80 100 125
30 80 100 125 150
40 104 125 150 200
50 130 175 200 250
60 154 200 225 300
75 192 250 300 350
100 248 300 350 450
125 312 400 450 600
150 360 450 500 600
200 480 600 - -
CURRENT IN AMPERES
TIME IN SECONDS
MELTING TIME – CURRENT DATA, 600V FUSES
AJT 1 to 600
General Purpose US Fuses
General Purpose US Fuses
GPUS5
American Power Fuses
AMP-TRAP 2000®
AJT (Class J TD)
12/04
575 Volt Three Phase Class J AJT Fuses380 Volt Three Phase Class J AJT Fuses
Full Recommended Fuse Ampere Rating
Motor Load Motor Acceleration Times
HP Amperes Minimum Typical Heavy Load
at 380V 2 sec. 5 sec. Over 5 sec.
1/2 1.3 1-6/10 2 2-1/4
3/4 1.9 2-1/2 2-8/10 3-1/2
1 2.5 3-2/10 4 4-1/2
1-1/2 3.6 4-1/2 5-6/10 6
2 4.1 5 6 7
3 5.8 8 8 10
5 9.2 12 15 17-1/2
7-1/2 13.3 17-1/2 20 25
10 17 20 25 30
15 25 30 40 45
20 33 40 50 60
25 41 50 60 70
30 48 60 80 90
40 68 80 100 125
50 79 90 125 150
60 93 110 150 175
75 116 150 175 200
100 150 175 225 250
125 189 250 300 350
150 218 300 350 400
200 291 350 450 500
Full Recommended Fuse Ampere Rating
Motor Load Motor Acceleration Times
HP Amperes Minimum Typical Heavy Load
at 460V 2 sec. 5 sec. Over 5 sec.
1/2 1.1 1-1/2 1-6/10 2
3/4 1.6 2 2-1/4 3
1 2.1 2-1/2 3-2/10 4
1-1/2 3 3-1/2 4-1/2 5-6/10
2 3.4 4 5 6
3 4.8 6 8 9
5 7.6 10 12 15
7-1/2 11 15 15 20
10 14 17-1/2 20 25
15 21 25 30 40
20 27 35 40 50
25 34 40 50 60
30 40 50 60 70
40 52 70 80 90
50 65 80 100 125
60 77 100 125 150
75 96 125 150 175
100 124 175 200 250
125 156 200 225 300
150 180 225 250 350
200 240 300 350 450
250 302 400 450 600
300 361 450 600 -
460 Volt Three Phase Class J AJT Fuses
Full Recommended Fuse Ampere Rating
Motor Load Motor Acceleration Times
HP Amperes Minimum Typical Heavy Load
at 575V 2 sec. 5 sec. Over 5 sec.
1/2 .9 1-1/4 1-1/2 1-6/10
3/4 1.3 1-6/10 2 1-1/2
1 1.7 2-1/4 2-1/2 3
1-1/2 2.4 3 3-1/2 4-1/2
2 2.7 3-2/10 4 5
3 3.9 5 6 7
5 6.1 8 9 12
7-1/2 9 12 15 17-1/2
10 11 15 17-1/2 20
15 17 20 25 30
20 22 30 35 35
25 27 35 40 50
30 32 40 50 60
40 41 50 60 70
50 52 70 80 90
60 62 80 90 110
75 77 100 125 150
100 99 125 150 175
125 125 150 200 225
150 144 175 225 250
200 192 250 300 350
250 240 300 350 400
300 289 350 450 500
Minimum - Minimum sizing may not be heavy enough for
motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate
with NEMA Class 20 overload relays. Suitable for
motor acceleration times up to 5 seconds.
Heavy Load - In accordance with Table 430-152. If this
fuse is not sufficient to start the load, it may
be increased to a maximum of 225% of full-
load amperes (430-52 Exc. 2b). Use this col-
umn for Design E Motors.
Three Phase Motor Fuse Selection Three Phase Motor Fuse Selection