Thermal-Magnetic Overcurrent Circuit Breaker 3200 Description Single pole thermal-magnetic circuit breaker with tease-free, trip-free, press-to-reset, snap action mechanism and additional manual release (M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A sockets 10 and 16. Approved to CBE standard EN 60934 (IEC 60934). Typical applications Control equipment, extra-low voltage wiring systems and components. 1 Ordering information 3200-... Type No. 3200 plug-in Current ratings 0.05...25 A 3200 - 5 A Technical data ordering example Standard current ratings and typical internal resistances Current rating (A) Internal resistance () Current rating (A) Internal resistance () 0.05 534 4 0.141 0.1 149 5 0.107 0.2 56 6 0.060 0.3 24.2 7 0.049 0.4 13.6 8 < 0.02 0.5 8.1 10 < 0.02 0.6 5.25 12 < 0.02 0.8 3.55 14 < 0.02 For further details please Voltage rating Current ratings Typical life Ambient temperature Insulation co-ordination (IEC 60664 and 60664 A) Dielectric strength (IEC 60664 and 60664A) operating area Insulation resistance Interrupting capacity Icn Degree of protection (IEC 60529/DIN 40050) Vibration 1 2.02 15 < 0.02 1.5 0.90 16 < 0.02 2 0.51 18 < 0.02 Shock 2.5 0.36 20 < 0.02 Corrosion 3 0.23 25 < 0.02 Humidity Mass Approvals Authority Standard Rated voltage Current ratings VDE IEC/EN 60934 AC 240 V DC 28 V 0.05...25 A 0.05...25 A 1833 www.e-t-a.de see chapter: Technical Information AC 240 V, 50/60 Hz; DC 28 V 0.05...25 A 500 operations at 1 x IN, inductive 4,000 operations at 1 x IN, resistive -30...+60 C (-22...+140 F) rated impulse pollution withstand voltage degree 2.5 kV 2 reinforced insulation in operating area test voltage AC 3,000 V double insulation > 100 M (DC 500 V) 0.05...0.8 A self-limiting 1...2 A 200 A 2.5...25 A 400 A operating area IP40 terminal area IP00 5 g (57-500 Hz), 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis 25 g (11 ms) to IEC 60068-2-27, test Ea 96 hours at 5 % salt mist to IEC 60068-2-11, test Ka 240 hours at 95 % RH to IEC 60068-2-78, test Cab approx. 50 g 1 Thermal-Magnetic Overcurrent Circuit Breaker 3200 Dimensions Internal connection diagram line 1 15.5 .610 OFF o13 .512 ON 10 .394 o9.5 .374 48.5 1.91 I > 2 Installation drawing 19 .748 current rating in A operating area (reinforced insulation) 11 .433 2 14 .551 43 1.69 50 1.97 1 43 1.69 9.6 .378 19 .748 34.5 1.36 1 2 1 2 6 .236 Typical time/current characteristics 0.05...7 A AC/DC 1) 8...16 A AC/DC 1) 18...25 A 1000 1000 1000 100 100 100 10 1 Trip time in seconds 10000 Trip time in seconds 10000 Trip time in seconds 10000 10 1 10 1 0.1 0.1 0.1 0.01 0.01 0.01 0.001 0.001 1 2 +60 C +140 F +23 C +73.4 F -30 C -22 F Ambient F temp. C -22 -30 -4 -20 +14 -10 +32 +73.4 +86 0 +23 +30 Derating factor 0.76 0.79 0.83 0.88 1 0.001 1 4 6 8 10 20 40 60 80 100 ... times rated current AC/DC 1) 1) 2 4 6 8 10 20 40 60 80 100 ... times rated current 1 2 4 6 8 10 20 40 60 80 100 ... times rated current Magnetic tripping currents are inceased by 20 % on DC supplies. +104 +122 +140 The time/current characteristic curve depends on the ambient temperature +40 +50 +60 prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section 1.04 1.11 1.19 1.29 Technical information. This is a metric design and millimeter dimensions take precedence ( mm ) inch 2 www.e-t-a.de 1833 Thermal-Magnetic Overcurrent Circuit Breaker 3200 Accessories 10R-A10 19 .748 50 1.97 8 .315 21 22 21 9.5 .374 1.5 .059 14.5 .571 1 27 1.06 o2.5 .099 50 pin lugs to DIN 46230 tinned copper 7 .276 ~70 ~2.76 12 22 11 8 .315 59 2.32 M5 x 12 o4 .157 Connector bus links -K10 X 210 589 01/ 2.5 mm2, (AWG 14) (black) up to 20 A max. load X 210 589 02/ 1.5 mm2, (AWG 16) (brown) up to 13 A max. load for sockets 10R-P10, 10R-A10 and 16 blade terminal DIN 46244-A6.3-0.8 (QC .250) wire cross sectional areas 2 x max. 2.5 mm2 (AWG 14) stranded 2 x max. 4 mm2 (AWG 12) solid 27.5 1.08 14 .551 42 1.65 30 1.18 12 blade terminal DIN 46244-A6.3-0.8 (QC .250) Terminal for mounting rack (DIN/EN 50 035-G32) X 200 800 01 for sockets 10R 12 .472 7 .276 11 68 2.68 6 .236 15 .591 45 1.77 75 2.95 7.5 .295 Blanking plug Y 301 477 01 for sockets 10R-P10/K10/A10 12 .472 21 12 11 5.6 .220 50 1.97 9.5 .374 22 30 1.18 1 .039 10R-P10 wire cross sectional areas 2 x max. 2.5 mm2 (AWG 14) stranded 2 x max. 4 mm2 (AWG 12) solid max. tightening torque of terminal screw: 1.2 Nm max. tightening torque 13 of mounting screw: 2.5 Nm .512 12 1 .472 .039 9.5 .374 Sockets 10R-K10 Bus bars for sockets 10... (up to 20 A max. load) Y 301 166 02, 2-way Y 301 166 01, 4-way Connector bus links -P10 X 210 588 01/ 1.5 mm2, (AWG 16) (brown) up to 13 A max. load X 210 588 02/ 2.5 mm2, (AWG 14) (black) up to 20 A max. load X 210 588 03/ 2.5 mm2, (AWG 14) (red) up to 20 A max. load X 210 588 04/ 2.5 mm2, (AWG 14) (blue) up to 20 A max. load for sockets 10R-P10, 10R-A10 12.5 .492 8.5 .335 4.2 .165 2.9 .114 7.9 .311 15 thickness = 0.8 mm .031 in. .591 22.9 .902 15 15 15 .591 .591 .591 52.9 2.08 100 quick-connect tabs 6.3 (.250) DIN 46247 tinned brass, insulated ~70 ~2.76 Socket 16 (up to 16 A max. load) symmetrical rail EN 50022-35x7.5 15 .591 1.5 .059 38.5 1.52 39.5 1.56 32 1.26 70 2.76 52 2.05 Adapter for socket 16 X 200 409 01 for track mounting to EN 50035-G32 (G profile) on request sockets individually (de)mountable This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. 1833 www.e-t-a.de 3 1 4 www.e-t-a.de 1833