Thermal-Magnetic Overcurrent Circuit Breaker 3200
www.e-t-a.de
1833
1
1
Description
Typical applications
Ordering information
Approvals
Technical data
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
press-to-reset, snap action mechanism and additional manual release
(M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A
sockets 10 and 16.
Approved to CBE standard EN 60934 (IEC 60934).
Control equipment, extra-low voltage wiring systems and components.
3200-...
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 28 V
Current ratings 0.05...25 A
Typical life 500 operations at 1 x IN, inductive
4,000 operations at 1 x IN, resistive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V double insulation
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity Icn 0.05...0.8 A self-limiting
1...2 A 200 A
2.5...25 A 400 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 50 g
Standard current ratings and typical internal resistances
Type No.
3200 plug-in
Current ratings
0.05...25 A
3200 - 5 A ordering example
Current
rating (A)
Internal
resistance (Ω)
Current
rating (A)
Internal
resistance (Ω)
0.05 534 4 0.141
0.1 149 5 0.107
0.2 56 6 0.060
0.3 24.2 7 0.049
0.4 13.6 8 < 0.02
0.5 8.1 10 < 0.02
0.6 5.25 12 < 0.02
0.8 3.55 14 < 0.02
1 2.02 15 < 0.02
1.5 0.90 16 < 0.02
2 0.51 18 < 0.02
2.5 0.36 20 < 0.02
3 0.23 25 < 0.02
Authority Standard Rated voltage Current ratings
VDE IEC/EN 60934 AC 240 V
DC 28 V 0.05...25 A
0.05...25 A
Thermal-Magnetic Overcurrent Circuit Breaker 3200
www.e-t-a.de 1833
2
1
Ambient °F
temp. °C
-22
-30 -4
-20 +14
-10 +32
0+73.4
+23 +86
+30 +104
+40 +122
+50 +140
+60
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Derating factor 0.76 0.79 0.83 0.88 1 1.04 1.11 1.19 1.29
Dimensions
1.69
OFF
ON
15.5
10
ø9.5
48.5
9.6
19
12
ø13
43 current rating in A
50
19
14
11
2
.374
.748
.378 1.91 .394
.610
.433
1.97
.748
.551
.512
line 1
2
I>
Installation drawing
12
operating area
(reinforced insulation)
43
6
34.5
1.36
1.69
.236
Typical time/current characteristics
+60 °C
+140 °F
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
+23 °C
+73.4 °F
-30 °C
-22 °F
0.05…7 A AC/DC
1)
1)
Magnetic tripping currents are inceased by 20 % on DC supplies.
18…25 A AC/DC
1)
8…16 A AC/DC
1)
Internal connection diagram
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Thermal-Magnetic Overcurrent Circuit Breaker 3200
www.e-t-a.de
1833
3
1
Thermal-Magnetic Overcurrent Circuit Breaker 3200
Accessories
Adapter
for socket 16
X 200 409 01
for track mounting
to EN 50035-G32
(G profile)
on request
12.5
22.9
4.2
7.9
2.9
8.5
15
thickness = 0.8 mm
.031 in.
15 15 15
52.9
.165
.311
.492
.114
.335
.591
.902
.591 .591 .591
2.08
Bus bars for sockets 10… (up to 20 A max. load)
Y 301 166 02, 2-way Y 301 166 01, 4-way
Sockets 10R-K10
Socket 16
(up to 16 A max. load)
wire cross sectional areas
2 x max. 2.5 mm
2
(AWG 14) stranded
2 x max. 4 mm
2
(AWG 12) solid
max. tightening torque of terminal screw: 1.2 Nm
blade terminal
DIN 46244-A6.3-0.8
(QC .250)
45
130 1
5.6
9.5
50
7.5 15
75
12
13
12
6
68
8
59
8
7
21 22
11 12
21 22
11 12
21 22
11 12
.039 .039
1.18
.220
.374
1.97
.295 .591
1.77
2.95
.472
.512
.472
.236
7
.276
blade terminal
DIN 46244-A6.3-0.8
(QC .250)
2.68
.315
.315
10R-P10
10R-A10
2.32
.276
symmetrical rail
EN 50022-35x7.5
32
39.5
70
52
38.5
15 1.5
sockets individually
(de)mountable
.591 .059
1.52
2.05
2.76
1.26
1.56
wire cross sectional areas
2 x max. 2.5 mm2 (AWG 14) stranded
2 x max. 4 mm2 (AWG 12) solid
max. tightening torque
of mounting screw: 2.5 Nm
100 quick-connect tabs 6.3 (.250)
DIN 46247 tinned brass,
insulated
~2.76
50 pin lugs to
DIN 46230
tinned copper
ø2.5
.099
~70
12 1.5
19
309.5
50
42
ø4
14.5
14
27.5
M5 x 12
9.5
27
1.65
1.18
.374
.748
1.97
.157
.571
.374
.059
1.08
.551
1.06
.472
Terminal for mounting rack
(DIN/EN 50 035-G32)
X 200 800 01
for sockets 10R
Blanking plug
Y
301 477 01
for sockets 10R-P10/K10/A10
Connector bus links -K10
X 210 589 01/ 2.5 mm2, (AWG 14) (black) up to 20 A max. load
X 210 589 02/ 1.5 mm2, (AWG 16) (brown) up to 13 A max. load
for sockets 10R-P10, 10R-A10 and 16
Connector bus links -P10
X 210 588 01/ 1.5 mm2, (AWG 16) (brown) up to 13 A max. load
X 210 588 02/ 2.5 mm2, (AWG 14) (black) up to 20 A max. load
X 210 588 03/ 2.5 mm2, (AWG 14) (red) up to 20 A max. load
X 210 588 04/ 2.5 mm2, (AWG 14) (blue) up to 20 A max. load
for sockets 10R-P10, 10R-A10
~2.76
~70
This is a metric design and millimeter dimensions take precedence ( mm )
inch
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
www.e-t-a.de 1833
4
1