C-TRIP CHARACTERISTICS ONE POLE ONE POLE PLUS NEUTRAL 1C 2CN Application Examples: Low inrush motors, lighting, wiring protection, appliances, business equipment, and control circuit applications. Relatively long thermal trip delay and medium magnetic trip point. Type Designation 2 -- (a) C -- (b) N -- (c) U -- (d) 60 -- (e) (a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current Approvals: UL508 Listed Rated Current Type/ Cat. No. 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 1CU03 1CU05 1CU075 NA 1CU1 1CU1.6 1CU2 1CU2.5 1CU3 1CU3.5 1CU4 1CU5 1CU6 1CU8 1CU10 NA NA 1CU13 1CU15 1CU16 1CU20 1CU25 1CU30 1CU32 1CU40 1CU50 1CU60 1CU63 Approvals UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * Type/ Cat. No. 2CNU03 2CNU05 2CNU075 NA 2CNU1 2CNU1.6 2CNU2 2CNU2.5 2CNU3 2CNU3.5 2CNU4 2CNU5 2CNU6 2CNU8 2CNU10 NA NA 2CNU13 2CNU15 2CNU16 2CNU20 2CNU25 2CNU30 2CNU32 2CNU40 2CNU50 2CNU60 2CNU63 Approvals UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * Voltage Rating 277VAC 277VAC Interrupting Capacity (UL/CSA - Ratings) 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB Group Short Circuit (UL/CSA - Ratings) 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required Interrupting Capacity (VDE - Ratings) 0.3-63A (RC): 10kA 0.3-63A (RC): 10kA Mechanical Endurance 10000 ON/OFF operations 10000 ON/OFF operations Calibration Temperature 40C (104F) 40C (104F) Standard Pack and Weight 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Terminal Size Acceptability Top: 18-3 AWG; Bottom: 18-2 AWG Top: 18-3 AWG; Bottom: 18-2 AWG Terminal Torque 20 lb.in. 20 lb.in. Basic Dimensions (Elevation View) Not European standard rating. Please refer to page 21 for specific applications. DC rating (Manufacturer's self certification): One pole 48VDC, two pole series 125VDC * VDE pending 91.5 mm (3.60 in.) 17.5 mm (0.69 in.) 91.5 mm (3.60 in.) 35 mm (1.38 in.) Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 10 TWO POLE THREE POLE Basic Dimensions (side view) 35 mm (1.38 in.) UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL * * * UL * 60 40 UL UL UL Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC 4 1 UL UL UL UL UL UL 10 4 1 0.4 10-1 UL 4x10-2 UL UL UL 10-2 4x10-3 10-3 1 2 3 4 5 6 8 10 20 40 100 Multiple of Rated Current UL UL V-EA-C Trip 13A Through 63A Rated Current UL UL 1.13-1.45xIN 60 40 UL UL UL UL UL * * * 10 Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC 4 1 UL * 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 0.3-63A (RC): 10kA 10000 ON/OFF operations 10000 ON/OFF operations 40C (104F) 40C (104F) 5/1.4kg (3.1 lb.) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. 20 lb.in. 35 mm (1.38 in.) 10 UL 480Y/277VAC 91.5 mm (3.60 in.) 1.13-1.45xIN Minutes 3CU03 3CU05 3CU075 NA 3CU1 3CU1.6 3CU2 3CU2.5 3CU3 3CU3.5 3CU4 3CU5 3CU6 3CU8 3CU10 NA NA 3CU13 3CU15 3CU16 3CU20 3CU25 3CU30 3CU32 3CU40 3CU50 3CU60 3CU63 UL V-EA-C Trip 0.3A Through 10A Rated Current Tripping time t 2CU03 2CU05 2CU075 NA 2CU1 2CU1.6 2CU2 2CU2.5 2CU3 2CU3.5 2CU4 2CU5 2CU6 2CU8 2CU10 NA NA 2CU13 2CU15 2CU16 2CU20 2CU25 2CU30 2CU32 2CU40 2CU50 2CU60 2CU63 Approvals Seconds Type/ Cat. No. Approvals Minutes 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A Type/ Cat. No. 70 mm (2.76 in.) Tripping time t Rated Current 3C 10 4 1 0.4 10-1 4x10-2 Seconds 2C 10-2 4x10-3 10-3 1 2 3 4 5 6 8 10 20 40 100 Multiple of Rated Current "C" Magnetic Trip Parameters Rated current 0.3A to 63A. 1. Hold for a minimum of 100ms at surge of 5 times rated current. 91.5 mm (3.60 in.) 52.5 mm (2.07 in.) 2. Trip in under 100ms at 10 times rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech. Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 11 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Altech: 4C.40 2CR6 2CR8 2CR3 2CR5 2CR1 3CR1 4CU32 4CU30 4CU35 4CU25 3CR30 3CR10 3CR20 3C.32 4CNU50 4CNU40 1CR2 1CR6 1CR4 1CR3 1CR5 1CR1 2CR20 2CR25 2CR40 2CR30 2CR15 2CR10 2CR13 2C.25 2C.16 2C5.0 1CR20 1CR05 1CR15 1CR16 1CR10